Pepperl+Fuchs Z788 Zener Barrier, 2-Channel, Asymmetrical
Description
Pepperl+Fuchs Z788 overview
The Pepperl+Fuchs Z788 is a two-channel DC zener barrier with positive polarity from the Z-System of Pepperl+Fuchs. It prevents the transfer of unacceptably high energy from the safe area into the hazardous area. The zener diodes in the barrier are connected in the reverse direction: in normal operation the breakdown voltage is never reached, but if a fault in the safe area pushes the voltage above that level, the diodes conduct and the fuse blows. Because the anodes of the diodes are grounded, the barrier has positive polarity.
The Z788 is an asymmetrical version. One channel is designed for a higher working voltage and the other for a lower one, which optimises applications that have different voltage levels with respect to ground potential. The datasheet specifies a working voltage of 26.5 V on one channel and 6.5 V on the other, both at 10 microamperes, series resistance of maximum 327 ohm and 64 ohm and a 50 mA fuse. The Z788 mounts on a 35 mm DIN rail with a modular terminal housing 12.5 mm wide.
Key features of the Pepperl+Fuchs Z788
- Two channels, DC version, positive polarity, asymmetrical design
- Working voltage 26.5 V and 6.5 V at 10 microamperes; maximum series resistance 327 ohm and 64 ohm
- Fuse rating 50 mA, with nominal resistance of 300 ohm on terminals 1 and 8 and 50 ohm on terminals 4 and 5
- Hazardous-area marking (1)GD, (M1) with [Ex ia Ga] IIC, [Ex ia Da] IIIC and [Ex ia Ma] I; certificate BAS 01 ATEX 7005
- Also marked Ex nA IIC T4 Gc (certificate TUV 99 ATEX 1484 X) for Zone 2 installation of the barrier itself
- IECEx certificates BAS 09.0142 and BAS 17.0091X; FM and UL control drawings listed
- DIN rail mountable on 35 mm rail; screw terminals for up to 2 x 2.5 square mm
- Ambient temperature -20 to 60 degrees C, IP20, mass approximately 150 g
Z788 technical specifications
Data below come from the Z788 datasheet released on 22 July 2026.
| Parameter | Value |
|---|---|
| Model | Z788 zener barrier, 2-channel, DC version, positive polarity, asymmetrical |
| Nominal resistance | Terminals 1, 8: 300 ohm; terminals 4, 5: 50 ohm |
| Series resistance | Terminals 1, 8: max. 327 ohm; terminals 4, 5: max. 64 ohm |
| Fuse rating | 50 mA |
| Working voltage, supply loop | Terminals 7, 8: max. 27 V; terminals 5, 6: max. 8.6 V |
| Working voltage, measurement loop | Terminals 7, 8: max. 26.5 V at 10 microamperes; terminals 5, 6: max. 6.5 V at 10 microamperes |
| Hazardous-area terminals | 1, 2 and 3, 4 |
| Safe-area terminals | 5, 6 and 7, 8 |
| Certificate | BAS 01 ATEX 7005 |
| Marking | (1) II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
| Voltage Uo | Terminals 1, 2: 28 V; terminals 3, 4: 9.56 V |
| Current Io | Terminals 1, 2: 93 mA; terminals 3, 4: 195 mA |
| Power Po | Terminals 1, 2: 650 mW; terminals 3, 4: 470 mW |
| Maximum safe voltage Um | 250 V |
| Minimum series resistance | Terminals 1, 2: 301 ohm; terminals 3, 4: 49 ohm |
| Zone 2 certificate | TUV 99 ATEX 1484 X, marking Ex nA IIC T4 Gc |
| IECEx | IECEx BAS 09.0142; IECEx BAS 17.0091X; Ex ec IIC T4 Gc |
| FM / UL | FM control drawing 116-0118; UL (cULus) control drawing 116-0139 |
| Ambient temperature | -20 to 60 degrees C; storage -25 to 70 degrees C |
| Relative humidity | Maximum 75 percent, without condensation |
| Degree of protection | IP20 |
| Connection | Screw terminals, core cross section max. 2 x 2.5 square mm |
| Dimensions | 12.5 x 115 x 116 mm (W x H x D) |
| Mass | Approximately 150 g |
| Mounting | On 35 mm DIN mounting rail according to EN 60715:2001 |
For the detailed intrinsic-safety parameters when channels are connected in series or in parallel, the datasheet refers to the zener barrier certificate; asymmetrical barriers have increased or decreased parameters depending on the connection. Always read the certificate for the final combination of Uo, Io and Po before approving a loop.
Typical applications in oil and gas, utilities, water and manufacturing
Zener barriers like the Z788 are used as an economical interface between safe-area equipment and intrinsically safe field devices. In oil and gas plants in Oman, the Z788 can protect circuits for thermocouple and resistance-type devices, switch contacts and low-power sensors on tanks, pumps and pipelines. The asymmetrical design suits circuits where one conductor works at a different potential to ground than the other.
In utilities, water treatment and manufacturing plants across the GCC, the Z788 is found in older cabinets and upgrades where Z-System modules are already installed. Its low cost and absence of a power supply make it attractive, but the user must provide a high-quality intrinsic safety earth connection because the zener diodes shunt fault energy to ground.
Selection and compatibility notes for Z788
Check the polarity, the voltage levels with respect to ground and the series resistance of both channels against the field device and the controller. With maximum series resistance of 327 ohm on the high-voltage channel and 64 ohm on the low-voltage channel, signal accuracy and loop compliance must be calculated for your application. Compare Uo, Io and Po with the field apparatus and the cable parameters.
A shunt-diode barrier needs a dedicated intrinsic safety earth with low impedance. If a grounded circuit is unacceptable, choose a galvanic isolator instead. If you need symmetrical channels, other barriers in the Z-System are available; confirm the model before ordering a replacement.
Installation and commissioning
Before mounting the Z788, confirm the hazardous-area apparatus and the cable parameters against the entity values on the nameplate and in the manufacturer certificate, and decide where the intrinsic safety earth will be taken. Mount the unit on the 35 mm top-hat DIN rail in a clean enclosure or cabinet in the safe area, keeping hazardous-area and safe-area wiring physically separated and clearly labelled. Mount the Z788 on the 35 mm DIN rail, connect the shield and ground connection indicated in the assembly diagram, and use the tag holder for identification. Use only the terminals for hazardous-area and safe-area connections shown in the datasheet.
Wire the Z788 strictly to the terminal table in the datasheet, tighten the terminal screws to the specified torque and check that no strands are left outside the clamp. Where the unit carries a certificate, the earth connection and the rail must meet the requirements stated there. After wiring, apply the supply, check the power indication, and simulate the field signal to prove the end-to-end loop before the plant is declared ready. Record the as-found readings for future loop checks of the Z788.
Maintenance and service life
The Z788 has no user-serviceable parts, so maintenance is mainly periodic inspection. During planned shutdowns, inspect terminals for corrosion and looseness, verify the supply voltage at the unit, and repeat the loop check recorded at commissioning. In coastal or humid locations around Muscat, Sohar and Duqm, a sealed or purged cabinet with a clean, dry interior greatly extends the life of any electronic interface such as the Z788.
If a loop drifts outside its tolerance or the unit shows no power indication with a healthy supply, replace the module rather than attempting repair, and keep the replacement documentation with the loop folder. Because certified intrinsically safe equipment must not be modified, any change in cabling, load or hazardous-area device should be re-assessed against the Z788 entity parameters before it is put into service.
Since the Z788 relies on a fuse, a blown fuse means the barrier has done its job; it must not be repaired but replaced, and the reason for the fault should be investigated first. Also verify the earth connection periodically.
Related products and ordering notes
Customers who enquire about the Z788 often also need matching accessories and neighbouring models from the same family, such as other Z-System zener barriers, isolating barriers of the KFD and KCD families and DIN rail accessories. Please tell us the existing barrier model if you are replacing a unit.
When you send an enquiry for the Z788, please quote the full part number exactly as printed on the nameplate, the quantity, and the intended application. If you are replacing an installed unit, a photograph of the nameplate helps us confirm the Z788 you need. Our team can arrange a quotation with delivery to Oman and across the GCC.
Frequently asked questions about Z788
The Z788 is a two-channel positive DC zener barrier with asymmetrical channels, a 50 mA fuse, maximum series resistance of 327 and 64 ohm, ATEX and IECEx certification and DIN rail mounting. It needs a high-integrity earth and is rated IP20 for cabinet use.
Documents and quotation
A copy of the datasheet for the Z788 is available on this page for your engineering review. To request a quotation, send the RFQ with the part number Z788, the quantity, the delivery location and any certification or documentation requirements, and we will respond with availability and lead time. Please review the specification against your loop or system requirements before ordering.
Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with Pepperl+Fuchs. Product names and part numbers are used only to identify the item you ask for.
Datasheets & Documents
- Datasheet Z788 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Pepperl+Fuchs is a German manufacturer of industrial sensors and explosion protection equipment, founded in 1945 in Mannheim by Walter Pepperl and Ludwig Fuchs as a radio repair shop. Defective transformers led them into manufacturing, and the company developed its first proximity switch in the late 1950s. Pepperl+Fuchs is headquartered in Mannheim and is a pioneer of intrinsically safe electrical equipment for hazardous areas.
Seven Star LLC lists Pepperl+Fuchs sensors, isolated barriers, power supplies and hazardous-area mobile devices, and supplies them to instrument and automation teams in Oman by exact model designation.
Pepperl+Fuchs company profile
| Founded | 1945, Mannheim-Sandhofen, Germany, by Walter Pepperl and Ludwig Fuchs |
|---|---|
| Headquarters | Mannheim, Germany |
| Ownership | Privately owned (Pepperl+Fuchs SE) |
| Origins | Radio repair workshop that began making replacement transformers |
| Product families | Inductive, capacitive, ultrasonic and photoelectric sensors, rotary encoders, R2000 LiDAR scanners, KFD and HiC isolated barriers, Zener barriers, remote I/O, purge and pressurization systems, Ex-rated enclosures |
Milestones
- 1945: Walter Pepperl and Ludwig Fuchs open their radio repair shop in Mannheim.
- 1958: The first proximity switch is developed (some company sources say 1959).
Pepperl+Fuchs product families on this page
On the interface side there are two systems. The K-System mounts on DIN rail and is represented here by the KFD2-UT2-Ex2 universal temperature converter. The H-System plugs into termination boards and is represented by the HiD2030 SMART transmitter power supply with HART. The PS1000-A6-24.20 is a 24 VDC, 20 A power supply for cabinets. Sensors listed include the NJ2-12GK-SN NAMUR inductive sensor, the R101 retro-reflective photoelectric sensor and the R2000 2-D LiDAR scanner. For field staff there are the Tab-Ex 05 DZ1 tablet for Zone 1/21 areas and the Smart-Ex 03 DZ2 smartphone for Zone 2/22 and Division 2 areas.
Where Pepperl+Fuchs equipment is used
Isolated barriers sit between field instruments in Zone 0 or Zone 1 and the DCS or safety system in refineries, gas plants and chemical works. NAMUR sensors report valve position and machine states in classified areas. Photoelectric sensors and LiDAR scanners work in conveying, packaging, warehousing and vehicle guidance. Ex-rated tablets and phones are carried on operator rounds and maintenance jobs.
Pepperl+Fuchs products we list
Ordering Pepperl+Fuchs parts: what we need
Send the complete model designation as printed on the device, including every suffix; a single letter can change the supply voltage or the output type. Add the part number if the label shows one. For barriers, tell us the field device and signal type, the number of channels and whether the safety loop needs a SIL-assessed module. For mobile devices, state the zone or division and the regional radio version.
Facts checked against Pepperl+Fuchs's own chronicle pages, October 2026.
Browse Pepperl+Fuchs products by category: Sensors & Transmitters, Industrial Computer, Isolator & Barrier, Power Modules.
FAQ
Questions about the Pepperl+Fuchs Z788 Zener Barrier, 2-Channel,
Answers from our engineering team on installation, compatibility and integration.
01What is the Z788 used for?
It is a two-channel DC zener barrier with positive polarity that limits energy from the safe area to intrinsically safe circuits in a hazardous area.
02Why is the Z788 called asymmetrical?
The datasheet describes it as an asymmetrical version with different voltage levels on its two channels, 26.5 V and 6.5 V working voltage, to optimise applications with different potentials to ground.
03What fuse does the Z788 have?
The fuse rating is 50 mA, and the series resistance is at most 327 ohm on terminals 1 and 8 and at most 64 ohm on terminals 4 and 5.
04Does the Z788 need an earth connection?
Yes. Zener barriers divert fault energy through grounded diodes, so a reliable intrinsic safety earth is essential.
05How do I order the Z788?
Send an RFQ with the part number Z788, quantity and delivery location in Oman or the GCC, and Seven Star LLC will reply with availability and lead time.


















Reviews