Pepperl+Fuchs KFD2-CRG2-1.D Transmitter Power Supply with Relays

Description

KFD2-CRG2-1.D transmitter power supply with display and two alarm relays

The KFD2-CRG2-1.D powers a 2-wire or 3-wire transmitter, or accepts a 4-20 mA current source, and gives the control system an isolated current output together with two relay alarm contacts. A display shows the measurement in engineering units and a keypad lets the operator scale and configure the module. A linearization function with up to 20 points corrects non-linear signals, such as a level that has to be converted to volume in a tank.

Seven Star LLC supplies the KFD2-CRG2-1.D in Oman and the GCC as an independent supplier in Muscat. The sections below explain the design, the limits and the points to check before ordering.

KFD2-CRG2-1.D type code

The KFD2-CRG2-1.D is a type designation of the Pepperl+Fuchs K-System, named in the datasheet as a transmitter power supply, a 1-channel signal conditioner with 24 V DC supply through the Power Rail. The housing is 40 mm wide because it holds two relays and a display.

Programmable high and low alarms, adjustable energized and de-energized delays of 0 to 250 seconds and line fault detection distinguish this module from the plain STC5 supplies, which have no relays or display.

Technical specifications of the KFD2-CRG2-1.D

Parameter Specification
Manufacturer / part number Pepperl+Fuchs / KFD2-CRG2-1.D
Function Transmitter power supply with relays and display, 1 channel
Input 0/4 … 20 mA; 2-wire, 3-wire transmitters or current sources
Available voltage ≥ 15 V at 20 mA; open circuit 24 V / 33 mA
Input resistance 45 Ω (terminals 2, 3)
Line fault detection Breakage I < 0.2 mA; short-circuit I > 22 mA
Analog output 0 … 20 mA or 4 … 20 mA, load max. 650 Ω; NAMUR NE43 levels
Relay outputs 2 x 250 V AC / 2 A / cos φ ≥ 0.7; 40 V DC / 2 A; life 5 x 107 cycles
Delay 0 … 250 s, adjustable
Linearization Up to 20 points
Accuracy Input < 30 µA; output < 20 µA; reaction time < 650 ms
Supply 20 … 30 V DC, approx. 130 mA; dissipation 2 W; consumption 2.5 W
Approval listed UL approval E223772
Functional safety SIL 2 (IEC/EN 61508 / 61511)
Ambient temperature -20 … 60 °C
Housing Type C2, 40 x 119 x 115 mm, approx. 300 g, 35 mm DIN rail, IP20

How the KFD2-CRG2-1.D works

The module supplies the connected transmitter with at least 15 V at 20 mA, measures the loop current across its 45 Ω input resistance and monitors the loop. Breakage below 0.2 mA and short-circuit above 22 mA are detected. The measured value is digitized and processed with the user scaling and, if required, the linearization table, then output as an active 0/4 to 20 mA signal and compared with the alarm thresholds.

Relay outputs follow the alarm logic with adjustable delays, and the datasheet states that both the relay contacts and the current output can be integrated into safety-relevant circuits. Faults are signalled by LEDs and a separate collective error message output on the Power Rail.

Compared with using a transmitter supply and an external alarm unit, the combination removes one device and one set of wiring, and it keeps the displayed value, the analog output and the alarms consistent because they come from the same measurement.

Positioning the KFD2-CRG2-1.D

Choose the KFD2-CRG2-1.D when a local indication and alarm point is needed together with loop power, for example at a tank level transmitter that also has to trip a pump. The KFD2-STC5-1 is the better choice when HART communication and the lowest cost per loop are required, because it is narrower and focuses on the SMART function.

It shares the Power Rail and power feed accessories with the KFD2-USC-1.D, KFD2-GUT-1.D and KFD2-UFC-1.D.

Selection and ordering checklist for the KFD2-CRG2-1.D

  • Transmitter type and loop current range
  • Scaling, units and whether linearization is needed
  • Alarm limits, hysteresis and delays for the two relays
  • Output range 0 to 20 mA or 4 to 20 mA
  • SIL requirement and safety documentation
  • Supply, rail arrangement and ambient limit

Configuring and maintaining the KFD2-CRG2-1.D

After wiring terminals 1 to 3 for the transmitter and the output and relay terminals, enter the scaling, units and alarm thresholds with the keypad or PACTware. For a tank with a non-linear geometry, enter the linearization points from the tank table. Verify each relay with a simulated input and write down the final parameters.

Maintenance consists of periodic loop verification. Because the module has no user serviceable parts, replace it as a unit and reload the saved configuration.

Typical applications in Oman and the GCC

Transmitter supplies with alarm relays are used on storage tanks, sumps, pressure vessels and header lines in oil and gas, water and power plants, where a local alarm is wanted without involving the DCS. Linearization is particularly useful for horizontal or conical tanks.

Transmitter supplies compared

Based on the datasheets.

Part number Relays Display Notes
KFD2-CRG2-1.D 2 Yes Scaling, linearization, delays
KFD2-STC5-1 None No HART focus, 20 mm
KCD2-STC-1 None No 12.5 mm, DIP switch configuration

Information to send with an RFQ for the KFD2-CRG2-1.D

Send these items for a quotation.

  • Transmitter model and loop range
  • Alarm setpoints and delays
  • Linearization requirement
  • Quantity and delivery date

Documents and quotation

The manufacturer datasheet for the KFD2-CRG2-1.D is attached on this page, so the electrical data, terminal assignment and ambient limits quoted above can be checked against the original document before an order is placed.

Seven Star LLC supplies Pepperl+Fuchs products in Oman and the GCC as an independent supplier in Muscat. Send the quantity, the signal types and the project delivery date, and we will confirm availability and lead time in a written quotation.

Other Models in the Pf Kfd2 D Series Range

Seven Star LLC supplies models from the Pf Kfd2 D Series range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Pepperl+Fuchs KFD2-USC-1.D Signal Converter with Trip ValueIsolator & BarrierView details
Pepperl+Fuchs KFD2-GUT-1.D Temperature Converter, 2 RelaysIsolator & BarrierView details
Pepperl+Fuchs KFD2-UFC-1.D Frequency Converter with Trip ValuesIsolator & BarrierView details
Pepperl+Fuchs KFD2-CRG2-1.D Transmitter Power Supply with RelaysIsolator & BarrierYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Pepperl+Fuchs KFD2-CRG2-1.D Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Pepperl+Fuchs is a German manufacturer of industrial sensors and explosion protection equipment, founded in 1945 in Mannheim by Walter Pepperl and Ludwig Fuchs as a radio repair shop. Defective transformers led them into manufacturing, and the company developed its first proximity switch in the late 1950s. Pepperl+Fuchs is headquartered in Mannheim and is a pioneer of intrinsically safe electrical equipment for hazardous areas.

Seven Star LLC lists Pepperl+Fuchs sensors, isolated barriers, power supplies and hazardous-area mobile devices, and supplies them to instrument and automation teams in Oman by exact model designation.

Pepperl+Fuchs company profile

Founded 1945, Mannheim-Sandhofen, Germany, by Walter Pepperl and Ludwig Fuchs
Headquarters Mannheim, Germany
Ownership Privately owned (Pepperl+Fuchs SE)
Origins Radio repair workshop that began making replacement transformers
Product families Inductive, capacitive, ultrasonic and photoelectric sensors, rotary encoders, R2000 LiDAR scanners, KFD and HiC isolated barriers, Zener barriers, remote I/O, purge and pressurization systems, Ex-rated enclosures

Milestones

  • 1945: Walter Pepperl and Ludwig Fuchs open their radio repair shop in Mannheim.
  • 1958: The first proximity switch is developed (some company sources say 1959).

Pepperl+Fuchs product families on this page

On the interface side there are two systems. The K-System mounts on DIN rail and is represented here by the KFD2-UT2-Ex2 universal temperature converter. The H-System plugs into termination boards and is represented by the HiD2030 SMART transmitter power supply with HART. The PS1000-A6-24.20 is a 24 VDC, 20 A power supply for cabinets. Sensors listed include the NJ2-12GK-SN NAMUR inductive sensor, the R101 retro-reflective photoelectric sensor and the R2000 2-D LiDAR scanner. For field staff there are the Tab-Ex 05 DZ1 tablet for Zone 1/21 areas and the Smart-Ex 03 DZ2 smartphone for Zone 2/22 and Division 2 areas.

Where Pepperl+Fuchs equipment is used

Isolated barriers sit between field instruments in Zone 0 or Zone 1 and the DCS or safety system in refineries, gas plants and chemical works. NAMUR sensors report valve position and machine states in classified areas. Photoelectric sensors and LiDAR scanners work in conveying, packaging, warehousing and vehicle guidance. Ex-rated tablets and phones are carried on operator rounds and maintenance jobs.

Pepperl+Fuchs products we list

Family Examples
Isolator & Barrier HiD2030 SMART Transmitter Power Supply w…, KFD2-SR2-Ex2.W K-System Isolated Switch…, KFD2-UT2-Ex2 Universal Temperature Conve…
Industrial Computers Tab-Ex 05 DZ1 WWAN Hazardous Area Tablet, Smart-Ex® 03 DZ2 smartphone for Zone 2/2…
Inductive Proximity Sensors NJ2-12GK-SN NAMUR Inductive Sensor
Power Modules PS1000-A6-24.20 Power Supply 24 VDC 20 A
Photoelectric Sensors R101 Retro-Reflective Photoelectric Sensor
Laser Distance, LiDAR & Radar Sensors R2000 2-D LiDAR Laser Scanner

Ordering Pepperl+Fuchs parts: what we need

Send the complete model designation as printed on the device, including every suffix; a single letter can change the supply voltage or the output type. Add the part number if the label shows one. For barriers, tell us the field device and signal type, the number of channels and whether the safety loop needs a SIL-assessed module. For mobile devices, state the zone or division and the regional radio version.

Facts checked against Pepperl+Fuchs's own chronicle pages, October 2026.

FAQ

Questions about the Pepperl+Fuchs KFD2-CRG2-1.D Transmitter Power

Answers from our engineering team on installation, compatibility and integration.

01What does the KFD2-CRG2-1.D add compared with a simple transmitter supply?
Two relay alarm outputs with adjustable delays, a display, keypad configuration, scaling and a linearization function of up to 20 points.
02Which transmitters can be connected?
2-wire and 3-wire transmitters and 2-wire current sources with 0/4 to 20 mA signals.
03What delays can be set?
The energized and de-energized delay is adjustable from 0 to 250 seconds.
04Is line fault detection included?
Yes. Breakage is recognised below 0.2 mA and a short circuit above 22 mA.
05How is it configured?
Through the keypad and display or with PACTware via the programming socket.