Brand:

Minimax Zonecheck Sprinkler Flow Switch Test Unit

Description

Test sprinkler flow switches in one minute without discharge

The Minimax Zonecheck is a device for fast functional testing of flow switches in sprinkler systems. It combines the flow switch and an automatic test system in one unit, so the flow switch can be tested remotely while the sprinkler system stays ready for operation.

When Zonecheck is switched on, water in the system is pumped around the flow switch in a circular movement to simulate the flow of one open sprinkler head. A light at the key switch or at the control panel confirms activation of the flow switch. One person can run the test in a maximum of one minute without disturbing the building, and without using fresh water.

Technical specifications

Parameter Specification
Maximum operating pressure 12 bar (175 psi)
Temperature range 5 C to 50 C (40 to 120 F)
Pump supply 1~ 230 V, 50 Hz; full-load current 0.93 A; power rating P1 195 W; IP44
Flow switch contacts 10 A at 125/230 VAC; 2.5 A at 24 VDC; IP54
Triggering flow rate 30 to 57 l/min
Delay time 0 to 30 s
Nominal widths DN 50, 65, 80, 100, 150 and 200
Zonecheck 450, length x width x height (mm) DN 50: 450 x 317 x 265; DN 65: 450 x 325 x 282; DN 80: 450 x 338 x 295; DN 100: 450 x 371 x 320; DN 150: 450 x 421 x 375; DN 200: 450 x 480 x 435
Zonecheck 450 Retrofit, length x width x height (mm) DN 50: 307 x 128 x 394; DN 65: 321 x 146 x 394; DN 80: 332 x 160 x 388; DN 100: 359 x 190 x 388; DN 150: 432 x 256 x 414; DN 200: 500 x 327 x 422
Retrofit kit Automatic test device with pump and spot-drilled clips; key switch or control panel ordered separately
Delivery Flow switch with grooved pipe length painted red, pump, completely assembled; left or right handed

Applications and benefits

Minimax recommends Zonecheck wherever flow switches are required, especially for sprinkler wet systems used for life safety to VdS/CEA 4001 such as theatres, multi-storey and high-rise buildings, and complex pipework. Several flow switches can be activated from one key switch or a control panel, and activation and identification can optionally be extended with MX loop technology.

  • Simplified routine testing from a central location
  • Test time of a maximum of one minute
  • Functional test without operating the sprinkler fire pump
  • Closed water circulation, no fresh water used and no corrosion from fresh water oxygen
  • Year on year cost savings versus the prescribed quarterly flow switch tests

The flow switch contacts are rated 10 A at 125/230 VAC and 2.5 A at 24 VDC with IP54, and the flow switch triggers between 30 and 57 l/min with a delay of 0 to 30 s. The sheet prints approval marks with a note that approvals relate to DN 50 to DN 150, so ask us for the certificate that covers your size. The retrofit kit is an automatic test device with pump and spot-drilled clips for existing sprinkler pipework; the key switch or control panel is ordered separately.

What to confirm before ordering

The datasheet gives overall dimensions per nominal width, so confirm the DN size, left or right handed assembly, and whether you need a complete unit or the retrofit kit for existing flow switches. For deluge systems see the Minimax FSX deluge valve set.

Related Minimax products: Minimax Preaction Sprinkler Double Safety Sprinkler Unit, Minimax MXOne Firefighting Turbine Water Mist Monitor, Minimax OneU 19 Inch Rack Fire Detection and Extinguishing, Minimax Carbon Dioxide CO2 Extinguishing Systems, Minimax FSX Deluge Valve Set (DN 50 to DN 200) and Minimax MX 200 HFC-227ea Fire Extinguishing Systems.

Documents and quotation

The two-page Minimax Zonecheck datasheet PB01We (04.11 print run) is attached. Seven Star LLC is an independent supplier in Muscat; we check the current data with Minimax before quoting. See Fire Fighting for related products.

Datasheets & Documents
  • PDF Datasheet Minimax Zonecheck Datasheet (PB01We, 04.11) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Minimax is a German fire protection company that designs, builds and services fire detection and extinguishing systems for industrial plants, power stations, data centres, warehouses and transport. The brand goes back to 1902, when Wilhelm Graaff launched his conical hand-held Minimax fire extinguisher. Today Minimax is part of the Minimax Viking Group, headquartered in Bad Oldesloe, Germany.

Seven Star LLC is an independent supplier in Oman and lists Minimax fire control panels, detectors, a deluge valve set and the MxSysCon fire control configuration software, supplied with its licence dongle. We also take inquiries for Minimax fire protection components and spare parts identified by part number.

Minimax company profile

Founded 1902, when Wilhelm Graaff introduced the conical Minimax hand fire extinguisher
Headquarters Bad Oldesloe, Schleswig-Holstein, Germany
Ownership Minimax Viking Group; Intermediate Capital Group (ICG) has held more than 90 % since 2018
Group brands Minimax (Europe) and Viking (sprinklers, USA), joined in 2009
Product families Fire detection and extinguishing control panels such as FMZ 5000, sprinkler and deluge systems, water mist, foam, CO2 and inert gas extinguishing systems, portable extinguishers

Milestones

  • 1902: Wilhelm Graaff launches the conical Minimax hand fire extinguisher.
  • 1955: The British Pyrene company buys Minimax.
  • 1969: Preussag AG acquires Minimax and merges it with Selbsttätige Feuerlöschanlagen Gesellschaft of Hamburg.
  • 2009: Minimax acquires the Viking Corporation, forming the Minimax Viking Group.
  • 2014: IK Investment Partners sells the group to KIRKBI and Intermediate Capital Group.
  • 2018: ICG raises its stake to more than 90 % as KIRKBI exits.

Minimax systems the software and parts belong to

The manufacturer's program covers fire detection and extinguishing control panels of the FMZ family and HELIOS aspirating smoke detectors. On the extinguishing side it builds deluge and other water-based systems, Minifog water mist, Oxeo inert gas and carbon dioxide systems, and spark extinguishing. Panel configuration software is tied to a specific panel generation. We did not find the name MxSysCon in the manufacturer's public documents, so the software version has to be checked against your panel type.

Minimax products we list

Family Examples
Fire Fighting Carbon Dioxide CO2 Extinguishing Systems, FSX Deluge Valve Set (DN 50 to DN 200), MX 200 HFC-227ea Fire Extinguishing Syst…, MXOne Firefighting Turbine Water Mist Mo…, OneU 19 Inch Rack Fire Detection and Ext…, Preaction Sprinkler Double Safety Sprink…, Spark Extinguishing Systems for Pneumati…
Logic Controllers Clunid Connect Fire Control Panel Networ…, Clunid FMZ6000 Fire Detection and Exting…, Inveron Hazard Management System Software, SOLID SDE Spark Extinguishing Control Pa…
Fire & Gas Detectors AMX4004 WEA Aspirating Smoke Detector fo…, HELIOS AMX5000 Aspirating Smoke Detector, UniVario YMX5000 Flame and Spark Detecti…
Automation Software MxSysCon Fire Control Configuration Soft…

Ordering Minimax items: what we need

Send the Minimax part number, the type and firmware version of the control panel, and a photo of the panel label. For detectors, nozzles or valves, add the nameplate data and the approval the project specifies. Minimax systems are engineered per site, so a component is only correct when it matches the original system documents. We check that match for buyers across the GCC before the order is placed.

Facts checked against published company histories and the 2014 and 2018 ownership announcements, October 2026.

FAQ

Questions about the Minimax Zonecheck Sprinkler Flow Switch Test Unit

Answers from our engineering team on installation, compatibility and integration.

01What does Zonecheck do?
It tests sprinkler system flow switches automatically and remotely while the system stays ready.
02How long does a test take?
A maximum of one minute, run by one person.
03Does it use fresh water?
No, it uses closed water circulation without consumption of fresh water.
04What pump supply is required?
1~ 230 V, 50 Hz, with a full-load current of 0.93 A and IP44 protection.
05Is there a retrofit option?
Yes, a Zonecheck retrofit kit exists for existing systems that already have flow switches.