- Automation & ControlView all 2,945 products
- Automation Accessories
- AC Drives
- PLC & I/O Cards
- Industrial Communications
- Vibration Monitoring
- Controllers & Data Acquisition
- Isolator & Barrier
- Safety Switches & Guard Locking
- Motor Soft Starters
- CCTV & Security
- Encoders
- Pneumatic Cylinders
- HMI Displays
- Servo Drives
- Industrial Computers
- Machine Vision
- Automation Software
- Robotics
Brand: Yokogawa
Yokogawa EJA510E-JBS4N-012NN Absolute Pressure Transmitter
Description
Yokogawa EJA510E-JBS4N-012NN in one paragraph
Yokogawa EJA510E-JBS4N-012NN is the in-line absolute pressure transmitter from the EJA-E range, configured with a B capsule so that the span can be set anywhere between 0.02 and 2 MPa absolute. Because the reading is referenced to vacuum, the lower range limit is zero and the signal does not drift with the weather the way a gauge reading does. The code JBS4N-012NN picks HART output, a 1/2 NPT female process port, 316L stainless wetted parts with a Hastelloy C-276 diaphragm, an aluminum housing with two 1/2 NPT conduit entries, and leaves out both the integral indicator and the pipe bracket.
It is a bare, plain-vanilla specification, which is exactly why it appears so often on maintenance lists: no indicator to break, no bracket to specify, and the standard wetted-parts combination that passes NACE MR0175 and MR0103 review according to the datasheet.
How to read the suffix of EJA510E-JBS4N-012NN
| Code position | Meaning |
|---|---|
| -J | 4 to 20 mA DC with HART 5 or HART 7 digital communication (selected at ordering) |
| B | Capsule: span 0.02 to 2 MPa |
| S | 316L SST process connector, Hastelloy C-276 diaphragm, 316L SST or F316L SST other wetted parts |
| 4 | Process connection: 1/2 NPT female |
| 1 | Amplifier housing: cast aluminum alloy |
| 2 | Electrical: 1/2 NPT female, two electrical connections, no blind plugs |
| N | Integral indicator: none |
| N | Mounting bracket: none |
Performance figures that belong to the B capsule
Numbers matter more than adjectives here. The B capsule has an upper range limit of 2 MPa abs, a maximum working pressure of 2 MPa abs and an over-pressure rating of 4 MPa abs. Burst pressure is 30 MPa. Reference accuracy is plus or minus 0.055 percent of calibrated span whenever the span is 0.2 MPa or larger; with the optional high accuracy code HAC this tightens to plus or minus 0.04 percent of span. For the absolute-pressure EJA510E, long-term stability is plus or minus 0.2 percent of the upper range limit over ten years.
- Response time 90 ms with damping at zero, including 45 ms dead time; pressure update period 45 ms.
- Damping adjustable from 0.00 to 100.00 s.
- Ambient temperature effect: plus or minus (0.15 percent of span plus 0.15 percent of URL) per 28 degrees C.
- Process temperature minus 40 to 120 degrees C; ambient minus 40 to 85 degrees C (minus 30 to 80 degrees C with an LCD).
- Weight about 1.2 kg without indicator or bracket.
Technical specifications table for EJA510E-JBS4N-012NN
| Item | Value |
|---|---|
| Model | EJA510E absolute pressure transmitter |
| Output | 4 to 20 mA DC, HART 5 or 7 (code J) |
| Capsule | B, span 0.02 to 2 MPa abs, URL 2 MPa abs |
| Max working pressure | 2 MPa abs (290 psia) |
| Over-pressure | 4 MPa abs (580 psia) |
| Burst pressure | 30 MPa |
| Wetted parts | 316L SST connector, Hastelloy C-276 diaphragm |
| Process connection | 1/2 NPT female |
| Housing | Cast aluminum, IP66/IP67, Type 4X |
| Electrical entries | Two 1/2 NPT female, no blind plug |
| Supply voltage | 10.5 to 42 V DC general use (10.5 to 30 V DC intrinsically safe) |
| Load | Up to 550 ohm at 24 V DC |
| Fill fluid | Silicone oil |
| Safety | SIL 2 capable single, SIL 3 dual (IEC 61508) |
Where EJA510E-JBS4N-012NN is used in Oman and the GCC
Absolute pressure is the right variable whenever vacuum or barometric swings would corrupt a gauge reading. Typical Gulf installations are vacuum distillation overheads and ejector suction lines in refineries, deaerator and condenser shell pressure in desalination and power units, and sub-atmospheric steam-jet systems. The 0.02 to 2 MPa abs window also suits compressor suction and interstage monitoring on instrument-air and nitrogen packages, where the reading should be independent of altitude and weather.
Selecting this variant over neighbours
Choose the B capsule when the process stays below 2 MPa abs and you want resolution at low pressure. If the line can reach more than 2 MPa abs the A and B capsules are over-ranged at 4 MPa, so the C capsule is the next step. Choose J rather than D when the control system speaks HART; choose the stainless housing code 2 for offshore or coastal salt air, and the corrosion-resistant aluminum code 3 where a lighter housing is acceptable. Wetted-parts code H is for fluids that attack 316L; here S is used.
Installation and commissioning of EJA510E-JBS4N-012NN
Mount the transmitter with the process port downward or sideways where condensate could collect so that the port cannot trap liquid when measuring gas; the 1/2 NPT female thread needs PTFE tape or paste compatible with the process. Since no bracket is included, fix it directly to a pipe stand or provide a 2-inch bracket separately. Wire through either 1/2 NPT entry, seal the unused one with a rated plug, close the covers tightly, and check the loop with a 250 ohm resistor if you intend to use a HART communicator. After mounting, apply vacuum or atmosphere and trim zero; tilting up to 90 degrees shifts zero by up to 0.21 kPa which can be corrected in the field.
The electronics are designed for self-diagnostics: CPU, hardware and configuration faults, plus pressure and capsule-temperature alarms, drive the output to 110 percent or minus 5 percent depending on the configured failure direction. Keep a calibration record, repeat zero trim at planned shutdowns, and verify the loop with a loop-test command rather than opening the cover in wet weather.
Ordering notes for EJA510E-JBS4N-012NN
When EJA510E-JBS4N-012NN appears on a spare parts list it is usually replacing a unit of the same family that already runs in the plant. Matching the suffix character by character avoids surprises with threads and conduit entries. If your nameplate shows an option code after a slash, such as an ATEX or IECEx approval, a lightning protector or an anti-corrosion coating, mention it in the RFQ so that the quotation covers the right variant. EJA510E-JBS4N-012NN as listed here is the base configuration with no options. The sibling units with indicators, other capsules or male threads are separate part numbers.
Quick answers about EJA510E-JBS4N-012NN
- What does the B in EJA510E-JBS4N-012NN stand for? B is the capsule code. It gives a span of 0.02 to 2 MPa absolute with a 2 MPa upper range limit, 4 MPa over-pressure rating and 30 MPa burst pressure.
- Is EJA510E-JBS4N-012NN supplied with an indicator? No. The ninth suffix position is N, which means no integral digital indicator, and the final N means no mounting bracket.
- Which protocol does the J suffix select? J is a 4 to 20 mA DC output with digital communication, HART 5 or HART 7 selected when ordering. D would be BRAIN and F or G the fieldbus versions.
- What range limits apply to this absolute transmitter? The lower range limit is zero because the EJA510E measures absolute pressure, and the upper range limit of the B capsule is 2 MPa abs.
- Does the 1/2 NPT female connection suit a gas line? Yes, it is a standard female pipe thread. For gas service install it so liquid cannot collect in the port, and use sealing suitable for the process.
Documents and quotation
To receive a quotation for the exact specification above, include the suffix exactly as printed on your nameplate.
The manufacturer datasheet GS 01C31F01-01EN for this model family is attached to the product page as a PDF. When you request a quotation, send the full part number EJA510E-JBS4N-012NN, the quantity, the tag or loop number, the process fluid and any approval code you need such as ATEX, IECEx, FM or CSA. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer. Lead times and availability are confirmed per request.
Datasheets & Documents
- Datasheet Yokogawa EJA510E-JBS4N-012NN Absolute Pressure Transmitter Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Yokogawa is the Japanese measurement and industrial automation company behind the DPharp EJA and EJX pressure transmitters, CENTUM distributed control systems and ProSafe-RS safety systems. Tamisuke Yokogawa set it up in 1915 as an electric meter research institute in Shibuya, Tokyo. It began selling electric meters in 1917, was incorporated as Yokogawa Electric Works in 1920, and has been Yokogawa Electric Corporation since 1986. In 1975 it released CENTUM, which it describes as the world's first distributed control system.
Seven Star LLC is an independent supplier in Muscat. We list Yokogawa transmitters, flowmeters, analysers, controllers, recorders and CENTUM and ProSafe spare modules, and supply them to oil and gas, power, water and process plants in Oman and the GCC by model code.
Yokogawa at a glance
| Established | 1915, Shibuya, Tokyo, by Tamisuke Yokogawa with Ichiro Yokogawa and Shin Aoki |
|---|---|
| Milestones | Electric meters from 1917; incorporated in 1920; CENTUM DCS in 1975; renamed Yokogawa Electric Corporation in 1986 |
| Headquarters | Tokyo, Japan |
| Product families | Pressure and temperature transmitters, magnetic, vortex and Coriolis flowmeters, liquid and gas analysers, controllers and recorders, CENTUM VP DCS, ProSafe-RS safety systems and STARDOM controllers |
Yokogawa products we list
| Family | Models | Typical use |
|---|---|---|
| Pressure and DP transmitters | EJA110E, EJA430E, EJA530E, EJX110A, EJX530A, EJX910A multivariable | Pressure, level and DP flow measurement in process plants |
| Temperature transmitters | YTA610, YTA710 | RTD and thermocouple signals converted to 4-20 mA, HART or fieldbus |
| Flowmeters | ADMAG AXG, ADMAG AXW, ROTAMASS TI, VY vortex, VF701 | Water and conductive liquids, mass flow of hydrocarbons, steam and gas |
| Analysers | TDLS8000 laser gas analyser, FLXA402, FLXA21 DO, E7042UD zirconia cell, K9471DS cover | Combustion O2, in-situ gas analysis, pH, conductivity and dissolved oxygen |
| Controllers and recorders | UT35A/UT32A, UT32A-D, UT55A/UT52A, UT75A, UP35A/UP32A, UP55A, YS1700, GX10/GX20, GP10/GP20, GM10, µR20000 | Single-loop control, furnace programs and data recording |
| Control and safety systems | CP451-10 processor, ADV161, ADV551, node interface unit, ProSafe-RS, ProSafe-RS Lite, ProSafe-SLS, FCN-500 | Spares and expansions for CENTUM DCS, safety systems and STARDOM |
| Battery packs | S9129FA, S9185FA, S9548FA | Memory backup batteries for DCS and controller modules |
The EJA and EJX transmitters use Yokogawa's DPharp sensor: two silicon resonators whose vibration frequency changes with pressure, so the output is a digital frequency rather than an analogue strain signal. The model code describes the instrument completely. In EJA110E, "110" is a differential pressure transmitter, and the letters after the dash set the span, wetted materials, process connection, electrical output and approvals. When you replace a transmitter, sending the full code from the nameplate avoids a mismatch in range or materials.
Where Yokogawa products are used
In Oman and the GCC, Yokogawa transmitters, analysers and control systems are found in oil and gas production, gas processing and LNG, refineries and petrochemical plants, power and desalination stations, and water treatment. Many plants still run CENTUM CS 3000 and CENTUM VP systems that need spare I/O modules and batteries.
Ordering Yokogawa products: what we need
Send the full model and suffix code from the nameplate (for example EJA110E-JMS5J-912NN/KF22) and the style code. For DCS modules, add the module type and system version. For analysers, send the sensor type, measuring range and process conditions.
Facts checked against Yokogawa's corporate history, October 2026.
Browse Yokogawa products by category: PLC & I/O Cards, Flowmeters, Pressure Instrumentation, Automation Accessories, Temperature Instrumentation.
FAQ
Questions about the Yokogawa EJA510E-JBS4N-012NN Absolute Pressure
Answers from our engineering team on installation, compatibility and integration.
01What does the B in EJA510E-JBS4N-012NN stand for?
B is the capsule code. It gives a span of 0.02 to 2 MPa absolute with a 2 MPa upper range limit, 4 MPa over-pressure rating and 30 MPa burst pressure.
02Is EJA510E-JBS4N-012NN supplied with an indicator?
No. The ninth suffix position is N, which means no integral digital indicator, and the final N means no mounting bracket.
03Which protocol does the J suffix select?
J is a 4 to 20 mA DC output with digital communication, HART 5 or HART 7 selected when ordering. D would be BRAIN and F or G the fieldbus versions.
04What range limits apply to this absolute transmitter?
The lower range limit is zero because the EJA510E measures absolute pressure, and the upper range limit of the B capsule is 2 MPa abs.
05Does the 1/2 NPT female connection suit a gas line?
Yes, it is a standard female pipe thread. For gas service install it so liquid cannot collect in the port, and use sealing suitable for the process.


















Reviews