Brand: VEGA
VEGA VEGAPULS 61 Radar Level Sensor 35 m PVDF
Description
VEGA VEGAPULS 61 at a glance
Think of the VEGA VEGAPULS 61 as the straightforward member of the pulse-radar family: a sensor for continuous level measurement of liquids when process conditions are simple, and when the plant wants a price-sensible, easy-to-mount device. Its antenna is encapsulated, so there is no exposed horn to foul, and the wetted parts are limited to PVDF or PP with an FPM process seal. VEGA describes the VEGAPULS 61 as offering simple and versatile mounting, and that is borne out by the choice of a G1½ thread, a 1½ NPT thread, a mounting strap, compression flanges from DN 80 (3 in) and adapter flanges from DN 100 (4 in).
The measuring range is up to 35 m (114.8 ft) with a deviation of 2 mm. In operation the antenna sends extremely short microwave pulses toward the product, the pulses return from the surface, and a time-stretching procedure converts the very short transit time into a precise distance. Nothing touches the liquid except the antenna face.
Benefits that matter on the plant floor
- No contact with the medium, so no wear, no adhesion problem on a probe, and no recalibration for density change.
- Measuring results that stay exact independent of process conditions inside the stated pressure window.
- Optional SIL qualification up to SIL2 for protective functions.
- Many electronics choices: 4 to 20 mA/HART in two-wire or four-wire form, Profibus PA, Foundation Fieldbus, Modbus, and a HART variant with an integrated accumulator.
- Double chamber housings accept supplementary electronics, namely a radio module or a power pack.
VEGAPULS 61 technical specifications
Data come from the 4 to 20 mA/HART two-wire specification sheet.
| Parameter | Value (datasheet) |
|---|---|
| Model | VEGAPULS 61, radar level sensor for liquids |
| Measuring range up to | 35 m (114.8 ft) |
| Deviation | 2 mm |
| Process fitting | Thread G1 1/2, 1 1/2 NPT, mounting strap, compression flanges from DN 80 (3 in), adapter flanges from DN 100 (4 in) |
| Process pressure | -1 to +3 bar (-100 to +300 kPa / -14.5 to +43.5 psig) |
| Process temperature | -40 to +80 C (-40 to +176 F) |
| Ambient, storage, transport temperature | -40 to +80 C |
| Operating voltage | 9.6 to 36 V DC |
| SIL qualification | Optionally up to SIL2 |
| Wetted materials | PVDF or PP |
| Process seal | FPM |
| Housing | Single or double chamber; plastic, stainless steel or aluminium; up to IP 68 (1 bar) |
| Electronics | 4 to 20 mA/HART two-wire and four-wire, Profibus PA, Foundation Fieldbus, Modbus, HART with accumulator |
| Datasheet reference | 34492-EN-160119 |
Applications for VEGAPULS 61 in regional industry
Because the sensor is limited to -1 to +3 bar and -40 to +80 °C, it belongs on atmospheric or low-pressure vessels. In Oman and wider GCC facilities that means water and wastewater basins and tanks, chemical storage of acids and alkalis compatible with PVDF or PP, cooling-water make-up tanks, firewater buffer tanks and utility day tanks in refineries, gas plants and power stations. In manufacturing, it is a sensible device for process water, ingredient tanks and effluent sumps. Place it on a vessel where condensate and splash are present but vacuum above -1 bar and pressure above 3 bar never occur.
Choosing a VEGAPULS 61 version and its limits
Pick the thread (G1½ or 1½ NPT) for a bare socket, the strap for open channels and sumps, and a compression or adapter flange when a DN 80 or DN 100 nozzle exists. Select the electronics that your control system already speaks: HART loops remain the common choice in older plants, while Profibus PA, Foundation Fieldbus and Modbus suit digital networks. The ambient window of -40 to +80 °C and the supply range of 9.6 to 36 V DC should be checked against the loop power available. Hazardous-area approvals (the sheet names ATEX and IEC) and ship approvals (GL, LRS, ABS) are listed generally, so confirm the exact version in the approval documents before you order for a classified area.
How VEGAPULS 61 differs from VEGAPULS 62, 65 and 66
The numbers separate the models cleanly. VEGAPULS 61 is the low-pressure one at 3 bar and +80 °C, in plastic wetted parts. VEGAPULS 62 offers 160 bar and up to +450 °C in 316L and exotic alloys, VEGAPULS 65 offers a slim rod antenna with 16 bar and +150 °C, and VEGAPULS 66 offers 160 bar and +400 °C with hygienic and bolted fittings. The VEGAPULS 61 deviation of 2 mm is tighter than the 8 mm stated for the 65 and 66, which makes it a good fit when accuracy on a plain tank is the priority.
Mounting and start-up of VEGAPULS 61
Mount away from the tank wall and from inflowing product streams, and point the antenna straight at the surface. Use the strap with an alignment device if the sensor has to hang over a channel. After wiring the loop and fitting the cable gland, set the minimum and maximum levels with the PLICSCOM module or with PACTware, and let the sensor suppress known false echoes from fixed objects. Handling the housing with IP 68 (1 bar) construction only helps if the gland and lid are correctly closed.
Service, spares and related items
With no moving parts the VEGAPULS 61 needs little servicing: check the antenna for deposits, the gland for tightness, and the loop for voltage. When ordering spares or a like-for-like replacement, quote the full type label so the electronics, housing and antenna match. Related items commonly requested together are the PLICSCOM display unit, the VEGACONNECT interface adapter and the mounting strap.
VEGAPULS 61 FAQ summary
- What is the pressure limit of the VEGAPULS 61? The process pressure range is -1 to +3 bar, so it is intended for atmospheric and low-pressure vessels.
- What materials touch the medium on the VEGAPULS 61? The wetted parts are PVDF or PP and the process seal is FPM, with an encapsulated antenna system.
- How far can the VEGAPULS 61 measure? Up to 35 m (114.8 ft) with a deviation of 2 mm, in liquids.
- Can the VEGAPULS 61 be used in a SIL loop? The specification sheet says optional SIL qualification up to SIL2 is available.
- Which fieldbus options exist for the VEGAPULS 61? Profibus PA, Foundation Fieldbus and Modbus, besides 4 to 20 mA/HART in two-wire and four-wire versions.
Documents and quotation
The manufacturer VEGA VEGAPULS 61 datasheet is available as a PDF download on this page, so your engineers can check ranges, materials and dimensions against the data sheet before ordering. To request a quotation send the part number VEGAPULS 61 together with the quantity, the required process connection, electronics version and any approval requirement through the RFQ form or by email. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer; product names and marks belong to their owners.
Other Models in the Vegapuls 6x Range
Seven Star LLC supplies models from the Vegapuls 6x range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| VEGA VEGAPULS 62 Radar Level Sensor 160 bar 450 C | Radar & Guided Wave Radar Level | View details |
| VEGA VEGAPULS 61 Radar Level Sensor 35 m PVDF | Radar & Guided Wave Radar Level | You are viewing this model |
Datasheets & Documents
- Datasheet VEGA VEGAPULS 61 Radar Level Sensor 35 m PVDF Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
VEGA is a German maker of level and pressure instruments. Bruno Grieshaber founded the company in 1959 in Triberg in the Black Forest, and it has been based in Schiltach since 1975, still family owned as VEGA Grieshaber KG. VEGA is best known for radar level sensors: it introduced the first two-wire radar level sensor in 1997 and the first 80 GHz radar sensor for bulk solids, the VEGAPULS 69, in 2015.
Seven Star LLC is an independent supplier listing VEGA radar and guided wave radar transmitters, point level switches, pressure transmitters and signal conditioning instruments for buyers in Oman and the GCC. Sensors are matched from the product code on the type label.
VEGA at a glance
| Origin | Founded by Bruno Grieshaber in 1959 in Triberg, Germany |
|---|---|
| Headquarters | Schiltach, Black Forest, Germany (since 1975) |
| Ownership | Family-owned company: VEGA Grieshaber KG |
| Milestones | First two-wire radar level sensor (1997), first 80 GHz radar for bulk solids, VEGAPULS 69 (2015), VEGAPULS 6X single radar platform for liquids and solids |
| Product families | VEGAPULS radar, VEGAFLEX guided wave radar, VEGASWING and VEGAPOINT switches, VEGACAL capacitive probes, VEGABAR and VEGADIF pressure, VEGAMET and VEGADIS signal conditioning |
VEGA sensor and instrument series
| Series | Type | Typical use |
|---|---|---|
| VEGAPULS 6X, VEGAPULS 69, VEGAPULS 64 | Process radar level transmitters (80 GHz) | Storage and process tanks, reactors with agitators, silos and bulk solids |
| VEGAPULS 11, 21, 31, 42 | Compact radar sensors | Water and wastewater, simple storage tanks; VEGAPULS 42 with IO-Link for machine integration |
| VEGAPULS C 21, C 11, C 22, C 23 | Radar sensors with fixed cable, IP68 | Wet wells, pumping stations, open channels and river levels |
| VEGAFLEX 81, 82, 83, 86 | Guided wave radar (TDR) | Level and interface in liquids, bulk solids, hygienic and high-temperature or high-pressure service (VEGAFLEX 86) |
| VEGASWING 61, 63, VEGAPOINT 21 | Vibrating and capacitive point level switches | Overfill protection, dry-run protection and high or low level alarms |
| VEGACAL 62 to VEGACAL 67 | Capacitive rod and cable probes | Point and continuous level in solids and conductive or adhesive liquids |
| VEGABAR 82, 83, 28, 29, 38 | Pressure transmitters, ceramic or metallic cell | Process pressure and hydrostatic level; compact 18/19 and 28/29/38 versions for utilities |
| VEGADIF 85 | Differential pressure transmitter | DP flow, filter monitoring and level in pressurised vessels |
| VEGAMET 841, VEGADIS 176 | Controller and loop display | Level display, pump control and remote indication of 4-20 mA signals |
Where VEGA instruments are used
VEGA radar sensors measure level in crude oil and product tanks, separators, chemical reactors, cement and aggregate silos, grain stores and water reservoirs. Compact cable radars are widely used in wastewater pumping stations and flood monitoring. Because 80 GHz radar focuses a narrow beam, it can measure past internal structures in a tank, and it is not affected by the temperature, pressure or vapour above the product, which suits hot Gulf storage tanks.
Ordering VEGA instruments: what we need
The product code on the type label (for example PS64.XXXXXXX) fixes the measuring range, antenna or probe, process connection, electronics and approvals. Send it with the serial number. For a new measurement add the medium and its dielectric constant if known, tank or silo height and internals, process pressure and temperature, process connection, output (4-20 mA HART, PROFIBUS PA, Modbus or IO-Link), and any hazardous-area or overfill protection approval required.
Facts checked against VEGA company and product information, October 2026.
Browse VEGA products by category: Level Transmitter, Pressure Instrumentation, Controllers and Data Acquisition.
FAQ
Questions about the VEGA VEGAPULS 61 Radar Level Sensor 35 m PVDF
Answers from our engineering team on installation, compatibility and integration.
01What is the pressure limit of the VEGAPULS 61?
The process pressure range is -1 to +3 bar, so it is intended for atmospheric and low-pressure vessels.
02What materials touch the medium on the VEGAPULS 61?
The wetted parts are PVDF or PP and the process seal is FPM, with an encapsulated antenna system.
03How far can the VEGAPULS 61 measure?
Up to 35 m (114.8 ft) with a deviation of 2 mm, in liquids.
04Can the VEGAPULS 61 be used in a SIL loop?
The specification sheet says optional SIL qualification up to SIL2 is available.
05Which fieldbus options exist for the VEGAPULS 61?
Profibus PA, Foundation Fieldbus and Modbus, besides 4 to 20 mA/HART in two-wire and four-wire versions.


















Reviews
There are no reviews yet.