Brand:

Pepperl+Fuchs KFD2-STC5-Ex1.2O Dual Output Supply

Description

One transmitter, two outputs: KFD2-STC5-Ex1.2O

Where a single field transmitter must feed two receivers, such as a control system and an independent safety system, the Pepperl+Fuchs KFD2-STC5-Ex1.2O avoids the need for two barriers and two transmitters. It powers a 2-wire or 3-wire SMART device in the hazardous area and creates two isolated 4 to 20 mA outputs, available as sink or source on terminals 7, 8, 9 and 10, 11, 12.

The datasheet lists the module as SIL 3 in its general specifications, one level above the SIL 2 of the single-output sibling, and the dual-output arrangement is the reason many plants choose it for protective loops.

Characteristics

  • Signal splitter: one input and two outputs, each isolated
  • Dual output 4 to 20 mA, sink or source, load 0 to 600 ohm, overload above 25 mA
  • Settling time 500 microseconds; ambient -20 to 60 degrees C
  • Short-circuiting unused outputs lowers internal dissipation by up to 100 mW per channel
  • Supports HART, BRAIN and Foxboro protocols

KFD2-STC5-Ex1.2O data table

Parameter Value
Supply 18 to 30 V DC, 1 W dissipation, 1.7 W consumption at maximum load
Input 4 to 20 mA on terminals 1+, 2-, 3
Outputs 7+, 8-, 9- and 10+, 11-, 12- (sink); 7-, 8+, 9+ and 10-, 11+, 12+ (source)
Load 0 to 600 ohm per output
External loop supply 2 to 30 V DC
Safe-side values Uo 26.2 V, Uq 27.25 V, Io 93 mA, Po 634 mW
Certificate CML 17 ATEX 2031X
Safety integrity SIL 3 listed (up to SIL 2 in the features line)
Mass about 200 g
Dimensions 20 x 124 x 115 mm, housing B2
Environment -20 to 60 degrees C, IP20

Why the second output is useful

A safety instrumented function should not share a receiver with the basic process control system, yet running two transmitters doubles hardware. With one device and two outputs, a technician can disconnect the DCS channel without disturbing the safety channel. The outputs are mutually isolated, and the connection diagram shows separate terminal sets for sink and source operation of each output.

KFD2-STC5-Ex1.2O against KFD2-STC5-Ex1

The single-output KFD2-STC5-Ex1 settles in 200 microseconds, allows 0 to 800 ohm, tolerates 70 degrees C and weighs about 150 g. KFD2-STC5-Ex1.2O settles in 500 microseconds, allows 0 to 600 ohm per output, tolerates 60 degrees C and weighs about 200 g, which is the price paid for the second output and its added circuitry.

Setting up the dual loop

Wire each output to its own receiver, decide separately whether each is sink or source, and verify both loops with a calibrator. If a loop is unused, short its terminals as described to cut dissipation.

Care of the module

Heat is the main enemy; keep a gap between modules where the cabinet is warm. Test both outputs at the plant maintenance interval.

Notes on certification

The ATEX certificate for this part is CML 17 ATEX 2031X, different from the CML 17 ATEX 2029X used for the single-output versions. Mention the exact part when providing documents for an audit.

Loop architecture with a split signal

In a typical safety-related design, output one feeds the basic process control system and output two goes to a logic solver. Each receiver needs its own loop power if the outputs run in sink mode, and each can be tested separately with a milliammeter in series. Because the module is heavier at about 200 g and has more internal parts than the single-output version, check that the rail and cabinet vibration levels in compressor houses do not exceed the manual limits. The designer should also document that the outputs are electrically separated from each other, so a fault in one receiver circuit does not propagate to the other.

Using the outputs in practice

After wiring, apply 4, 12 and 20 mA at the transmitter or with a simulator and read both outputs. The two values should agree within the accuracy of the instrument used. If one output is not needed, short its terminals rather than leaving it open, as the datasheet explains this reduces internal heat by as much as 100 mW. The module supports HART, BRAIN and Foxboro protocols, so handheld communicators or asset-management software can reach the transmitter through either output. Because both receivers stay isolated from each other and from the supply, you can maintain one loop while the other keeps running, which is a clear benefit during partial shutdowns. Label both receivers on the cabinet drawing to avoid cross-connection during maintenance, and note the terminal groups 7 to 9 and 10 to 12 on the loop sheet.

Questions buyers ask about KFD2-STC5-Ex1.2O

How many outputs does KFD2-STC5-Ex1.2O provide? It provides two isolated 4 to 20 mA outputs from a single input, usable as a signal splitter.

What load can each output of KFD2-STC5-Ex1.2O drive? The load range is 0 to 600 ohm, with overload detection above 25 mA.

Which SMART protocols does KFD2-STC5-Ex1.2O support? The datasheet lists HART, BRAIN and Foxboro.

How can the dissipation of KFD2-STC5-Ex1.2O be reduced? Short-circuiting unused outputs decreases internal power dissipation by up to 100 mW per channel.

What ATEX certificate does KFD2-STC5-Ex1.2O carry? The EU-type examination certificate is CML 17 ATEX 2031X.

Documents and quotation

The manufacturer datasheet for KFD2-STC5-Ex1.2O accompanies this listing as a PDF so your engineers can verify terminals, ratings and approvals before purchase. State whether both receivers are sinks, sources or one of each. To request a quotation, send the RFQ with the exact part number KFD2-STC5-Ex1.2O, the quantity, the delivery location in Oman or the GCC and any project reference. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer.

Other Models in the Stc5 Stv5 Range

Seven Star LLC supplies models from the Stc5 Stv5 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Pepperl+Fuchs KFD2-STC5-Ex1.H High Voltage SupplyIsolator & BarrierView details
Pepperl+Fuchs KFD2-STC5-Ex1.2O Dual Output SupplyIsolator & BarrierYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Pepperl+Fuchs KFD2-STC5-Ex1.2O Dual Output Supply Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Pepperl+Fuchs is a German manufacturer of industrial sensors and explosion protection equipment, founded in 1945 in Mannheim by Walter Pepperl and Ludwig Fuchs as a radio repair shop. Defective transformers led them into manufacturing, and the company developed its first proximity switch in the late 1950s. Pepperl+Fuchs is headquartered in Mannheim and is a pioneer of intrinsically safe electrical equipment for hazardous areas.

Seven Star LLC lists Pepperl+Fuchs sensors, isolated barriers, power supplies and hazardous-area mobile devices, and supplies them to instrument and automation teams in Oman by exact model designation.

Pepperl+Fuchs company profile

Founded 1945, Mannheim-Sandhofen, Germany, by Walter Pepperl and Ludwig Fuchs
Headquarters Mannheim, Germany
Ownership Privately owned (Pepperl+Fuchs SE)
Origins Radio repair workshop that began making replacement transformers
Product families Inductive, capacitive, ultrasonic and photoelectric sensors, rotary encoders, R2000 LiDAR scanners, KFD and HiC isolated barriers, Zener barriers, remote I/O, purge and pressurization systems, Ex-rated enclosures

Milestones

  • 1945: Walter Pepperl and Ludwig Fuchs open their radio repair shop in Mannheim.
  • 1958: The first proximity switch is developed (some company sources say 1959).

Pepperl+Fuchs product families on this page

On the interface side there are two systems. The K-System mounts on DIN rail and is represented here by the KFD2-UT2-Ex2 universal temperature converter. The H-System plugs into termination boards and is represented by the HiD2030 SMART transmitter power supply with HART. The PS1000-A6-24.20 is a 24 VDC, 20 A power supply for cabinets. Sensors listed include the NJ2-12GK-SN NAMUR inductive sensor, the R101 retro-reflective photoelectric sensor and the R2000 2-D LiDAR scanner. For field staff there are the Tab-Ex 05 DZ1 tablet for Zone 1/21 areas and the Smart-Ex 03 DZ2 smartphone for Zone 2/22 and Division 2 areas.

Where Pepperl+Fuchs equipment is used

Isolated barriers sit between field instruments in Zone 0 or Zone 1 and the DCS or safety system in refineries, gas plants and chemical works. NAMUR sensors report valve position and machine states in classified areas. Photoelectric sensors and LiDAR scanners work in conveying, packaging, warehousing and vehicle guidance. Ex-rated tablets and phones are carried on operator rounds and maintenance jobs.

Pepperl+Fuchs products we list

Family Examples
Isolator & Barrier HiD2030 SMART Transmitter Power Supply w…, KFD2-SR2-Ex2.W K-System Isolated Switch…, KFD2-UT2-Ex2 Universal Temperature Conve…
Industrial Computers Tab-Ex 05 DZ1 WWAN Hazardous Area Tablet, Smart-Ex® 03 DZ2 smartphone for Zone 2/2…
Inductive Proximity Sensors NJ2-12GK-SN NAMUR Inductive Sensor
Power Modules PS1000-A6-24.20 Power Supply 24 VDC 20 A
Photoelectric Sensors R101 Retro-Reflective Photoelectric Sensor
Laser Distance, LiDAR & Radar Sensors R2000 2-D LiDAR Laser Scanner

Ordering Pepperl+Fuchs parts: what we need

Send the complete model designation as printed on the device, including every suffix; a single letter can change the supply voltage or the output type. Add the part number if the label shows one. For barriers, tell us the field device and signal type, the number of channels and whether the safety loop needs a SIL-assessed module. For mobile devices, state the zone or division and the regional radio version.

Facts checked against Pepperl+Fuchs's own chronicle pages, October 2026.

FAQ

Questions about the Pepperl+Fuchs KFD2-STC5-Ex1.2O Dual Output Supply

Answers from our engineering team on installation, compatibility and integration.

01How many outputs does KFD2-STC5-Ex1.2O provide?
It provides two isolated 4 to 20 mA outputs from a single input, usable as a signal splitter.
02What load can each output of KFD2-STC5-Ex1.2O drive?
The load range is 0 to 600 ohm, with overload detection above 25 mA.
03Which SMART protocols does KFD2-STC5-Ex1.2O support?
The datasheet lists HART, BRAIN and Foxboro.
04How can the dissipation of KFD2-STC5-Ex1.2O be reduced?
Short-circuiting unused outputs decreases internal power dissipation by up to 100 mW per channel.
05What ATEX certificate does KFD2-STC5-Ex1.2O carry?
The EU-type examination certificate is CML 17 ATEX 2031X.