Brand:

Pepperl+Fuchs KFD2-ST2-Ex2 Switch Amplifier, 2-Ch Active Transistor

Description

Pepperl+Fuchs KFD2-ST2-Ex2 overview

The Pepperl+Fuchs KFD2-ST2-Ex2 is a two-channel isolated switch amplifier of the K-System from Pepperl+Fuchs. It transfers digital signals from NAMUR sensors or dry contacts in a hazardous area to the safe area. A proximity sensor or switch controls an active transistor output for the safe-area load, and the output changes state when the input signal changes state.

The output state can be reversed with switches S1 and S2, and switch S3 enables or disables line fault detection of the field circuit. In an error condition the transistor returns to its de-energised state, and a fault is shown by LEDs according to NAMUR NE 44, plus a separate collective error message when the Power Rail is used. The outputs share the common pole terminal 14 plus, so this model is intended for systems that already share the supply positive, which keeps wiring simple.

Key features of the Pepperl+Fuchs KFD2-ST2-Ex2

  • Two channels with active transistor outputs that switch the positive supply
  • NAMUR input with line fault detection and switches for output reversal
  • 1-signal level of the supply voltage minus 3.5 V at 100 mA, short-circuit protected
  • Switching frequency up to 5 kHz
  • SIL 2 according to IEC/EN 61508
  • Common pole terminal 14 plus, no separate isolation between outputs and supply
  • LED fault display according to NAMUR NE 44 and Power Rail collective error message
  • Housing type B2, 20 mm wide, IP20, minus 20 to 60 degrees C

KFD2-ST2-Ex2 technical specifications

The values below are taken from the manufacturer datasheet of the KFD2-ST2-Ex2, release date 2022-01-10. Always confirm the current datasheet and the certificates before final engineering.

Parameter Value
Model KFD2-ST2-Ex2, Switch Amplifier, 2-channel isolated barrier
Signal type Digital input
Safety Integrity Level SIL 2
Rated supply voltage 20 to 30 V DC, ripple up to 10 percent (Power Rail or terminals 14+, 15-)
Rated current Up to 50 mA
Input NAMUR according to EN 60947-5-6; terminals 1+, 2+, 3- and 4+, 5+, 6-
Open circuit voltage / short-circuit current Approx. 8 V DC / approx. 8 mA
Switching point / hysteresis 1.2 to 2.1 mA / approx. 0.2 mA
Line fault detection Breakage 0.1 mA or less; short-circuit above 6 mA
Output Active electronic outputs; output I terminal 7+; output II terminal 9+
Signal level 1-signal: (L+) minus 3.5 V at 100 mA, short-circuit protected; 0-signal: off-state current up to 10 microamperes
Switching frequency Up to 5 kHz
Isolation Input to output and to supply: reinforced insulation, 300 V rms; output to supply and output to output not available, common pole terminal 14+
Hazardous-area marking (1)G [Ex ia] IIC; certificate PTB 00 ATEX 2035
Input Ex ia values Uo 10.5 V, Io 13 mA, Po 34 mW (linear characteristic)
Zone 2 certificate TUV 99 ATEX 1499 X, marking Ex nA II T4
IECEx IECEx PTB 05.0011
Ambient temperature Minus 20 to 60 degrees C
Dimensions / mass 20 x 119 x 115 mm (W x H x D), housing type B2 / approx. 150 g
Degree of protection / mounting IP20, screw terminals / 35 mm DIN rail

Because the output and supply are not separately isolated, this model is suited to systems that connect the load to the same ground reference. If your control system needs isolated digital inputs, choose a model with isolated outputs.

Typical applications in oil and gas, utilities, water and manufacturing

Position and process switching in hazardous areas relies on NAMUR proximity sensors and dry contacts, from valve limit switches on ESD valves at wellheads to level switches on storage tanks and flow switches on cooling water lines. The KFD2-ST2-Ex2 passes these signals out of the hazardous area to relays, PLC inputs or annunciators, and its line fault detection tells operators when a cable is open or shorted instead of leaving them with a silent failure.

In power stations, water treatment plants and manufacturing facilities around the GCC, the same module is common on package units, burner management panels and compressor skids. Because the signal is a simple switching state, the KFD2-ST2-Ex2 is easy to commission, and spare units are often held on the shelf because a failed channel can stop a whole skid.

Selection and compatibility notes for KFD2-ST2-Ex2

Check the sensor type first. The input is designed for NAMUR sensors according to EN 60947-5-6 and for mechanical contacts with the resistor network shown in the wiring diagram, so a three-wire sensor or a powered contact needs a different interface. Next check what the safe-area load requires, because a relay output and a transistor output behave very differently with PLC cards, solenoids and counters.

If the signal is part of a safety function, read the functional safety data in the datasheet, including the SIL value and the conditions attached to it, and compare it with your safety requirement specification. When the KFD2-ST2-Ex2 replaces an older module, compare terminal numbers and the supply arrangement, since the Power Rail option changes how power and the collective error message are wired.

Installation and commissioning of the KFD2-ST2-Ex2

Before mounting the KFD2-ST2-Ex2, confirm the field device and cable parameters against the entity values in the datasheet and the certificate, and decide whether the module will be powered from a Power Rail or from its own supply terminals. Mount it on a 35 mm DIN rail in a clean, ventilated cabinet in the safe area, keep hazardous-area and safe-area wiring physically separated and labelled, and respect the spacing and marking required by your site rules for intrinsically safe circuits. Wire the load between the output terminal and the common negative of the supply, since the KFD2-ST2-Ex2 switches the positive supply voltage.

Wire the KFD2-ST2-Ex2 only to the terminal assignment printed in the wiring diagram, tighten the screws and check that no strands are left outside the clamp. After applying the supply, check the power indication, then simulate the field signal and prove the complete loop from field to control system before the plant is handed over. Record the as-found readings so that later loop checks of the KFD2-ST2-Ex2 can be compared with the commissioning values.

Maintenance and service life

The KFD2-ST2-Ex2 has no serviceable parts, so maintenance is mostly inspection. During planned shutdowns, check terminals for looseness and corrosion, verify the supply voltage at the module, and repeat the loop check that was recorded at commissioning. In coastal and humid locations such as Muscat, Sohar and Duqm, a clean, dry and sealed cabinet greatly extends the life of any electronic interface. Check the supply voltage at terminal 14 plus during routine inspection, because the output level of the KFD2-ST2-Ex2 follows the supply voltage minus about 3.5 V.

If a loop drifts out of tolerance or the unit shows no power indication with a healthy supply, replace the module instead of attempting a repair, and keep the replacement documentation in the loop folder. Certified intrinsically safe equipment must not be modified, and any change to cabling, load or field device should be re-assessed against the KFD2-ST2-Ex2 entity parameters before it returns to service.

Related products and ordering notes

Customers who ask for the KFD2-ST2-Ex2 often need neighbouring models or accessories from the same system, such as other KFD2, KFA6 and KHA6 switch amplifiers, NAMUR inductive sensors, the Power Rail and power feed modules, and the K-System accessories. If you are standardising a cabinet on one family, send us the loop list and we can quote the matching modules together.

When you send an enquiry for the KFD2-ST2-Ex2, quote the full part number exactly as printed on the nameplate, the quantity and the intended application. If you are replacing an installed unit, a photograph of the nameplate helps us confirm the exact variant you need. We can arrange a quotation with delivery to Oman and across the GCC.

Frequently asked questions about KFD2-ST2-Ex2

The KFD2-ST2-Ex2 is a SIL 2 two-channel switch amplifier with active transistor outputs that share a common positive pole, switching up to 5 kHz with NAMUR line fault detection.

Documents and quotation

A copy of the manufacturer datasheet for the KFD2-ST2-Ex2 is attached to this page for your engineering review. To request a quotation, send the RFQ with the part number KFD2-ST2-Ex2, the quantity, the delivery location and any certification or documentation requirements, and we will reply with availability and lead time. Please check the specification against your loop or system requirements before ordering.

Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with Pepperl+Fuchs. Product names and part numbers are used only to identify the item you ask for.

Datasheets & Documents
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Pepperl+Fuchs is a German manufacturer of industrial sensors and explosion protection equipment, founded in 1945 in Mannheim by Walter Pepperl and Ludwig Fuchs as a radio repair shop. Defective transformers led them into manufacturing, and the company developed its first proximity switch in the late 1950s. Pepperl+Fuchs is headquartered in Mannheim and is a pioneer of intrinsically safe electrical equipment for hazardous areas.

Seven Star LLC lists Pepperl+Fuchs sensors, isolated barriers, power supplies and hazardous-area mobile devices, and supplies them to instrument and automation teams in Oman by exact model designation.

Pepperl+Fuchs company profile

Founded 1945, Mannheim-Sandhofen, Germany, by Walter Pepperl and Ludwig Fuchs
Headquarters Mannheim, Germany
Ownership Privately owned (Pepperl+Fuchs SE)
Origins Radio repair workshop that began making replacement transformers
Product families Inductive, capacitive, ultrasonic and photoelectric sensors, rotary encoders, R2000 LiDAR scanners, KFD and HiC isolated barriers, Zener barriers, remote I/O, purge and pressurization systems, Ex-rated enclosures

Milestones

  • 1945: Walter Pepperl and Ludwig Fuchs open their radio repair shop in Mannheim.
  • 1958: The first proximity switch is developed (some company sources say 1959).

Pepperl+Fuchs product families on this page

On the interface side there are two systems. The K-System mounts on DIN rail and is represented here by the KFD2-UT2-Ex2 universal temperature converter. The H-System plugs into termination boards and is represented by the HiD2030 SMART transmitter power supply with HART. The PS1000-A6-24.20 is a 24 VDC, 20 A power supply for cabinets. Sensors listed include the NJ2-12GK-SN NAMUR inductive sensor, the R101 retro-reflective photoelectric sensor and the R2000 2-D LiDAR scanner. For field staff there are the Tab-Ex 05 DZ1 tablet for Zone 1/21 areas and the Smart-Ex 03 DZ2 smartphone for Zone 2/22 and Division 2 areas.

Where Pepperl+Fuchs equipment is used

Isolated barriers sit between field instruments in Zone 0 or Zone 1 and the DCS or safety system in refineries, gas plants and chemical works. NAMUR sensors report valve position and machine states in classified areas. Photoelectric sensors and LiDAR scanners work in conveying, packaging, warehousing and vehicle guidance. Ex-rated tablets and phones are carried on operator rounds and maintenance jobs.

Pepperl+Fuchs products we list

Family Examples
Isolator & Barrier HiD2030 SMART Transmitter Power Supply w…, KFD2-SR2-Ex2.W K-System Isolated Switch…, KFD2-UT2-Ex2 Universal Temperature Conve…
Industrial Computers Tab-Ex 05 DZ1 WWAN Hazardous Area Tablet, Smart-Ex® 03 DZ2 smartphone for Zone 2/2…
Inductive Proximity Sensors NJ2-12GK-SN NAMUR Inductive Sensor
Power Modules PS1000-A6-24.20 Power Supply 24 VDC 20 A
Photoelectric Sensors R101 Retro-Reflective Photoelectric Sensor
Laser Distance, LiDAR & Radar Sensors R2000 2-D LiDAR Laser Scanner

Ordering Pepperl+Fuchs parts: what we need

Send the complete model designation as printed on the device, including every suffix; a single letter can change the supply voltage or the output type. Add the part number if the label shows one. For barriers, tell us the field device and signal type, the number of channels and whether the safety loop needs a SIL-assessed module. For mobile devices, state the zone or division and the regional radio version.

Facts checked against Pepperl+Fuchs's own chronicle pages, October 2026.

FAQ

Questions about the Pepperl+Fuchs KFD2-ST2-Ex2 Switch Amplifier, 2-Ch

Answers from our engineering team on installation, compatibility and integration.

01How does the KFD2-ST2-Ex2 output work?
It has two active transistor outputs that switch the supply positive, giving a 1-signal of the supply voltage minus 3.5 V at 100 mA.
02Are the outputs isolated from each other?
No. The datasheet states that isolation between outputs, and between outputs and supply, is not available because of the common pole terminal 14 plus.
03What SIL level does it have?
The datasheet states SIL 2 according to IEC/EN 61508 for the KFD2-ST2-Ex2.
04How fast can the KFD2-ST2-Ex2 switch?
The datasheet gives a switching frequency of up to 5 kHz for both channels.
05How do I order the KFD2-ST2-Ex2?
Send an RFQ with the part number KFD2-ST2-Ex2, the quantity and the delivery location in Oman or the GCC, and Seven Star LLC will reply with availability and lead time.