Brand: Yokogawa
Yokogawa EJX430A Gauge Pressure Transmitter, Traditional Mount
Description
Yokogawa EJX430A Gauge Pressure Transmitter, Traditional Mount: overview
The Yokogawa EJX430A is a gauge pressure transmitter in the traditional cover-flange body. It brings the EJX performance level to ordinary gauge pressure points, with an accuracy of plus or minus 0.04% of span and a long-term stability of plus or minus 0.1% of URL per 15 years.
Seven Star LLC lists the Yokogawa EJX430A for engineers, maintenance planners and procurement teams in Oman and across the GCC who need to replace an installed unit, extend a loop or specify a new instrument for an oil and gas, utility, water or manufacturing project. The page below summarizes the key facts from the manufacturer datasheet so that a first technical review can be done before the full document is opened.
Key features of the EJX430A
- EJX430A uses a single crystal silicon resonant sensor.
- Stated reference accuracy: plus or minus 0.04% of span; plus or minus 0.025% of span when option /hac is specified.
- Fast response with damping adjustable from 0.00 to 100.00 s, and a 10-segment signal characterizer for the analog output.
- Integral LCD indicator option with 5-digit display, bar graph and local parameter setting through the external zero adjustment screw.
- EJX multi-sensing diagnostics detect problems such as impulse line blockage or heat trace breakage, with an optional status output.
- Cast aluminum housing as standard with IP66/IP67 and Type 4X protection, and stainless steel housing as an option.
- SIL 2 capability for the standard HART type, so the EJX430A can be used in safety instrumented functions after the usual proof-test planning.
EJX430A technical specifications
Capsule H covers 2.5 to 500 kPa, capsule A 0.0175 to 3.5 MPa and capsule B 0.08 to 16 MPa. With option /HAC the reference accuracy improves to plus or minus 0.025% of span, which is attractive for tank-farm inventory, custody-related pressure compensation and other applications where small errors carry a cost.
Process connections are made through Rc1/4 or 1/4 NPT female threads on the cover flanges, or through optional Rc1/2 or 1/2 NPT female process connectors.
Multi-sensing diagnostics and an optional status output are available, and the standard HART and BRAIN types are certified for SIL 2 safety use.
The table lists the main values stated in the datasheet for this model. Values depend on the selected capsule, wetted material and options, so always confirm the final model code with the datasheet before ordering.
| Parameter | Value |
|---|---|
| Type | Gauge pressure transmitter, traditional (cover flange) mount |
| Capsule H span | 2.5 to 500 kPa (10 to 2000 inH2O) |
| Capsule A span | 0.0175 to 3.5 MPa (2.5 to 500 psi) |
| Capsule B span | 0.08 to 16 MPa (12 to 2300 psi) |
| Reference accuracy | Plus or minus 0.04% of span; plus or minus 0.025% of span when option /HAC is specified |
| Maximum working pressure | H: 500 kPa; A: 3.5 MPa; B: 16 MPa |
| Maximum over pressure | H and A: 16 MPa; B: 25 MPa |
| Stability | Plus or minus 0.1% of URL per 15 years |
| Ambient temperature | -40 to 85 C (-30 to 80 C with LCD display) |
| Process temperature | -40 to 120 C |
| Response time | 90 ms (150 ms for H capsule with certain wetted material codes) |
| Output | 4 to 20 mA DC with HART or BRAIN; FOUNDATION Fieldbus and PROFIBUS PA also offered |
| Process connections | Rc1/4 or 1/4 NPT female on cover flanges; Rc1/2 or 1/2 NPT female process connectors optional |
| Weight | 2.8 kg for wetted material codes S and L, without indicator, bracket and process connector |
Typical applications in Oman and the GCC
- Oil and gas. Upstream and midstream facilities use the EJX430A for pump discharge and suction pressure, tank level by hydrostatic head, filter and strainer monitoring, utility headers and compressed-air systems, where a stable digital signal and fast response help the control system and the safety layer.
- Utilities and power. In power and utility plants across the GCC the EJX430A supports steam, feedwater, fuel gas and cooling circuits, and its diagnostics reduce unplanned inspection walks in hot plant areas.
- Water and desalination. Desalination and water treatment plants rely on pressure and differential pressure points for pump protection and membrane skid monitoring, and a EJX430A fits those duties with materials chosen for the water chemistry.
- Manufacturing and process. Petrochemical, fertilizer, food and general manufacturing units in Oman use the EJX430A on reactors, filters, compressors and storage, where HART or fieldbus communication feeds asset-management software.
Selection and compatibility notes
Start the selection of a EJX430A from the measured variable and the calibrated span, then pick the capsule whose upper range limit leaves comfortable margin. The datasheet shows that accuracy is quoted for spans at or above a capsule-specific value and carries an extra term for narrower spans, so very high rangedown should be checked against the formula rather than assumed.
Check the wetted materials against the process and the cleaning or flushing chemicals. Material code S with a Hastelloy C-276 diaphragm is the typical starting point, and other materials can be selected through the model code. The datasheet warns that an unsuitable material can leak process fluid or damage the diaphragm, so the choice must be made with the process conditions in hand.
Output and protocol should follow the control system. A 4 to 20 mA signal with digital communication is standard, and Fieldbus and PROFIBUS PA types have separate datasheets. For hazardous areas, review the approval options listed in the datasheet, such as FM, ATEX, CSA and IECEx, and confirm that the certificate on the nameplate matches the zone and gas group of the installation.
Installation and commissioning of the EJX430A
Mount the EJX430A close to the tapping point and keep the impulse line short and free of traps. For liquid service on a level duty, the zero must be set with the actual head of liquid in mind. Install an isolation and vent valve at the process connection so the transmitter can be removed or calibrated without shutting down the process.
After mounting, apply the electrical connection through the conduit entry, ground the housing, and power the loop. Perform a loop test and set the zero with the process isolated or the impulse lines equalized. Range the EJX430A either with a HART or BRAIN communicator or locally through the zero adjustment screw. Document the tag, range and damping in the commissioning record.
Maintenance and calibration
The EJX430A needs little routine maintenance. Check zero and span against a reference standard at an interval set by your calibration policy, inspect impulse lines and vent or drain plugs for blockage and leakage, and review the diagnostics reported by the transmitter. Keep the housing covers tight with intact O-rings, because the enclosure rating depends on them. Spare indicator and amplifier units can be changed in the field without touching the process.
Related products and ordering notes for the EJX430A
Other Yokogawa models in the same product area include EJX440A, EJX530A, EJX630A and EJA430E, which may suit neighboring points on the same plant. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer. Product names and model codes are used only to identify compatible equipment.
When you ask for a quotation, state the exact model code, the measuring range, the output type, any hazardous area approval and the quantity. A complete code lets us confirm that the unit matches the installed unit or the project specification, and it avoids delays caused by option mismatches.
Frequently asked questions in short
What is the Yokogawa this model? The Yokogawa this model is a high-performance gauge pressure transmitter. The this model is a gauge pressure transmitter in the traditional cover-flange body. What measuring ranges does the this model cover? Datasheet values for the EJX430A: 2.5 to 500 kPa (10 to 2000 inH2O); 0.0175 to 3.5 MPa (2.5 to 500 psi); 0.08 to 16 MPa (12 to 2300 psi). What accuracy and output does the EJX430A provide? For the EJX430A the datasheet gives plus or minus 0.04% of span; plus or minus 0.025% of span when option /hac is specified. Output and communication: 4 to 20 mA DC with HART or BRAIN; FOUNDATION Fieldbus and PROFIBUS PA also offered.
Documents and quotation
The manufacturer datasheet for the EJX430A is attached to this page and gives the complete model and suffix codes, dimensions and options. To receive a quotation, send the RFQ with the part number EJX430A, the quantity and your required range and approvals, and the Seven Star LLC team will reply with availability and delivery information for Oman and the GCC.
Datasheets & Documents
- Datasheet Yokogawa EJX430A Gauge Pressure Transmitter, Traditional Mount Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Yokogawa is the Japanese measurement and industrial automation company behind the DPharp EJA and EJX pressure transmitters, CENTUM distributed control systems and ProSafe-RS safety systems. Tamisuke Yokogawa set it up in 1915 as an electric meter research institute in Shibuya, Tokyo. It began selling electric meters in 1917, was incorporated as Yokogawa Electric Works in 1920, and has been Yokogawa Electric Corporation since 1986. In 1975 it released CENTUM, which it describes as the world's first distributed control system.
Seven Star LLC is an independent supplier in Muscat. We list Yokogawa transmitters, flowmeters, analysers, controllers, recorders and CENTUM and ProSafe spare modules, and supply them to oil and gas, power, water and process plants in Oman and the GCC by model code.
Yokogawa at a glance
| Established | 1915, Shibuya, Tokyo, by Tamisuke Yokogawa with Ichiro Yokogawa and Shin Aoki |
|---|---|
| Milestones | Electric meters from 1917; incorporated in 1920; CENTUM DCS in 1975; renamed Yokogawa Electric Corporation in 1986 |
| Headquarters | Tokyo, Japan |
| Product families | Pressure and temperature transmitters, magnetic, vortex and Coriolis flowmeters, liquid and gas analysers, controllers and recorders, CENTUM VP DCS, ProSafe-RS safety systems and STARDOM controllers |
Yokogawa products we list
| Family | Models | Typical use |
|---|---|---|
| Pressure and DP transmitters | EJA110E, EJA430E, EJA530E, EJX110A, EJX530A, EJX910A multivariable | Pressure, level and DP flow measurement in process plants |
| Temperature transmitters | YTA610, YTA710 | RTD and thermocouple signals converted to 4-20 mA, HART or fieldbus |
| Flowmeters | ADMAG AXG, ADMAG AXW, ROTAMASS TI, VY vortex, VF701 | Water and conductive liquids, mass flow of hydrocarbons, steam and gas |
| Analysers | TDLS8000 laser gas analyser, FLXA402, FLXA21 DO, E7042UD zirconia cell, K9471DS cover | Combustion O2, in-situ gas analysis, pH, conductivity and dissolved oxygen |
| Controllers and recorders | UT35A/UT32A, UT32A-D, UT55A/UT52A, UT75A, UP35A/UP32A, UP55A, YS1700, GX10/GX20, GP10/GP20, GM10, µR20000 | Single-loop control, furnace programs and data recording |
| Control and safety systems | CP451-10 processor, ADV161, ADV551, node interface unit, ProSafe-RS, ProSafe-RS Lite, ProSafe-SLS, FCN-500 | Spares and expansions for CENTUM DCS, safety systems and STARDOM |
| Battery packs | S9129FA, S9185FA, S9548FA | Memory backup batteries for DCS and controller modules |
The EJA and EJX transmitters use Yokogawa's DPharp sensor: two silicon resonators whose vibration frequency changes with pressure, so the output is a digital frequency rather than an analogue strain signal. The model code describes the instrument completely. In EJA110E, "110" is a differential pressure transmitter, and the letters after the dash set the span, wetted materials, process connection, electrical output and approvals. When you replace a transmitter, sending the full code from the nameplate avoids a mismatch in range or materials.
Where Yokogawa products are used
In Oman and the GCC, Yokogawa transmitters, analysers and control systems are found in oil and gas production, gas processing and LNG, refineries and petrochemical plants, power and desalination stations, and water treatment. Many plants still run CENTUM CS 3000 and CENTUM VP systems that need spare I/O modules and batteries.
Ordering Yokogawa products: what we need
Send the full model and suffix code from the nameplate (for example EJA110E-JMS5J-912NN/KF22) and the style code. For DCS modules, add the module type and system version. For analysers, send the sensor type, measuring range and process conditions.
Facts checked against Yokogawa's corporate history, October 2026.
Browse Yokogawa products by category: PLC & I/O Cards, Flowmeters, Pressure Instrumentation, Automation Accessories, Temperature Instrumentation.
FAQ
Questions about the Yokogawa EJX430A Gauge Pressure Transmitter,
Answers from our engineering team on installation, compatibility and integration.
01What is the Yokogawa EJX430A?
The Yokogawa EJX430A is a high-performance gauge pressure transmitter. The EJX430A is a gauge pressure transmitter in the traditional cover-flange body.
02What measuring ranges does the EJX430A cover?
Datasheet values for the EJX430A: 2.5 to 500 kPa (10 to 2000 inH2O); 0.0175 to 3.5 MPa (2.5 to 500 psi); 0.08 to 16 MPa (12 to 2300 psi).
03What accuracy and output does the EJX430A provide?
For the EJX430A the datasheet gives plus or minus 0.04% of span; plus or minus 0.025% of span when option /hac is specified. Output and communication: 4 to 20 mA DC with HART or BRAIN; FOUNDATION Fieldbus and PROFIBUS PA also offered.
04How is the EJX430A installed on a process line?
The EJX430A is installed near the tapping point with a short impulse line or process connector, an isolation valve and a vent valve, so that it can be zeroed and removed without stopping the process.
05How can I request a quotation for the EJX430A in Oman?
Send an RFQ with the part number EJX430A, quantity, range, output and approvals through the inquiry form. Seven Star LLC replies with availability and delivery for Oman and the GCC, and the datasheet is on the product page.