Schneider Electric ABLS1A24021 24 V 2.1 A Power Supply

Description

ABLS1A24021: 24 V DC regulated power supply, 2.1 A (50 W)

The ABLS1A24021 is an optimised DIN-rail supply in a plastic housing 30 mm wide. It is a regulated switch mode power supply from Schneider Electric’s Modicon Power Supply offer that delivers 24 V DC at 2.1 A, equal to 50 W. Schneider Electric lists it as the Optimized variant of the family, a slim unit that clips onto the standard rail. Seven Star LLC supplies the ABLS1A24021 in Oman and the GCC as an independent supplier based in Muscat.

The reference follows a family pattern: ABL is the power supply prefix, the letter S names the style (optimized), the characters 1A a series code that we do not decode, 24 the output voltage in volts and 021 the output current in tenths of an amp (here 24 V and 2.1 A, rounded). This is our reading of the pattern; the datasheet is the authority for ordering.

The ABL Modicon power supply family around the ABLS1A24021

The thirteen references below share a 12 V, 24 V or 48 V output and differ in style, power and size.

Reference Style Output Rated power
ABLM1A24012 modular DIN-rail 24 V / 1.25 A 30 W
ABLP1A12085 panel-mount 12 V / 8.5 A 100 W
ABLP1A24045 panel-mount 24 V / 4.5 A 100 W
ABLP1A24062 panel-mount 24 V / 6.25 A 150 W
ABLP1A24100 panel-mount 24 V / 10 A 240 W
ABLS1A12062 optimised DIN-rail 12 V / 6.25 A 75 W
ABLS1A24021 optimised DIN-rail 24 V / 2.1 A 50 W
ABLS1A24031 optimised DIN-rail 24 V / 3.13 A 75 W
ABLS1A24038 optimised DIN-rail 24 V / 3.8 A 91.2 W
ABLS1A24050 optimised DIN-rail 24 V / 5 A 120 W
ABLS1A24100 optimised DIN-rail 24 V / 10 A 240 W
ABLS1A48025 optimised DIN-rail 48 V / 2.5 A 120 W

Output, ripple and protection of the ABLS1A24021

The ABLS1A24021 delivers 24 V DC at 2.1 A, adjustable over 24–28 V. At 80 % utilisation the load would be 1.68 A. Residual ripple is < 75 mV, the line and load regulation is < 0.5 % at 0 to 100 % load at 25 °C and < 1 % at full voltage range in line at 25 °C, and the supply can start loads with up to 3000 µF of capacitance.

Protection includes overload and short-circuit with automatic reset, over-temperature with manual reset and overvoltage with manual reset. Output coupling is listed as parallel or serial. The connection pages of the datasheet show a parallel arrangement of at most two identical units, with equal cables and a maximum voltage difference of 25 mV, the load kept below 90 % of twice the nominal current, and a series arrangement with two diodes. The datasheet describes this parallel arrangement in terms of load sharing and does not present it as a redundancy scheme.

Typical uses of the ABLS1A24021 in Oman and the GCC

A 24 V, 50 W supply like this unit serves panel builders who want a slim DIN-rail supply in standard control cabinets across Oman and the GCC: PLC and sensor supplies in water and wastewater plants, pump and ventilation controls in buildings, and instrument panels in power and oil and gas sites. The region’s heat is the main consideration. The derating-free ambient band quoted above is the figure to compare with real cabinet temperature in direct sun or in rooms without strong air conditioning; where it is exceeded, either choose a larger rating so the load stays well under the derated current or improve ventilation.

Input behaviour of the ABLS1A24021

The input is 100–240 V AC single phase with limits of 85–264 V AC at 50–60 Hz, one band for both 115 V and 230 V networks. The inrush current is 35.0 A at 115 V and 75.0 A at 230 V, input current is < 1.1 A 115 V AC and < 0.65 A 230 V AC and the power factor is 0.45 at 115 V AC and 0.35 at 230 V AC. An internal fuse (not interchangeable, 3.15 A) protects the input and the datasheet recommends external protection of 10 A Curve B, 20 A Curve C, 6 A Curve C; the unit is listed for TN, TT and IT networks with a maximum leakage current of 1 mA 240 V AC. The datasheet adds that a switch or circuit breaker near the product must serve as the disconnecting device, that the unit is tested with branch circuit protection up to 20 A, and that it is only suitable for audio, video, information, communication, industrial and control equipment. Turn-on time is <3s and the holding time is > 20 ms 100 V AC and > 100 ms 230 V AC.

Choosing the ABLS1A24021: a short checklist

  • Confirm the load voltage is 24 V DC and the total current stays below 2.1 A, with margin for the derating shown in the datasheet.
  • Check the supply network: 100–240 V AC single phase.
  • Check the mounting: Top hat type TH35-15 rail conforming to IEC 60715, Top hat type TH35-7.5 rail conforming to IEC 60715, Double-profile DIN rail, and the space of 30 × 75 × 89.5 mm.
  • State the highest cabinet temperature of the installation.

ABLS1A24021 technical specifications

Parameter Specification
Manufacturer / part number Schneider Electric / ABLS1A24021
Variant Optimized, plastic enclosure
Nominal input voltage 100–240 V AC single phase
Input voltage limits 85–264 V AC
Rated power 50 W
Output voltage / current 24 V DC / 2.1 A
Output voltage adjustment 24–28 V
Efficiency 86 % at 115 V AC / 88 % at 230 V AC
Power dissipation 7.5 W
Integrated input fuse Integrated fuse (not interchangeable) 3.15 A
Dimensions (W × H × D) 30 × 75 × 89.5 mm
Net weight 0.180 kg
Operating temperature (no derating) −10 to 55 °C without derating

Mounting, cooling and environment of the ABLS1A24021

The unit measures 30 × 75 × 89.5 mm and weighs 0.180 kg. Mounting options in the datasheet: Top hat type TH35-15 rail conforming to IEC 60715, Top hat type TH35-7.5 rail conforming to IEC 60715, Double-profile DIN rail. Protection is IP20, the overvoltage category is II, pollution degree 2 and the shock protection class is Class I. Altitude is < 2000 m.

Temperature behaviour is described by mounting position (A and B are the permitted orientations; the datasheet shows incorrect mounting too). The datasheet gives these ambient bands for mounting position A: −10 to 55 °C without derating. Beyond them: −20 to −10 °C with current derating of 2 % per °C; 55 to 70 °C with current derating of 3.33 % per °C. Shock resistance is 150 m/s² for 11 ms, and a green LED shows the output voltage.

Information to send with an RFQ for the ABLS1A24021

  • Reference ABLS1A24021 and quantity.
  • Supply voltage, AC or DC, and frequency at the site.
  • Load current and any peak or capacitive start-up currents.
  • Mounting arrangement and enclosure temperature.
  • Delivery location and required date.

Documents and quotation

The manufacturer datasheet for the ABLS1A24021 is attached on this page and carries the complete specification set, including the dimension drawings and the derating information. Compare the datasheet revision with your project documents before you freeze a bill of materials.

Send us the reference ABLS1A24021, the quantity and the delivery location, and Seven Star LLC will reply to your request for quotation. We work as an independent supplier based in Muscat and serve customers across Oman and the GCC.

Other Models in the Se Abl Power Range

Seven Star LLC supplies models from the Se Abl Power range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Schneider Electric ABLM1A24012 24 V 1.25 A Power SupplyPower ModulesView details
Schneider Electric ABLP1A12085 12 V 8.5 A Power SupplyPower ModulesView details
Schneider Electric ABLS1A12062 12 V 6.25 A Power SupplyPower ModulesView details
Schneider Electric ABLS1A24021 24 V 2.1 A Power SupplyPower ModulesYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Schneider Electric ABLS1A24021 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric ABLS1A24021 24 V 2.1 A Power

Answers from our engineering team on installation, compatibility and integration.

01What does the ABLS1A24021 output?
It delivers 24 V DC at 2.1 A (50 W), adjustable over 24–28 V.
02What input voltage does the ABLS1A24021 accept?
The datasheet lists 100–240 V AC single phase with limits of 85–264 V AC.
03Can two ABLS1A24021 units be paralleled?
The datasheet shows a parallel connection of at most two identical units with equal cabling and a maximum voltage difference of 25 mV. It is meant for capacity, not for redundancy.
04What protection does the ABLS1A24021 have?
Overload and short-circuit protection with automatic reset, plus over-temperature and overvoltage protection with manual reset. Ingress protection is IP20.
05What are the dimensions of the ABLS1A24021?
30 × 75 × 89.5 mm and a net weight of 0.180 kg. Mounting options: Top hat type TH35-15 rail conforming to IEC 60715, Top hat type TH35-7.5 rail conforming to IEC 60715, Double-profile DIN rail.