Schneider Electric ABLP1A12085 12 V 8.5 A Power Supply

Description

ABLP1A12085: 12 V DC regulated power supply, 8.5 A (100 W)

The ABLP1A12085 is a panel-mount supply in an aluminium enclosure, 97 × 30 × 129 mm. It is a regulated switch mode power supply from Schneider Electric’s Modicon Power Supply offer that delivers 12 V DC at 8.5 A, equal to 100 W. Its metal enclosure is meant to be bolted to a plate or clipped to rail inside a cabinet, and the IP10 rating means it must never be exposed outside an enclosure. Seven Star LLC supplies the ABLP1A12085 in Oman and the GCC as an independent supplier based in Muscat.

The reference follows a family pattern: ABL is the power supply prefix, the letter P names the style (panel mount), the characters 1A a series code that we do not decode, 12 the output voltage in volts and 085 the output current in tenths of an amp (here 12 V and 8.5 A, rounded). This is our reading of the pattern; the datasheet is the authority for ordering.

Choosing the ABLP1A12085: a short checklist

  • Confirm the load voltage is 12 V DC and the total current stays below 8.5 A, with margin for the derating shown in the datasheet.
  • Check the supply network: 100–240 V AC single phase.
  • Check the mounting: Top hat type TH35-15 rail conforming to IEC 60715, Top hat type TH35-7.5 rail conforming to IEC 60715, Double-profile DIN rail, panel mounting, and the space of 97 × 30 × 129 mm.
  • State the highest cabinet temperature of the installation.

Mounting, cooling and environment of the ABLP1A12085

The unit measures 97 × 30 × 129 mm and weighs 0.3 kg. Mounting options in the datasheet: Top hat type TH35-15 rail conforming to IEC 60715, Top hat type TH35-7.5 rail conforming to IEC 60715, Double-profile DIN rail, panel mounting. Protection is IP10, the overvoltage category is II, pollution degree 2 and the shock protection class is Class I. Altitude is 5000 m.

Temperature behaviour is described by mounting position (A and B are the permitted orientations; the datasheet shows incorrect mounting too). The datasheet gives these ambient bands for mounting position A: −30 to 50 °C without derating. Beyond them: 50 to 70 °C with current derating of 2 % per °C. Shock resistance is 150 m/s² for 11 ms, and a green LED shows the output voltage.

ABLP1A12085 technical specifications

Parameter Specification
Manufacturer / part number Schneider Electric / ABLP1A12085
Variant Panel mount, aluminium enclosure
Nominal input voltage 100–240 V AC single phase
Input voltage limits 90–264 V AC
Rated power 100 W
Output voltage / current 12 V DC / 8.5 A
Output voltage adjustment 10.8–13.2 V
Efficiency 88 % at 230 V AC
Power dissipation 21 W
Integrated input fuse Integrated fuse (not interchangeable) 4 A
Dimensions (W × H × D) 97 × 30 × 129 mm
Net weight 0.3 kg
Operating temperature (no derating) −30 to 50 °C without derating

Output, ripple and protection of the ABLP1A12085

The ABLP1A12085 delivers 12 V DC at 8.5 A, adjustable over 10.8–13.2 V. At 80 % utilisation the load would be 6.80 A. Residual ripple is < 120 mV, the line and load regulation is < 0.5 % at 0 to 100 % load at 25 °C and < 1 % at full voltage range in line at 25 °C, and the supply can start loads with up to 4000 µF of capacitance.

Protection includes overload and short-circuit with automatic reset, over-temperature with manual reset and overvoltage with manual reset. Output coupling is listed as parallel or serial. The connection pages of the datasheet show a parallel arrangement of at most two identical units, with equal cables and a maximum voltage difference of 25 mV, the load kept below 90 % of twice the nominal current, and a series arrangement with two diodes. The datasheet describes this parallel arrangement in terms of load sharing and does not present it as a redundancy scheme.

Input behaviour of the ABLP1A12085

The input is 100–240 V AC single phase with limits of 90–264 V AC at 50–60 Hz, one band for both 115 V and 230 V networks. The inrush current is 45 A at 115 V and 85 A at 230 V, input current is < 2.3 A 115 V AC and < 1.5 A 230 V AC and the power factor is 0.55 at 115 V AC and 0.45 at 230 V AC. An internal fuse (not interchangeable, 4 A) protects the input; the unit is listed for TN, TT and IT networks with a maximum leakage current of 1 mA 240 V AC. The datasheet adds that a switch or circuit breaker near the product must serve as the disconnecting device, that the unit is tested with branch circuit protection up to 20 A, and that it is only suitable for audio, video, information, communication, industrial and control equipment. Turn-on time is < 500 ms and the holding time is > 20 ms 115 V AC and > 40 ms 230 V AC.

The ABL Modicon power supply family around the ABLP1A12085

The thirteen references below share a 12 V, 24 V or 48 V output and differ in style, power and size.

Reference Style Output Rated power
ABLM1A24012 modular DIN-rail 24 V / 1.25 A 30 W
ABLP1A12085 panel-mount 12 V / 8.5 A 100 W
ABLP1A24045 panel-mount 24 V / 4.5 A 100 W
ABLP1A24062 panel-mount 24 V / 6.25 A 150 W
ABLP1A24100 panel-mount 24 V / 10 A 240 W
ABLS1A12062 optimised DIN-rail 12 V / 6.25 A 75 W
ABLS1A24021 optimised DIN-rail 24 V / 2.1 A 50 W
ABLS1A24031 optimised DIN-rail 24 V / 3.13 A 75 W
ABLS1A24038 optimised DIN-rail 24 V / 3.8 A 91.2 W
ABLS1A24050 optimised DIN-rail 24 V / 5 A 120 W
ABLS1A24100 optimised DIN-rail 24 V / 10 A 240 W
ABLS1A48025 optimised DIN-rail 48 V / 2.5 A 120 W

Typical uses of the ABLP1A12085 in Oman and the GCC

A 12 V, 100 W supply like this unit serves machine builders and cabinet makers who fit supplies directly on a mounting plate across Oman and the GCC: PLC and sensor supplies in water and wastewater plants, pump and ventilation controls in buildings, and instrument panels in power and oil and gas sites. The region’s heat is the main consideration. The derating-free ambient band quoted above is the figure to compare with real cabinet temperature in direct sun or in rooms without strong air conditioning; where it is exceeded, either choose a larger rating so the load stays well under the derated current or improve ventilation.

Information to send with an RFQ for the ABLP1A12085

  • Reference ABLP1A12085 and quantity.
  • Supply voltage, AC or DC, and frequency at the site.
  • Load current and any peak or capacitive start-up currents.
  • Mounting arrangement and enclosure temperature.
  • Delivery location and required date.

Documents and quotation

The manufacturer datasheet for the ABLP1A12085 is attached on this page and carries the complete specification set, including the dimension drawings and the derating information. Compare the datasheet revision with your project documents before you freeze a bill of materials.

Send us the reference ABLP1A12085, the quantity and the delivery location, and Seven Star LLC will reply to your request for quotation. We work as an independent supplier based in Muscat and serve customers across Oman and the GCC.

Other Models in the Se Abl Power Range

Seven Star LLC supplies models from the Se Abl Power range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Schneider Electric ABLM1A24012 24 V 1.25 A Power SupplyPower ModulesView details
Schneider Electric ABLP1A12085 12 V 8.5 A Power SupplyPower ModulesYou are viewing this model
Schneider Electric ABLS1A12062 12 V 6.25 A Power SupplyPower ModulesView details
Schneider Electric ABLS1A24021 24 V 2.1 A Power SupplyPower ModulesView details
Datasheets & Documents
  • PDF Datasheet Schneider Electric ABLP1A12085 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric ABLP1A12085 12 V 8.5 A Power

Answers from our engineering team on installation, compatibility and integration.

01What does the ABLP1A12085 output?
It delivers 12 V DC at 8.5 A (100 W), adjustable over 10.8–13.2 V.
02What input voltage does the ABLP1A12085 accept?
The datasheet lists 100–240 V AC single phase with limits of 90–264 V AC.
03Can two ABLP1A12085 units be paralleled?
The datasheet shows a parallel connection of at most two identical units with equal cabling and a maximum voltage difference of 25 mV. It is meant for capacity, not for redundancy.
04What protection does the ABLP1A12085 have?
Overload and short-circuit protection with automatic reset, plus over-temperature and overvoltage protection with manual reset. Ingress protection is IP10.
05What are the dimensions of the ABLP1A12085?
97 × 30 × 129 mm and a net weight of 0.3 kg. Mounting options: Top hat type TH35-15 rail conforming to IEC 60715, Top hat type TH35-7.5 rail conforming to IEC 60715, Double-profile DIN rail, panel mounting.