Schneider Electric ATV212HD22N4 ATV212 22 kW HVAC Drive 480 V

Description

ATV212HD22N4: 22 kW / 30 hp Altivar 212 HVAC drive

The ATV212HD22N4 is a Schneider Electric Altivar 212 variable speed drive, listed in its datasheet as: variable speed drive ATV212 – 22kW – 30hp – 480V – 3ph – EMC – IP21. The Altivar 212 range is specified for pumps and fans in HVAC and building services, and this reference is a 22 kW (30 hp) drive for large chilled-water pumps and cooling-tower or AHU fans drawing about 43 A. Seven Star LLC supplies the ATV212HD22N4 in Oman and the GCC as an independent supplier in Muscat.

Reading the reference: ATV212 is the range named in the datasheet, and the title gives the rest, namely 22 kW, 30 hp, 480 V, three-phase, EMC filter and IP21. Use the figures in the table below rather than decoding the letters, because the datasheet does not publish a decoding key.

Lifecycle note for the ATV212HD22N4

The datasheet of the ATV212HD22N4 carries the notices “Discontinued on: 8 Jun 2026” and “To be discontinued”. This page therefore describes a drive that the manufacturer has withdrawn. Seven Star LLC can only say what is obtainable once you send the enquiry, and a project that needs a long service life should ask about a current alternative.

Technical specifications of the ATV212HD22N4

Parameter Specification
Manufacturer / part number Schneider Electric / ATV212HD22N4
Description variable speed drive ATV212 – 22kW – 30hp – 480V – 3ph – EMC – IP21
Product specific application Pumps and fans in HVAC
Motor power 22 kW / 30 hp
Motor power range AC-3 15 to 25 kW at 380 to 440 V 3 phases
Supply voltage 380…480 V – 15…10 %; limits 323 to 528 V
Line current 33.1 A at 480 V; 41.6 A at 380 V
Apparent power 33.2 kVA at 380 V
Continuous output current 43.5 A at 380 V; 43.5 A at 460 V
Maximum transient current 47.9 A for 60 s
Output frequency / speed range 0.5 to 200 Hz / 1 to 10
EMC filter Class C2 EMC filter integrated
Switching frequency 6…16 kHz adjustable (nominal 8 kHz)
Prospective line Isc 22 kA
Communication Modbus; LonWorks; APOGEE FLN; BACnet; METASYS N2
Dimensions (W x H x D) 240 mm x 420 mm x 214 mm
Net weight 26.4 kg
Power dissipation / air flow 626 W / 214 m3/h
Noise level 59.9 dB
Power terminals 50 mm² / 1/0 AWG; torque 24 N.m, 212 lb.in
IP degree of protection IP21; IP20 and IP41 on the upper part are also listed
Ambient temperature, operation -10 to 40 °C (without derating); 40 to 50 °C (with derating factor)
Ambient temperature, storage -25 to 70 °C
Product certifications C-Tick; UL; NOM 117; CSA

Panel ventilation for the ATV212HD22N4

The datasheet gives a power dissipation of 626 W and an air flow of 214 m3/h for the ATV212HD22N4, with a noise level of 59.9 dB. Use these two numbers when you size the enclosure: the dissipation is the heat that has to leave the panel, and the air flow is the volume the drive fan moves.

The operating range is -10 to 40 °C (without derating); 40 to 50 °C (with derating factor), so in a hot switchroom the derating factor above 40 °C is not a footnote but a design condition. The datasheet gives the operating position as vertical within 10 degrees. It starts the 240 x 420 x 214 mm body, with 50 mm² (1/0 AWG) power terminals at 24 N.m, so heavy lugs and a proper torque tool are part of the job.

Output current, overload and control of the ATV212HD22N4

At 22 kW the ATV212HD22N4 lists a line current of 33.1 A at 480 V; 41.6 A at 380 V and an apparent power of 33.2 kVA at 380 V. The continuous output current is 43.5 A at 380 V; 43.5 A at 460 V with a transient of 47.9 A for 60 s, so the motor nameplate current must stay below 43.5 A if the drive is to carry it continuously; the transient figure only covers short overload.

Output frequency runs from 0.5 to 200 Hz with a speed range of 1 to 10. The motor control profiles include voltage/frequency ratio (2 points, 5 points, automatic IR compensation), an energy-saving quadratic U/f profile for fans and pumps, and sensorless flux vector control. Transient overtorque is 120 % of nominal motor torque for 60 s, and ramps are adjustable from 0.01 to 3200 s or automatic according to the load.

The line short-circuit rating is listed as 22 kA. Treat it as a design input for the supply side and compare it with the fault level of the board that feeds the drive.

Installing the ATV212HD22N4 in a panel

The ATV212HD22N4 measures 240 mm wide, 420 mm high and 214 mm deep and weighs 26.4 kg. The power terminals L1/R, L2/S and L3/T take 50 mm² / 1/0 AWG at a tightening torque of 24 N.m, 212 lb.in, while the control terminals take 2.5 mm² at 0.6 N.m.

Cable data in the datasheet distinguishes IEC cable without the mounting kit (copper 90 °C XLPE/EPR or 70 °C PVC at 45 °C) from UL 508 cable with the UL Type 1 kit (copper 75 °C PVC at 40 °C), which is relevant if the panel is built to both regimes. The relative humidity limit is 5 to 95 % without condensation, so condensation control matters in coastal switchrooms.

The ATV212HD22N4 within the ATV212 22 kW range

The table shows the ATV212HD22N4 next to the other ATV212 N4 references handled here, using each datasheet. Notice how the frame changes in steps, while the loss in watts and the output current climb continuously.

Reference Motor power Output current Power dissipation W x H x D (mm)
ATV212HU30N4 3 kW / 4 hp 7.2 A 137 W 142 x 184 x 150
ATV212HU40N4 4 kW / 5 hp 9.1 A 176 W 142 x 184 x 150
ATV212HU55N4 5.5 kW / 7.5 hp 12 A 215 W 142 x 184 x 150
ATV212HU75N4 7.5 kW / 10 hp 16 A 291 W 180 x 232 x 170
ATV212HD11N4 11 kW / 15 hp 22.5 A 430 W 180 x 232 x 170
ATV212HD15N4 15 kW / 20 hp 30.5 A 625 W 245 x 330 x 190
ATV212HD22N4 22 kW / 30 hp 43.5 A 626 W 240 x 420 x 214
ATV212HD30N4 30 kW / 40 hp 58.5 A 847 W 240 x 420 x 214
ATV212HD37N4 37 kW / 50 hp 79 A 976 W 240 x 550 x 244
ATV212HD45N4 45 kW / 60 hp 94 A 1253 W 240 x 550 x 244

Start-up checklist for the ATV212HD22N4

On first start enter the motor nameplate data, set the lower and upper frequency limits and the acceleration and deceleration times, and confirm the direction of rotation on an uncoupled motor where possible. The drive has a red LED that shows the DC bus is energised; wait for it to go out before touching the power terminals.

If this drive is a spare for a running plant, record the settings of the old drive first, because settings may have to be re-entered rather than copied across. Send us the nameplate data and we will confirm the correct reference.

Information to send with an RFQ for the ATV212HD22N4

  • Full reference ATV212HD22N4 and the quantity
  • Motor nameplate power, current and voltage
  • Application (pump or fan), supply voltage and frequency
  • Building-management protocol required
  • Delivery location and timing

Documents and quotation

A datasheet for this product is attached on this page. It lists the electrical, mechanical and environmental data summarised above, and it is the document to check against your own drawings.

Send us the part number, quantity and application and we will confirm availability and a quotation. Seven Star LLC is an independent supplier in Muscat and is not affiliated with the manufacturer.

Other Models in the Se Atv212 N4 Range

Seven Star LLC supplies models from the Se Atv212 N4 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Schneider Electric ATV212HD11N4 ATV212 11 kW HVAC Drive 480 VAC DrivesView details
Schneider Electric ATV212HD15N4 ATV212 15 kW HVAC Drive 480 VAC DrivesView details
Schneider Electric ATV212HD22N4 ATV212 22 kW HVAC Drive 480 VAC DrivesYou are viewing this model
Schneider Electric ATV212HD30N4 ATV212 30 kW HVAC Drive 480 VAC DrivesView details
Schneider Electric ATV212HD37N4 ATV212 37 kW HVAC Drive 480 VAC DrivesView details
Datasheets & Documents
  • PDF Datasheet Schneider Electric ATV212HD22N4 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric ATV212HD22N4 ATV212 22 kW HVAC

Answers from our engineering team on installation, compatibility and integration.

01What motor power does the ATV212HD22N4 drive?
The datasheet lists 22 kW (30 hp) on a 380 to 480 V three-phase supply, with a continuous output current of 43.5 A at 380 V; 43.5 A at 460 V.
02Does the ATV212HD22N4 have an EMC filter?
Yes. The datasheet lists a Class C2 EMC filter integrated in the drive, together with IEC 61800-3 categories C2 and C3.
03Which communication protocols are listed for the ATV212HD22N4?
The datasheet lists Modbus, BACnet, METASYS N2, APOGEE FLN and LonWorks. The built-in port is 2-wire RS 485, and LonWorks uses an option card.
04What are the size and heat loss of the ATV212HD22N4?
The datasheet gives 240 mm x 420 mm x 214 mm and a net weight of 26.4 kg, a power dissipation of 626 W and an air flow of 214 m3/h.
05Is the ATV212HD22N4 still available?
The datasheet shows a discontinuation date of 8 Jun 2026. Send us the enquiry and we will tell you what can still be supplied.