- Automation & ControlView all 2,610 products
- Automation Accessories
- AC Drives
- PLC & I/O Cards
- Industrial Communications
- Vibration Monitoring
- Controllers & Data Acquisition
- Isolator & Barrier
- Safety Switches & Guard Locking
- Motor Soft Starters
- CCTV & Security
- Encoders
- HMI Displays
- Pneumatic Cylinders
- Servo Drives
- Industrial Computers
- Machine Vision
- Automation Software
- Robotics
Brand: Schneider Electric
Schneider Electric LC1D32U7 32 A TeSys Deca Contactor
Description
LC1D32U7: 32 A TeSys Deca contactor with 240 V AC coil
The LC1D32U7 is a Schneider Electric TeSys Deca contactor that the datasheet describes as TeSys D contactor – 3P(3 NO) – AC-3 – <= 440 V 32 A – 240 V AC 50/60 Hz coil. The 32 A reference shares the 85 x 45 x 92 mm housing with the 25 A and 38 A versions, so panel layouts do not change when the AC-3 rating steps up; the datasheet gives 32 A in AC-3 and 50 A in AC-1. Seven Star LLC supplies the LC1D32U7 in Oman and the GCC as an independent supplier based in Muscat.
Reading the reference: LC1D is the TeSys Deca three-pole contactor family, the figure 32 is the frame and current class, and the final letters U7 point to the coil. The datasheet confirms the coil as 240 V AC 50/60 Hz, so no further ordering table is needed to see what is fitted.
Weight is 0.375 kg and mechanical durability is 15 million cycles, the same as its smaller neighbour, while the AC-3 electrical durability is stated at 1.65 million cycles at 32 A.
Technical specifications of the LC1D32U7
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Schneider Electric / LC1D32U7 |
| Description | TeSys D contactor – 3P(3 NO) – AC-3 – <= 440 V 32 A – 240 V AC 50/60 Hz coil |
| Range | TeSys Deca Advanced |
| Device short name | LC1D |
| Poles / contact composition | 3P / 3 NO |
| Contactor application | Resistive load; Motor control |
| Utilisation categories | AC-3; AC-3e; AC-1; AC-4 |
| Rated operational voltage | Power circuit: <= 690 V AC 25 to 400 Hz; Power circuit: <= 300 V DC |
| Rated operational current AC-3 (≤440 V) | 32 A (below 60 °C) |
| Rated operational current AC-1 | 50 A at up to 440 V AC (below 60 °C) |
| Control circuit voltage | 240 V AC 50/60 Hz |
| Rated breaking capacity | 550 A at 440 V for power circuit |
| Associated gG fuse, coordination type 1 / type 2 | 63 A / 63 A |
| Rated insulation voltage Ui / impulse Uimp | 690 V / 6 kV |
| Mechanical durability | 15 Mcycles |
| Electrical durability | 1.65 million cycles at 32 A in AC-3 and 1.4 million cycles at 50 A in AC-1 (Ue up to 440 V) |
| Coil technology | Without built-in suppressor module |
| Inrush / hold-in power (50 Hz) | 70 VA / 7 VA |
| Operating time | 4 to 19 ms opening; 12 to 22 ms closing |
| Auxiliary contacts | 1 NO + 1 NC |
| Mounting | Rail; Plate |
| Ingress protection | IP20 front face conforming to IEC 60529 |
| Ambient temperature around the device | -40 to 60 °C |
| Dimensions H x W x D | 85 mm x 45 mm x 92 mm |
| Net weight | 0.375 kg |
| Certifications listed | UL; CCC; CSA; Marine; UKCA; EAC; CB Scheme |
Motor ratings of the LC1D32U7 at each supply voltage
| Supply voltage (AC, 50/60 Hz) | Motor power in AC-3 (kW) |
|---|---|
| 220/230 V | 7.5 kW |
| 380/400 V | 15 kW |
| 415/440 V | 15 kW |
| 500 V | 18.5 kW |
| 660/690 V | 18.5 kW |
AC-3 is the category for squirrel-cage motors started and stopped while running; the datasheet converts the 32 A rating into the motor powers above for each supply voltage. At 380/400 V the LC1D32U7 is listed for 15 kW. For heavier duty such as inching or plugging the AC-4 category applies and the datasheet lists 7.5 kW at 400 V, which is lower because those duties wear the contacts faster. The same device is rated 50 A in AC-1, the category for resistive loads such as heaters, so it can switch a higher current when the load is not a motor.
Coil and control supply of the LC1D32U7
The coil of the LC1D32U7 is rated 240 V AC at 50/60 Hz. That fits a 240 V control supply; in Oman the phase-to-neutral voltage of the 415 V network is normally in this region, so the coil can be fed directly from phase and neutral.
According to the datasheet the contactor operates between 0.8 and 1.1 times Uc at 50 Hz, which for this coil is about 192 V to 264 V, and between 0.85 and 1.1 times Uc at 60 Hz (204 V to 264 V). Drop-out occurs between 0.3 and 0.6 times Uc, about 72 V to 144 V, which is the range to remember when a weak control supply makes the contactor chatter instead of opening cleanly.
Inrush is 70 VA at 50 Hz (70 VA at 60 Hz) and hold-in is 7 VA (7.5 VA at 60 Hz). Dividing by the coil voltage gives roughly 0.29 A on closing and 0.03 A when held; these are calculated approximations for sizing the control transformer or PLC interposing relay, not datasheet figures. The datasheet gives closing in 12 to 22 ms and opening in 4 to 19 ms.
The coil is described as without built-in suppressor module, so inductive switching of the coil can disturb sensitive electronics on the same control circuit unless a suppressor is added separately; check accessory compatibility with the supplier before ordering one.
Protection, coordination and service life of the LC1D32U7
For short-circuit protection the datasheet pairs the LC1D32U7 with a 63 A gG fuse at up to 690 V for coordination type 1 and 63 A gG for type 2. Type 2 is the stricter level: the contactor must remain usable after a fault, with at most light welds that can be separated. The rated breaking capacity is 550 A at 440 V for power circuit and the short-time withstand current is listed as 60 A 40 °C – 10 min for power circuit for the power circuit.
Contact life is stated as 15 Mcycles mechanically and, electrically, 1.65 million cycles at 32 A in AC-3 and 1.4 million cycles at 50 A in AC-1 (Ue up to 440 V). The maximum operating rate is 3600 cyc/h at 60 °C. For functional-safety calculations the datasheet gives a B10d of 1,369,863 cycles at nominal load and 20,000,000 cycles at mechanical load, per EN/ISO 13849-1.
The auxiliary block built into the LC1D32U7 is 1 NO + 1 NC; the datasheet notes the contacts are mechanically linked and that the NC is a mirror contact to IEC 60947-4-1, so it can be used in a safety circuit to prove that the main contacts have opened. The signalling circuit is specified for a minimum of 17 V and 5 mA.
Where the LC1D32U7 sits among the LC1D frames
The same coil letters appear on the 25 A and 38 A references, so a plant that standardises on one control voltage can keep one coil code across three current ratings. Other coil versions of the same frame that we handle are LC1D32B7, LC1D32F7, LC1D32M7, LC1D32P7; they carry the same power circuit and differ only in the coil voltage.
| Frame | AC-3 current | AC-3 kW at 380/400 V | AC-1 current | Body H x W x D | Net weight | Mechanical life |
|---|---|---|---|---|---|---|
| LC1D25.. | 25 A | 11 kW | 40 A | 85 x 45 x 92 mm | 0.37 kg | 15 Mcycles |
| LC1D32 (this frame) | 32 A | 15 kW | 50 A | 85 x 45 x 92 mm | 0.375 kg | 15 Mcycles |
| LC1D38.. | 38 A | 18.5 kW | 50 A | 85 x 45 x 92 mm | 0.38 kg | 15 Mcycles |
The 15 kW rating at 380/400 V places it in the range of circulation pumps, supply and exhaust fans, screw compressors of modest size and mixer drives.
Selecting and ordering the LC1D32U7
- Motor power or load current at your supply voltage, and the duty category: AC-3 for starting, AC-4 for plugging and inching, AC-1 for resistive loads. This LC1D32U7 is rated 32 A AC-3 and 50 A AC-1.
- Coil voltage: this reference is 240 V AC; any other control voltage needs a different suffix, so state the control supply before quoting.
- Panel space: 85 mm x 45 mm x 92 mm and 0.375 kg for this body, mounted on rail or plate.
- Overload protection and the fuse or breaker that will be paired with the contactor, using the coordination values above.
- Any auxiliary or mechanical interlock accessories, the quantity, and whether the unit is for new work or a replacement of an existing LC1D device.
Mounting, wiring and commissioning of the LC1D32U7
Mount the LC1D32U7 on a 35 mm rail or screw it to a plate with the clearances of the installation sheet. The datasheet lists a flexible power conductor range of 2.5 to 10 mm² on connector 1 and 2.5 to 10 mm² on the second connector (without cable end), with a power-terminal torque of 2.5 N.m; the control terminals take 1.7 N.m on this frame except where the datasheet states otherwise. Keep control cabling apart from the power cables and fit the protective cover.
Typical applications of the LC1D32U7 in Oman and the GCC
Oil and gas facilities, power stations and petrochemical plants use contactors of this size for auxiliary drives: lube-oil pumps, ventilation, dosing, sump and transfer pumps. The LC1D32U7 suits designs that need a 240 V AC control voltage and a compact body. The datasheet lists marine and other certifications for the reference (see the table), but confirm the approval required by the project against the exact reference.
On construction and industrial sites around Muscat, Sohar and Salalah the LC1D32U7 replaces or extends starters on conveyors, crushers, compressors and washdown pumps. Dust and humidity make enclosure ratings and regular cleaning important. The datasheet lists a protective treatment of TH conforming to IEC 60068-2-30, which is relevant for damp heat.
Documents and quotation
A datasheet for the LC1D32U7 is attached on this page, listing the electrical, mechanical and environmental data used above. Send us the part number, quantity and application and we will confirm availability and a quotation.
Seven Star LLC is an independent supplier in Muscat and is not affiliated with the manufacturer.
Other Models in the Se Lc1d 32 Range
Seven Star LLC supplies models from the Se Lc1d 32 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Schneider Electric LC1D32B7 32 A TeSys Deca Contactor | Contactors & Overload Relays | View details |
| Schneider Electric LC1D32F7 32 A TeSys Deca Contactor | Contactors & Overload Relays | View details |
| Schneider Electric LC1D32M7 32 A TeSys Deca Contactor | Contactors & Overload Relays | View details |
| Schneider Electric LC1D32P7 32 A TeSys Deca Contactor | Contactors & Overload Relays | View details |
| Schneider Electric LC1D32U7 32 A TeSys Deca Contactor | Contactors & Overload Relays | You are viewing this model |
Datasheets & Documents
- Datasheet Schneider Electric LC1D32U7 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.
Schneider Electric company profile
| Origins | 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry |
|---|---|
| Headquarters | Rueil-Malmaison (Paris region), France |
| Ownership | Public company listed on Euronext Paris |
| Key acquisitions | Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software |
| Brand names still in use | Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform |
| Product families | Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software |
Milestones
- 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
- 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
- 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
- 1997: Modicon, the company behind the first programmable logic controller, joins the group.
- 1999: The group takes the name Schneider Electric.
- 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.
Choosing Schneider Electric breakers and motor control
Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.
Where Schneider Electric products are used
In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.
APC by Schneider Electric: UPS and critical power
Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.
Schneider Electric products we list
| Family | Examples |
|---|---|
| Circuit breakers | Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW |
| Motor control | TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480 |
| Drives | Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo |
| PLCs, HMIs and relays | Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655 |
| Protection, metering and power | Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS |
Ordering Schneider Electric products: what we need
Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.
Facts checked against Schneider Electric's published company history, October 2026.
Browse Schneider Electric products by category: Circuit Breaker, Electrical & Power Modules, AC Drives, PLC & I/O Cards, Metering Systems, UPS and Batteries.
FAQ
Questions about the Schneider Electric LC1D32U7 32 A TeSys Deca
Answers from our engineering team on installation, compatibility and integration.
01What is the rated current of the LC1D32U7?
The datasheet lists 32 A in AC-3 and 50 A in AC-1 at up to 440 V AC, both for operation below 60 °C.
02What coil does the LC1D32U7 use?
The control circuit voltage is 240 V AC 50/60 Hz. It is an AC coil for 50/60 Hz without a built-in suppressor module.
03What are the dimensions and weight of the LC1D32U7?
The datasheet gives 85 mm high, 45 mm wide and 92 mm deep, with a net weight of 0.375 kg.
04How is the LC1D32U7 mounted?
The datasheet lists mounting on rail or plate. Power and control terminals are accessible from the front with the protective cover fitted.
05What is the electrical life of the LC1D32U7?
The datasheet states 1.65 million cycles at 32 A in AC-3 and 1.4 million cycles at 50 A in AC-1 (Ue up to 440 V) and a mechanical durability of 15 Mcycles. Real life depends on the load category and switching rate.


















Reviews