Schneider Electric LUB12 TeSys Ultra Power Base 12 A

Description

LUB12 power base of a TeSys Ultra motor starter

The LUB12 is a Schneider Electric product listed in the datasheet as: Power base, TeSys Ultra, 12 A, screw clamps control. The LUB12 is the power part of a TeSys Ultra starter: it contains the contacts, the isolation function and the circuit-breaker-like short-circuit protection for a 12 A motor. A control unit (such as an LUCA or LUCM model) plugs into the front and decides how the motor is protected and controlled. Seven Star LLC supplies the LUB12 in Oman and the GCC as an independent supplier based in Muscat.

Reading the reference: LU marks TeSys Ultra, B the power base, and 12 the maximum motor current in amperes. The datasheet describes it as a non-reversing three-pole base with isolation capability.

Technical specifications of the LUB12

Parameter Specification
Manufacturer / part number Schneider Electric / LUB12
Description Power base, TeSys Ultra, 12 A, screw clamps control
Range TeSys
Product name TeSys Ultra
Device short name LUB
Product or Component Type Non reversing power base
Device Application Motor control; Motor protection
Poles description 3P
Suitability for isolation Yes
[Ue] rated operational voltage 690 V AC power circuit
Network frequency 40 to 60 Hz
[Ith] conventional free air thermal 12 A
[Ie] rated operational current 12 A <= 440 V; 12 A 500 V; 9 A 690 V
Utilisation category AC-43; AC-44; AC-41
[Ics] rated service breaking 50 kA 230 V
capacity 50 kA 440 V; 10 kA 500 V; 4 kA 690 V
Auxiliary contact composition 1 NO + 1 NC
Auxiliary contacts type Linked contacts 1 NO + 1 NC IEC 60947-4-1; Mirror contact 1 NC IEC 60947-1
[Uc] control circuit voltage 24 V AC 50/60 Hz; 24 V DC; 48 to 72 V AC 50/60 Hz; 48 to 72 V DC; 110 to 240 V AC 50/60 Hz; 110 to 220 V DC
Typical current consumption 130 mA 24 V DC I maximum while closing with LUCA, LUCB, LUCC, LUCD; 140 mA 24 V AC I maximum while closing with LUCA, LUCB, LUCC, LUCD
Heat dissipation 2 W control circuit with LUCA, LUCB, LUCC, LUCD; 1.7 W control circuit with LUCM
Safety reliability level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Operating time 35 ms opening with LUCA, LUCB, LUCC, LUCD, LUCM control circuit; 50 ms >= 72 V closing with LUCA, LUCB, LUCC, LUCD control circuit
Mechanical durability 15 Mcycles
maximum operating rate 3600 cyc/h
Product Certifications CE; UL; CSA; CCC; EAC; ASEFA; ATEX; Marine
Standards EN 60947-6-2; IEC 60947-6-2; UL 60947-4-1, with phase barrier; CSA C22.2 No 60947-4-1, with phase barrier
[Ui] rated insulation voltage 690 V IEC 60947-6-2 3; 600 V UL 60947-4-1; 600 V CSA C22.2 No 60947-4-1
[Uimp] rated impulse withstand 6 kVIEC 60947-6-2
Safe separation of circuit 400 V SELV between the control and auxiliary circuits IEC 60947-1 appendix N
Fixing mode Clipped (DIN rail); Screw-fixed (plate)
Connections – terminals Control circuit: screw clamp terminals 1 cable(s) 0.34 to 1.5 mm² flexible with cable end
Width 45 mm
Height 154 mm
Depth 126 mm
Net Weight 0.9 kg
Compatibility code LUB
IP degree of protection IP20 IEC 60947-1 front panel and wired terminals; IP20 IEC 60947-1 other faces; IP40 IEC 60947-1 front panel outside connection zone
Ambient air temperature (operation or storage, as listed) -25 to 60 °C with LUCM
operation -25 to 70 °C with LUCA, LUCB, LUCC, LUCD
Fire resistance 960 °C parts supporting live components IEC 60695-2-12; 650 °C IEC 60695-2-12
Operating altitude 2000 m

How the TeSys Ultra power base and control unit work together

Suitable for isolation: Yes. Rated operational current: 12 A <= 440 V; 12 A 500 V; 9 A 690 V. Utilisation categories: AC-43; AC-44; AC-41. Service breaking capacity: 50 kA 230 V. Control voltage: 24 V AC 50/60 Hz; 24 V DC; 48 to 72 V AC 50/60 Hz; 48 to 72 V DC; 110 to 240 V AC 50/60 Hz; 110 to 220 V DC. Auxiliary contacts: 1 NO + 1 NC.

A TeSys Ultra starter is two parts: the power base switches and protects the motor circuit, and the control unit holds the protection settings and the communication. The same base can take different control units, from simple standard types to multifunction units with diagnostics, which is why the base alone does not set thermal protection behaviour.

Where the LUB12 fits and what it combines with

The base accepts standard control units (LUCA, LUCB and LUCC types), advanced ones (LUCM), and communication modules; the specific list of compatible control units is on the datasheet. A base of this size is for motors up to 12 A, which at 400 V is roughly 5.5 kW.

Because the starter combines breaker and contactor functions in a compact housing, it is an alternative to a separate motor circuit breaker, contactor and overload set when panel space is tight.

Selection checklist for the LUB12

  • Motor full-load current below 12 A.
  • Which control unit is plugged in; the base does not set overload class.
  • Control voltage for the coil: see the table above.
  • Need for add-on modules for communications or a reversing function.
  • Short-circuit rating at the supply voltage from the datasheet.
  • Spare control units on site: they are field-replaceable.

Installing and servicing the LUB12

Mount on 35 mm rail or plate, fit the control unit by plugging it into the front, and connect motor and supply to the power terminals. The control unit locks into the base, and the power base can be isolated with the front lever.

Check tightness after the first week of operation, as thermal cycling can loosen screw terminals, and verify that the control unit matches the motor current before the first start.

Typical applications of the LUB12 in Oman and the GCC

Typical use is as a compact starter for a motor on small pumps, fans, conveyors and process units in the region. Because of the narrow body, they are popular in compact MCCs and skid-mounted panels.

Dimensions, environment and approvals of the LUB12

For the LUB12, plan the mounting space from the datasheet: 45 mm (W) x 154 mm (H) x 126 mm (D). The LUB12 weighs 0.9 kg. Mounting, derating and enclosure choices follow the environmental data below, which should be compared with the actual panel temperature and the dust and humidity of the site in Oman and the GCC.

Ambient temperature limits in the datasheet: -25 to 60 °C with LUCM. Ingress protection: IP20 IEC 60947-1 front panel and wired terminals; IP20 IEC 60947-1 other faces; IP40 IEC 60947-1 front panel outside connection zone. Operating altitude: 2000 m. Vibration resistance: 2 gn 5 to 300 Hz power poles open IEC 60068-2-27; 4 gn 5 to 300 Hz power poles closed IEC 60068-2-27. Shock resistance: 10 gn power poles open IEC 60068-2-27; 15 gn power poles closed IEC 60068-2-27. Standards listed: EN 60947-6-2; IEC 60947-6-2; UL 60947-4-1, with phase barrier; CSA C22.2 No 60947-4-1, with phase barrier. Certifications listed for this reference: CE; UL; CSA; CCC; EAC; ASEFA; ATEX; Marine.

Information to send with an RFQ for the LUB12

  • Full reference and quantity required
  • Existing equipment, panel or rack it must fit
  • Supply voltage, load or signal details of the application
  • Required delivery location and timing
  • Whether a spare, a replacement or a new installation

Documents and quotation

A datasheet for this product is attached on this page. It lists the electrical, mechanical and environmental data summarised above.

Send us the part number, quantity and application and we will confirm availability and a quotation. Seven Star LLC is an independent supplier in Muscat and does not represent itself as an official channel of the manufacturer.

Datasheets & Documents
  • PDF Datasheet Schneider Electric LUB12 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric LUB12 TeSys Ultra Power Base 12 A

Answers from our engineering team on installation, compatibility and integration.

01What current can the LUB12 handle?
The datasheet gives 12 A <= 440 V; 12 A 500 V; 9 A 690 V.
02Is the LUB12 suitable for isolation?
Stated as Yes.
03What utilisation categories apply?
Listed: AC-43; AC-44; AC-41.
04What is the control voltage for the LUB12?
Listed: 24 V AC 50/60 Hz; 24 V DC; 48 to 72 V AC 50/60 Hz; 48 to 72 V DC; 110 to 240 V AC 50/60 Hz; 110 to 220 V DC.
05What is its mechanical life?
The datasheet gives 15 Mcycles.