Brand:

Sauter VUG050F304 DN50 Kvs 40 Flanged Control Valve PN25

Description

The VUG050F304 is a DN 50 flanged two-way control valve from the Sauter VUG series, rated PN 25/16 with a Kvs of 40 m³/h. Its ductile-iron body, stainless-steel trim and 20 mm stroke make it a main-branch valve for chilled-water, hot-water and low-temperature steam loops in building services, driven by Sauter SUT valve actuators.

A DN 50 branch valve for plant rooms and risers

Valves in this size usually control an air-handling-unit coil bank, a heat-exchanger secondary or a riser branch. The datasheet limits the VUG to continuous control of cold and hot water in closed circuits, with a flange to EN 1092-2 form B so it bolts between standard counter-flanges. At DN 50 the plug is stainless steel with a glass-fibre-reinforced PTFE sealing ring, and the leakage rate at maximum Δps is 0.05 % of Kvs or less. Steam service up to 200 °C is also permitted with the same Δpmax values, provided the valve is not run mainly in the lower third of its stroke.

Key features from the datasheet

  • Equal-percentage characteristic; SUT actuators can switch it to linear or quadratic
  • Control ratio above 50:1; valve closed when the spindle is moved out; closing against or with the pressure
  • Valve body of ductile cast iron EN-GJS-400-18U-LT, painted matt jet black RAL 9005
  • Seat of 1.4021 and spindle and plug of 1.4305 stainless steel
  • Maintenance-free brass stuffing box with six tapered PTFE rings, a spring and a grease reserve
  • PED fluid group II; this DN 50 type carries the CE mark

Technical specification

Parameter Specification
Order code VUG050F304
Description Flanged through valve, PN 25/16 (el.)
Nominal diameter DN 50
Kvs value 40 m³/h
Valve stroke 20 mm
Nominal pressure PN 25/16
Connection Flange EN 1092-2, form B; fitting length EN 558-1 basic series 1
Operating temperature -10 to 200 °C
Operating pressure (PN 25) 25 bar at 30 to 120 °C; 21.7 bar at 200 °C
Characteristic Equal percentage
Leakage rate 0.05 % of Kvs or less at maximum Δps
Weight 13.8 kg
Max. Δpv, against / with pressure 12 bar / 6 bar
Valve body EN-JS 1049 (EN-GJS-400-18U-LT)
Valve seat 1.4021, X20Cr13
Spindle and plug 1.4305, X8CrNiS18-9
Plug seal PTFE, glass-fibre reinforced
Stuffing box CW617N, CuZn40Pb2
Dimensions A 126, c 67, L 230, H 20, k 125 mm; flange holes 19 x 4, b 19 mm

Selection and ordering guide

The first digits give the nominal size and the last digit group the PN rating; DN 15 to 50 are PN 25/16, while DN 65 appears as both VUG065F316 (PN 16) and VUG065F304 (PN 25). Neighbouring sizes are separate orders.

Order code DN Kvs m³/h Stroke Weight
VUG040F304 40 25 20 mm 11.2 kg
VUG050F304 50 40 20 mm 13.8 kg
VUG065F304 65 63 40 mm 25 kg
VUG080F304 80 100 40 mm 37 kg

Closing against the pressure, the datasheet gives Δpmax for DN 50 of 4.0 bar with AVM 322 (1000 N), 11.0 bar with AVM 234S (2500 N), 8.5 bar with AVF 234S (2000 N, spring return, Δps 8.5 bar) and 4.0 bar with AVN 224S (1100 N). Warranty applies only with Sauter actuators.

Installation and operation notes

  • Mount the actuator directly on the valve with screws; take care not to turn the plug on the seat. The actuator finds the lower seat on commissioning and sets the stroke automatically.
  • Fit in any position except suspended; horizontal fitting is limited to 25 kg of weight on the valve.
  • Flush the system before commissioning (DIN EN 14336) and fit collecting filters; water quality per VDI 2035; glycol 20 % to 55 %.
  • Above 130 °C use intermediate piece 0372336180 and above 180 °C adapter 0372336240; insulate the valve only up to the actuator connecting clip.
  • Observe the flow direction arrow; when closing with the pressure the arrow must be pasted over per the fitting instructions.
  • Not suitable for drinking-water installations, ATEX zones or safety functions.

Applications in Gulf building services

Large GCC buildings combine long chilled-water risers with high static head, so a PN 25 flanged valve with robust seating is a common pick for AHU coils, plate heat exchangers and district-cooling interface skids. Dust and sand ingress is a site-level matter, but the datasheet requirement for filters and flushing applies to every new Gulf project. Hot-water and low-pressure steam duty up to 200 °C is within the stated range.

Selection and installation notes

A control valve is selected from the flow and the pressure drop, not only from the pipe size. Confirm the Kvs value, the pressure class, the medium and temperature, and the actuator that suits the valve stroke. Fit the valve with the flow direction shown on the body, provide room for the actuator, flush the line before fitting and check the valve travel at commissioning.

Information needed for a quotation

Send the full model code, the quantity, the delivery location in Oman or the GCC, the intended use and any accessories needed, so that the complete package can be quoted together.

Documents and supply information

The manufacturer data sheet is attached to this page and should be read together with the project specification and the site risk assessment before a purchase is confirmed. Ratings, standards and dimensions are quoted as printed on that sheet. Lead time, stock position and certificates available with the shipment are confirmed in the quotation, and we supply to Oman and the wider GCC region for industrial, utility and building services projects.

Accessories and related items

Item Description
0372336180 Intermediate piece for medium 130 to 180 °C
0372336240 Adapter for medium 180 to 200 °C
0378284100 / 102 Stuffing box heater 230 VAC / 24 VAC, 15 W, below 0 °C
0560260001 Stuffing box for cold-water use with silicone-containing grease
Actuators AVM 322(S), AVM 234S, AVF 234S, AVN 224S

Frequently asked questions

What flange standard does the VUG050F304 use?

Flange connection to EN 1092-2, seal form B, with fitting length to EN 558-1 basic series 1; the drilling for DN 50 is 4 holes of 19 mm on a 125 mm circle.

Which actuators drive this valve?

The datasheet lists AVM 322(S), AVM 234S, AVN 224S and the spring-return AVF 234S. Pressure ratings apply only with Sauter actuators.

Can it control steam?

Yes, up to 200 °C with the same Δpmax values as in the combination tables, but do not run it mostly in the lower third of the stroke.

Is it approved for drinking water or hazardous areas?

No. The datasheet states it is not suitable for drinking-water installations, ATEX zones or safety functions.

Who supplies the VUG050F304 in Oman?

Seven Star LLC is an independent supplier in Muscat and quotes against the exact order code; confirm the actuator, voltage and accessories before ordering.

Documents and quotation

The official Fr. Sauter AG product data sheet 13.6 56.120 (edition 2025) is linked on this page. Send the order code, quantity and application to request a quotation. See more in Globe Valves.

Datasheets & Documents
  • PDF Datasheet Sauter VUG product data sheet 13.6 56.120 (PDF) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

SAUTER is a Swiss building automation company, founded in 1910 by Fritz Sauter in Grindelwald, where he made timers to switch street lights. The company moved to Basel in the 1910s, where it is still headquartered, and in 1935 turned toward control technology. Its first software-controlled building management system followed in 1974. SAUTER is privately owned by the founding families.

Seven Star LLC is an independent supplier in Muscat. We list SAUTER field devices against exact order codes and the official SAUTER data sheets, for HVAC contractors and facility teams in Oman and the GCC.

SAUTER company profile

Founded 1910, Grindelwald, Switzerland, by Fritz Sauter
Headquarters Basel, Switzerland
Ownership Founding families, privately held
First products Timers for street lighting
Product families EY-modulo automation stations, SAUTER Vision Center building management software, ecos room controllers, control valves and valve actuators, damper actuators, temperature, humidity and pressure sensors

Milestones

  • 1910: Fritz Sauter starts making timers in Grindelwald.
  • 1935: SAUTER moves into control technology.
  • 1974: The first software-controlled building management system is introduced.

SAUTER product series

Valves and actuators include the VUG050F304 DN50 flanged control valve, the VKAI032F300 DN32 cut-off ball valve, the AKM115F120 rotary actuator for ball valves and the ASF112F222 spring-return damper actuator.

Sensors and controllers include the EGP100F412 differential pressure transducer, the EGQ222F032 CO2 and temperature room transducer, the EGT346F103 Ni1000 duct temperature sensor and the NRFC413MF111 Modbus fan coil thermostat. Safety devices include the TUC407F001 safety temperature limiter to EN 14597 and the DSF158F001 stainless pressure switch with SIL 2.

Where SAUTER products are used

Air handling units and fan coils, chilled and hot water circuits, boiler plants and room control in hotels, hospitals, offices, schools and laboratories connected to a building management system.

SAUTER products we list

Family Examples
Valve Actuators AKM115F120 8 Nm 230 V Rotary Actuator fo…, ASF112F222 7 Nm 24 V Spring-Return Dampe…
Temperature Instrumentation EGT346F103 Ni1000 Duct Temperature Senso…, TUC407F001 Safety Temperature Limiter 95…
Pressure Instrumentation EGP100F412 Differential Pressure Transdu…
Gas Analyzer Systems EGQ222F032 CO2 and Temperature Room Tran…
Controllers & Data Acquisition NRFC413MF111 Modbus Fan Coil Thermostat…

Ordering SAUTER products: what we need

Send the full SAUTER order code, such as VUG050F304. If unknown, give the valve size, Kvs and pressure rating, the actuator torque or force, control signal and supply voltage, and for sensors the range, output and mounting.

Facts checked against SAUTER's own history page (sauter-controls.com), October 2026.

Frequently Asked Questions

What flange standard does the VUG050F304 use?
Flange connection to EN 1092-2, seal form B, with fitting length to EN 558-1 basic series 1; the drilling for DN 50 is 4 holes of 19 mm on a 125 mm circle.
Which actuators drive this valve?
The datasheet lists AVM 322(S), AVM 234S, AVN 224S and the spring-return AVF 234S. Pressure ratings apply only with Sauter actuators.
Can it control steam?
Yes, up to 200 °C with the same Δpmax values as in the combination tables, but do not run it mostly in the lower third of the stroke.
Is it approved for drinking water or hazardous areas?
No. The datasheet states it is not suitable for drinking-water installations, ATEX zones or safety functions.
Who supplies the VUG050F304 in Oman?
Seven Star LLC is an independent supplier in Muscat and quotes against the exact order code; confirm the actuator, voltage and accessories before ordering.