Brand: SOR
SOR 2700 Ultrasonic Point Level Switch
Description
An ultrasonic point level switch with no moving parts and no calibration
The SOR 2700 is a single or dual point ultrasonic level switch for the economical detection of clean liquids. A sensor with a gap contains two piezoelectric crystals: one transmits sound across the gap and the other receives it. Sound crosses a liquid-filled gap strongly and an air-filled gap weakly, and the electronics switch a relay on the difference. There is no calibration or set-up; SOR states that maintenance is limited to an annual visual inspection.
A field-selectable failsafe (high or low level), an adjustable time delay of 0 to 30 seconds and a self-test button come standard. Dual-point units can be used as two independent alarm points or together for pump-up or pump-down control logic at no extra cost.
Technical specifications
| Parameter | Specification |
|---|---|
| Manufacturer / series | SOR Inc. (SOR Controls Group), 2700 Series ultrasonic level switches |
| Model | 2700 (electronics) with 371 single-point or 372 dual-point sensor |
| Input power | 120/240 VAC, 50/60 Hz, or 24 VDC |
| Current draw (max.) | 70 mA at 24 VDC; 40 mA at 120 VAC; 20 mA at 240 VAC |
| Output, standard | Single point 10 A SPDT, 250 VAC / 24 VDC; dual point two 10 A SPDT (DC rating for resistive loads) |
| Output, HR/RG accessory | 2 A SPDT, 250 VAC / 24 VDC (per point) |
| Response time | 250 ms on, 250 ms off |
| Repeatability | 0.078 in (2 mm) |
| Time delay / failsafe | 0 to 30 s adjustable / field-selectable |
| Enclosure / conduit | NEMA 4X, IP65 / 3/4 in NPT |
| Remote distance from sensor | Up to 50 ft (15.2 m), cable 1 to 50 ft |
| Ambient temperature | -40 to 160 F (-40 to 71 C) |
| Process temperature | -40 to 250 F (-40 to 121 C) |
| Maximum process pressure | 2,000 psig (138 bar); flange ratings 275 psig (150#) or 720 psig (300#) |
| Sensor types | U (vertical gap, 701) or N (horizontal notch gap, 711/721) |
| Sensor materials | 316SS standard; Monel, Carpenter 20 or Hastelloy C (N type) |
| Probe length | U: 1.2 in and 1.7 to 180 in; N: 2 to 180 in (U flanged from 3 in) |
| Process connections | 3/4, 1, 1-1/2 or 2 in NPT; 1 to 4 in ANSI RF flanges, 150# or 300# |
| Approvals | FM explosion proof Class I Groups C, D; Class II Groups E, F, G; Class III Div. 1 (option) |
| Weight | 3 lb (1.4 kg) electronics; sensor 0.5 lb for the first 6 in plus 1 lb per additional 12 in, plus flange |
| Manufacturer warranty | 3 years |
Application limits that decide selection
The catalog is direct about where an ultrasonic switch works. The medium must be a liquid with less than about 5% suspended solids, it must be able to drain from the sensor gap (a liquid too viscous to flow out of the 3/4 in gap will cause false alarms), and fluids of 100 cP or more should not be aerated. It cannot tell two gases apart or a gas from a solid. Within those limits it is a low-cost alternative to float switches for clean hydrocarbons, water, lube oil and coolants, including seal pot service.
Model code and what to confirm
The electronics code runs 2700, housing K1 (integral), power AC or DC, agency 00 or FM, point count 01 or 02 and accessories (BK, GW, HR, PK, RG, RM remote mount, tag plates). The sensor is ordered separately: 371 for single point, 372 for dual, with sensor type U or N, material, insertion length in inches and process connection. Match sensor and electronics approvals to keep the FM listing valid. Confirm the liquid and solids content, viscosity, insertion length, connection, supply voltage, relay rating and whether remote mounting is required.
How the SOR 2700 works
The sensor has a small gap with two crystals. One sends a sound pulse across the gap and the other listens. When liquid fills the gap, the sound arrives strongly. When air fills the gap, it arrives weakly. The electronics read the difference and switch a relay after the set time delay.
Where the SOR 2700 is used
- High and low level alarms in clean liquid tanks
- Pump control
- Process vessels
- Sumps and day tanks
- Overfill protection
Selection checklist for the SOR 2700
- Single or dual point sensor
- Sensor type, U or N
- Sensor material and probe length
- Process connection
- Process temperature and pressure
- Supply, 120/240 VAC or 24 VDC
- Failsafe, high or low
- Remote cable length
Installation, commissioning and maintenance notes for the SOR 2700
Thread or flange the sensor into the vessel so the gap sits at the switch level. Run the cable to the electronics, within 50 ft. Wire the supply and the relay. Select the failsafe mode and set the delay. Press the self-test button and check the relay.
Requesting a quotation for the SOR 2700
Please send the liquid, the temperature, the pressure and the connection. Seven Star LLC serves industrial customers in Oman and the GCC and replies with a quotation based on the information provided.
SOR 2700 input power
The input is 120/240 VAC or 24 VDC.
SOR 2700 output
The single point unit has a 10 A SPDT relay, and the dual point unit has two.
SOR 2700 response time
The response time is 250 ms on and 250 ms off.
SOR 2700 repeatability
The repeatability is 2 mm.
SOR 2700 time delay
The delay is adjustable from 0 to 30 seconds.
SOR 2700 process temperature
The process range is minus 40 to plus 121 degrees C.
SOR 2700 pressure rating
The maximum process pressure is 2,000 psig, 138 bar.
SOR 2700 enclosure
The enclosure is rated NEMA 4X and IP65 with a 3/4 in NPT conduit entry.
SOR 2700 sensor materials
The sensor is 316 stainless steel, with Monel, Carpenter 20 or Hastelloy C on the N type.
Switch records for the SOR 2700
Record the failsafe setting, the delay and the date of the annual visual inspection.
Choosing the right SOR 2700 sensor
Use the dual point sensor where one unit must give two alarm points or run pump-up and pump-down logic.
Documents and quotation
The attached SOR 2700 catalog (Form 2011) holds the specification, ordering trees and sensor data, and the instruction manual (Form 2012) covers installation and setup. Send the sensor type, length, connection and supply for a quotation. See more level instrumentation.
See also: SOR 1510 Side Mounted Float Level Switch.
Datasheets & Documents
Reviews (0)
How would you rate this product? Cancel reply
About brand
SOR is an American maker of pressure, temperature and level instruments, based in Lenexa, Kansas. Roy Dunlap started the business in 1946 as a machine shop, and in 1956 developed a pressure switch with a static O-ring seal, which gave the company its later names, Static O Ring (1965) and SOR (1978). SOR has supplied nuclear-qualified switches since 1982, and in September 2026 DwyerOmega announced it had acquired SOR Controls Group.
Seven Star LLC is an independent supplier in Muscat. We list SOR switches and transmitters for oil and gas and process plants in Oman and the GCC.
SOR company profile
| Founded | 1946, Kansas, USA, by Roy Dunlap |
|---|---|
| Headquarters | Lenexa, Kansas |
| Key invention | Pressure switch with a static O-ring seal, 1956 |
| Name | Static O Ring (1965), SOR (1978) |
| Ownership | DwyerOmega, acquisition announced 24 September 2026 |
| Product families | Pressure, differential pressure and temperature switches, 1500 series level switches, magnetic level indicators, SSi temperature sensors, SENSOR sampling systems, nuclear-qualified switches |
Milestones
- 1946: Roy Dunlap starts the business.
- 1956: The static O-ring pressure switch is developed.
- 1978: The company becomes SOR.
- 1982: SOR begins its nuclear-qualified switch programme.
- 2026: DwyerOmega announces the acquisition of SOR Controls Group.
SOR product series
Switches include the 6L explosion-proof pressure switch, the 1510 side mounted float level switch, the 2700 ultrasonic point level switch and the 1520 top mounted vane flow switch.
Transmitters include the 815DT smart differential pressure transmitter and the 1800DP differential pressure transmitter.
Mechanical switches such as the 6L give a direct trip signal without a power supply, while transmitters send a continuous 4-20 mA signal. Explosion-proof enclosures and stainless wetted parts are standard on many models for oil and gas service.
Where SOR instruments are used
Pressure alarms and trips, high and low level alarms on vessels, flow proving and differential pressure measurement in wellsites, gas plants and refineries.
SOR products we list
Ordering SOR instruments: what we need
Send the model code, range or setpoint, wetted materials, process and electrical connection and the hazardous-area certification.
Facts checked against SOR company history and DwyerOmega's September 2026 announcement, October 2026.
Browse SOR products by category: Pressure Instrumentation, Flow Indicators & Switches, Level Instrumentation.
FAQ
Questions about the SOR 2700 Ultrasonic Point Level Switch
Answers from our engineering team on installation, compatibility and integration.
01How does the SOR 2700 detect level?
Two piezoelectric crystals face each other across a sensor gap; strong received sound means liquid in the gap and weak sound means air, and a relay switches accordingly.
02Does it need calibration?
No. SOR states that no calibration or additional set-up is required; it has a field-selectable failsafe, a 0 to 30 s time delay and a self-test button.
03Which liquids is it suited to?
Clean liquids with less than about 5% suspended solids that can drain from the gap; viscous aerated fluids of 100 cP or more are outside its limits.
04What process limits apply?
-40 to 250 F (-40 to 121 C) and up to 2,000 psig, with flanged connections rated 275 psig (150#) or 720 psig (300#).
05What outputs are available?
A 10 A SPDT relay at 250 VAC or 24 VDC per point as standard, with 2 A hermetically sealed or gold-contact relay accessories; dual-point units offer pump up or down logic.