Brand: E2S
E2S GNExCP7-BG Explosion-Proof Break Glass Manual Call Point
Description
Overview
The E2S GNExCP7-BG is an explosion-proof Ex d break glass manual call point that combines a corrosion-proof GRP enclosure with a 316 stainless steel operating mechanism and IP66/67/68 ingress protection. It is approved to IECEx, ATEX, UL and cUL standards for Zone 1, 2, 21 and 22 and Class I/II Division 2 installations, and an F version can be specified where compliance with UL38 (manual signaling boxes for fire alarm systems) or ULC-S528 is required. The E2S GNExCP7-BG gives personnel a simple, reliable way to raise a fire or emergency alarm by hand in areas where flammable gas or combustible dust may be present.
Seven Star LLC supplies the E2S GNExCP7-BG to fire and gas system integrators, operators and contractors throughout Oman and the GCC. Clients choose us as a trusted supplier because we provide engineering support in Muscat, and we review switch type, terminal arrangement, end-of-line values and addressable module requirements with the fire alarm panel supplier before the call points are ordered.
Working Principle
A break glass call point holds a switch in its normal state by pressure from a frangible glass element. When an operator breaks the glass on the E2S GNExCP7-BG, the internal 316 stainless steel mechanism is released and changes over a sealed IP67 micro switch, which signals the alarm condition to the control panel. A test key (SP70-0040) allows the device to be tested without breaking the element, and spare glasses are supplied in boxes of 50 (SP70-0001), which keeps routine function testing quick and inexpensive.
The switch is available as a single-pole changeover (SPCO/SPDT) or double-pole changeover (DPCO/DPDT). Conventional fire panels normally supervise the circuit using end-of-line and series resistors or Zener diodes, and the E2S GNExCP7-BG can be ordered with these components factory fitted on its dedicated termination board. For addressable systems, versions are offered with interface modules from Honeywell, Ziton, Johnson Controls, Hochiki, Apollo, Consilium, Siemens, Securiton and Simplex, so the call point reports directly on the panel loop.
Engineering Design of the E2S GNExCP7-BG
The enclosure of the E2S GNExCP7-BG is anti-static, UV-stable GRP, rated IP66/67/68 to EN/IEC 60529 and Type 4/4X/3R/13 to UL50E/NEMA 250. Standard colour is red, with blue, green, yellow, black, magenta and striped colour combinations available for non-fire functions such as emergency shutdown or general alarm. An optional 316 stainless steel lift flap protects the glass against accidental operation, and an optional LED indicator can show the alarm status locally. The unit weighs about 2.1 kg.
Three M20 x 1.5 cable entries are provided, two facing down and one on the side, and the back box can be rotated to give two top-facing entries instead. Adaptors convert the entries to 1/2″ NPT, 3/4″ NPT or M25, and two stopping plugs are included. Inside, installers can choose DIN rail terminals (8 x SAK2.5) or the E2S termination board with six 2.5 mm² terminals plus four dedicated EOL and series terminals. An external M5 earth stud is fitted. Electrical limits are 250 V AC at 3.33 A, 48 V DC at 1.0 A and 24 V DC at 3.0 A.
Key Features
The design points that make the E2S GNExCP7-BG suitable for hazardous area fire alarm systems include:
- A corrosion-proof, anti-static and UV-stable GRP enclosure with IP66/67/68 and Type 4/4X/3R/13 ratings.
- A 316 (A4) stainless steel mechanism that keeps working in humid, saline and chemically aggressive air.
- Single or double changeover switching in a sealed IP67 switch for conventional or interlocked circuits.
- A choice of DIN rail terminals or a termination board with dedicated EOL and series device positions.
- Factory-fitted resistors or Zener diodes, plus duplicated and parallel wiring options on double switch versions.
- Addressable module versions for the loop protocols of the main fire alarm panel manufacturers.
- An optional stainless steel lift flap, an optional LED indicator and a wide selection of enclosure colours.
- SIL 2 compliance to IEC 61508 (2010) and an MTBF of 479.6 years to MIL 217.
Industrial Applications
The E2S GNExCP7-BG is installed along escape routes, at exits from process modules, near pump and compressor skids, at tank farm bund access points and on loading racks, jetties and offshore decks, anywhere personnel need to initiate a fire alarm manually within a classified area. Colour-coded versions are often used for related functions, for example yellow for an emergency shutdown push and red for fire, so that operators recognise the purpose of each E2S GNExCP7-BG at a glance. The DNV certificate supports its use on vessels and offshore structures.
In Oman, typical users include oil and gas production stations, gas plants, refineries and petrochemical complexes in Sohar, Duqm and Salalah, as well as power, water and port facilities. Seven Star LLC helps engineering teams in Muscat and throughout the GCC confirm compatibility between the call point and the fire alarm panel, define the correct EOL values and plan spares such as replacement glasses and test keys for the E2S GNExCP7-BG.
Technical Specifications
The following data for the E2S GNExCP7-BG is taken from the E2S product datasheet (part 1-24-150):
| Parameter | Specification |
|---|---|
| Model | E2S GNExCP7-BG Break Glass Manual Call Point |
| Operation | Break glass, 316 stainless steel mechanism |
| Switch | Sealed IP67; SPCO/SPDT or DPCO/DPDT |
| Electrical rating | 250 V AC max, 3.33 A; 48 V DC max, 1.0 A; 24 V DC max, 3.0 A |
| Terminals | DIN rail 8 x SAK2.5, or termination board with 6 x 2.5 mm² plus 4 x EOL/series terminals |
| IECEx / ATEX coding | II 2G Ex db IIC T5 Gb (Ta −55 to +70 °C); Ex db IIC T6 Gb (Ta −55 to +65 °C); II 2D Ex tb IIIC T90 °C Db |
| NEC / CEC | Class I Div 2 Groups A, B, C, D T5; Class I Zone 1 AEx db IIC T5 Gb; Zone 21 AEx tb IIIC |
| Certificates | UL/cUL E482536 and E513632, IECEx ULD 19.0007X, DEMKO 19 ATEX 2101X, UL21UKEX2134X, INMETRO IEx 23.0091X, PESO CCOE P632054, DNV TAA000034V |
| Functional safety | SIL 2 to IEC 61508 (2010) |
| Ingress protection | IP66/67/68 (EN/IEC 60529); Type 4/4X/3R/13 (UL50E/NEMA 250) |
| Enclosure | GRP, anti-static and UV stable; red as standard, other solid and striped colours available |
| Cable entries | 2 x M20 x 1.5 down and 1 x M20 x 1.5 side; adaptable to 1/2″ NPT, 3/4″ NPT, M25 |
| Options | 316 stainless steel lift flap, LED indicator, addressable modules, duty label and equipment tag |
| Temperature | −55 to +60 / +70 °C depending on coding |
| Humidity | 95% RH at 20 °C |
| MTBF | 479.6 years / 4,201,680 hours (MIL 217) |
| Weight | 2.1 kg (4.63 lb) |
Ordering and Configuration
An order code is assembled from GNExCP7BG, the switch type (S or D), terminals (D for DIN rail, P for termination board or X for an addressable module), lift flap (N or L), cable entry option, stopping plug material, duty label and tag option, product version (A for UL, cUL, IECEx, ATEX, INMETRO and PESO, F for UL38 and ULC-S528 fire use, or a letter for the chosen addressable module), wiring option, enclosure colour, LED option and optional EOL and series modules such as E470R or S5V1Z. Note that the F version requires a red enclosure and a FIRE/FEU duty label and is not offered with the LED indicator. Accessories include the SP65-0001-A4 pole mount kit and SP65-0002-A4 sunshade for the E2S GNExCP7-BG.
Related Products
Pair manual call points with automatic detection such as the General Monitors FL5000 flame detector or the C-TEC CP416 CAST-PRO smoke detector, and signal the alarm with the E2S BExCS110-05 horn and beacon.
Other GRP warning devices in this series are the E2S GNExS1F alarm horn sounder and E2S GNExB2X10 xenon strobe beacon.
How to Order
For a formal quotation, current regional warehouse availability or the E2S datasheet for the E2S GNExCP7-BG, get in touch with the instrumentation division at Seven Star LLC. We supply E2S manual call points to projects in Oman and the GCC, and our engineering support team in Muscat will help you finalise the E2S GNExCP7-BG order code for your fire alarm panel and hazardous area.
Datasheets & Documents
- Datasheet E2S GNExCP7-BG Break Glass Manual Call Point Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
E2S builds one thing: audible and visual warning signals. The company, founded in 1992 and based in London, United Kingdom, makes sounders, beacons, combined units, manual call points and loudspeakers for industrial, marine and hazardous-area sites. Seven Star LLC sources and supplies E2S explosion-protected alarm sounders and xenon beacons for fire and gas systems in Oman, including the GNEx and BEx models shown on this page.
E2S hazardous-area families
E2S groups its Ex signals by family. GNEx and BEx are both for Zone 1 and Zone 21, and the STEx family covers the same zones. D1x and D2x are the lines for Class/Division sites, and the IS family is intrinsically safe for Zone 0. The listed items show the pattern: GNExS1F is an alarm horn sounder, GNExB2X10 a xenon strobe beacon and BExCS110-05 a combined sounder and beacon.
Ordering E2S signals: what we need
An E2S part number is completed by suffixes for supply voltage, lens color, cable entries and options, so send the whole code from the label. For a new requirement give the area classification, gas group and temperature class, voltage, lens color, entry thread, and the approval your project needs. Many GCC projects name IECEx or ATEX in the specification.
Browse E2S products by category: Fire & Gas Detector.
Related products
Frequently Asked Questions
It is approved to IECEx, ATEX, UL and cUL for Zone 1, 2, 21 and 22 and Class I/II Division 2 locations, with coding such as II 2G Ex db IIC T5 Gb. The GRP enclosure is rated IP66/67/68 and Type 4/4X/3R/13 for outdoor and offshore use.
Yes. Versions are available with addressable modules from Honeywell, Ziton, Johnson Controls, Hochiki, Apollo, Consilium, Siemens, Securiton and Simplex. Note that versions fitted with addressable modules do not carry UL, cUL or ULC approval.
The E2S termination board has dedicated EOL and series terminals, and resistors or Zener diodes can be factory fitted using codes such as E470R or S5V1Z. DIN rail terminals are offered as an alternative for simpler wiring.
A dedicated test key, part SP70-0040, operates the mechanism for routine testing without destroying the glass element. Replacement glasses are supplied in boxes of 50 under part SP70-0001.
Yes. Seven Star LLC supplies E2S manual call points to projects across Oman and the GCC as a trusted supplier, with engineering support in Muscat. We can confirm switch type, terminals, colour and module options against your fire alarm panel.

Reviews