WIKA A2G-40 Differential Pressure Switch for HVAC Air
Description
WIKA A2G-40 differential pressure switch for ventilation and air-conditioning
The WIKA A2G-40 is a differential pressure switch for dry, clean, non-aggressive gases, usually air. Its job is to monitor filters, ventilators and blowers in ventilation ducts, air-conditioning units and clean room installations, and to monitor overpressure in clean rooms and laboratories. It is offered in six pressure range increments from 20 … 200 Pa to 500 … 4,500 Pa, in a plastic case with side-mounted hose nozzles and an M16 cable gland. Seven Star LLC supplies the A2G-40 in Oman and the GCC as an independent supplier in Muscat, and this page explains the ranges and electrical limits so that the RFQ can name the right range and application.
How the A2G-40 switches
Two hoses connect the switch to the two pressure points, for example the upstream and downstream side of a filter. A silicone diaphragm inside the case moves with the difference between the two pressures and operates a contact when the difference reaches the set point. The set point is adjusted within the chosen pressure range, and the contact returns when the difference falls by the switch differential (hysteresis) given in the data sheet. The device is in the Δp function: it monitors a pressure difference rather than a single pressure.
As a filter monitor the switch gives a signal when the pressure drop across a dirty filter exceeds the set value, and as a fan monitor it signals the loss of pressure rise when a belt breaks or a motor trips. In clean rooms it can indicate loss of overpressure. Because there are six ranges, an installation can pick the increment that suits the clean filter drop and the alarm drop.
Technical specifications of the A2G-40
| Parameter | Specification |
|---|---|
| Manufacturer / part number | WIKA / A2G-40 |
| Function | Differential pressure switch (Δp) for dry, clean, non-aggressive gases |
| Pressure ranges | 20 … 200 Pa; 30 … 300 Pa; 30 … 500 Pa; 40 … 600 Pa; 100 … 1,500 Pa; 500 … 4,500 Pa |
| Switch differential | 20, 25, 25, 35, 80 and 250 Pa respectively |
| Switch point accuracy | Lowest limit ±8 / ±8 / ±8 / ±8 / ±20 / ±100 Pa; highest limit ±15 % |
| Units | Pa, kPa, inWC, mmWC, mbar |
| Maximum operating pressure | Test pressure 25 kPa; burst pressure 50 kPa |
| Process connection | Side-mount nozzle for hoses 4 … 6 mm inner diameter |
| Electrical connection | Cable gland M16; screw terminals max. 1.5 mm² |
| Mounting | Wall mounting |
| Materials | Case ABS; window polycarbonate; diaphragm silicone; plastic seals |
| Temperature | Medium -20 … +60 °C; ambient -20 … +85 °C |
| Humidity | 0 … 95 % relative, non-condensing |
| Ingress protection | IP54 |
| Weight | 150 g |
Switching power of the A2G-40
The contact rating depends on the range. For the lowest range (20 … 200 Pa) the data sheet gives 0.1 A resistive at AC 125 V, AC 250 V and DC 30 V. For all other ranges the resistive rating is 3 A at AC 125 V, AC 250 V and DC 30 V, and 2 A on inductive loads (cos φ about 0.6 to 0.7). At DC 125 V the resistive rating is 0.4 A and the inductive rating 0.05 A on those ranges. The lowest range therefore suits signalling to a PLC input or a relay coil, while the others can drive small contactors or alarm horns directly. Always confirm the load type, because a rating given for a resistive load does not apply to inductive devices.
Where the A2G-40 fits and related WIKA models
If a continuous signal is needed instead of an alarm contact, the A2G-55 Eco differential pressure transmitter measures the same low air pressures with a 0 … 10 V or 4 … 20 mA output. Both models use hoses of similar size and the same wall-mounting style, so a filter monitoring design can use the transmitter for trending and the switch for a hard-wired alarm. Where liquids or higher pressures are involved, WIKA gauges such as the 732.51 differential pressure gauge or switch-type instruments in other families apply.
Selection and ordering checklist for the A2G-40
- Range increment, chosen so that the alarm value lies inside it and above the lowest limit with margin.
- Contact load: resistive or inductive, voltage and current, especially for the 20 … 200 Pa range.
- Hose size 4 … 6 mm and the length to the duct.
- Units shown on the scale: Pa, kPa, inWC, mmWC or mbar.
- Medium: air or clean, dry, non-aggressive gas only.
- Ambient and medium temperature within the limits.
- Approvals such as EAC, if required.
Installation and commissioning of the A2G-40
Mount on a wall (the data sheet lists wall mounting) and connect the plus hose to the higher-pressure point and the minus hose to the lower-pressure point. Keep hoses short and free of liquid pockets, and take pressure from duct connectors facing away from the flow. Set the switch point as described in the operating instructions, then verify it with a hand pump and manometer, since the data sheet allows an upper limit tolerance of ±15 %. Fit the cable through the M16 gland and close the cover to maintain the IP54 rating. Avoid mounting the switch where condensate can run into it; the housing is not for wet spaces.
Typical applications in Oman and the GCC
Gulf air conditioning plants run with high dust and sand loading, so the pressure drop across filters can rise quickly. The A2G-40 gives an alarm for filter replacement in air handling units of hospitals, hotels, malls, offices and industrial buildings, and it signals a fan failure in ducts and cooling-tower air systems. It is also used in clean rooms and laboratories to monitor overpressure, within the limit of medium temperature of -20 to +60 °C.
A2G-40 ranges compared
| Range (Pa) | Switch differential (Pa) | Lowest-limit accuracy | Contact rating |
|---|---|---|---|
| 20 … 200 | 20 | ±8 Pa | 0.1 A resistive |
| 30 … 300 | 25 | ±8 Pa | 3 A resistive |
| 30 … 500 | 25 | ±8 Pa | 3 A resistive |
| 40 … 600 | 35 | ±8 Pa | 3 A resistive |
| 100 … 1,500 | 80 | ±20 Pa | 3 A resistive |
| 500 … 4,500 | 250 | ±100 Pa | 3 A resistive |
Information to send with an RFQ
- A2G-40 with range in Pa
- Contact load and voltage
- Scale unit
- Quantity and delivery site
Documents and quotation
The WIKA data sheet for the A2G-40 is attached on this page.
Send the range, unit and quantity and Seven Star LLC will confirm availability and a quotation.
Other Models in the Wika A2g Range
Seven Star LLC supplies models from the Wika A2g range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| WIKA A2G-55 Eco Differential Pressure Transmitter, 250-5000 Pa | Pressure Instrumentation | View details |
| WIKA A2G-40 Differential Pressure Switch for HVAC Air | Pressure Instrumentation | You are viewing this model |
Datasheets & Documents
- Datasheet WIKA A2G-40 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
WIKA is the German manufacturer of pressure, temperature, level and flow instruments, best known for its pressure gauges. Alexander Wiegand and Philipp Kachel founded it on 2 January 1946 in Klingenberg am Main, Bavaria. The name comes from the first two letters of their surnames. WIKA is still run by the Wiegand family and is headquartered in Klingenberg.
Seven Star LLC is an independent supplier in Muscat. We list WIKA pressure gauges, diaphragm seals, transmitters, switches, thermometers and thermowells, and supply them to plants, contractors and panel builders in Oman and the GCC by model and order code.
WIKA company profile
| Established | 2 January 1946, Klingenberg am Main, Germany, by Alexander Wiegand and Philipp Kachel |
|---|---|
| First products | Mechanical pressure and temperature gauges |
| Ownership | Family-owned; managed by Alexander Wiegand, grandson of the founder, since 1996 |
| Product families | Pressure gauges, diaphragm seals, pressure transmitters and switches, thermometers, RTDs, thermocouples, thermowells, calibration equipment, level and flow instruments |
Milestones
- 1946: Alexander Wiegand and Philipp Kachel found the company in Klingenberg am Main on 2 January; pressure gauge production starts at the end of the year. The name WIKA comes from the first letters of their surnames.
- 1951: Konrad Wiegand, the founder's son, takes over management.
- 1967: Ursula Wiegand leads the company after her husband's death.
- 1986: The company is reunited with the Kachel thermometer factory, which Philipp Kachel had set up after leaving in 1956.
- 1994: Certification to DIN ISO 9001.
- 1996: Alexander Wiegand, the founder's grandson, becomes head of the company.
WIKA products we list
| Family | Models | Typical use |
|---|---|---|
| Bourdon tube pressure gauges | 111.10, 111.12, 212.20, 213.53, 232.50, 233.50, 232.30/233.30 safety pattern | HVAC and utilities (111 series) to process plants (23x series in stainless steel) |
| Diaphragm and differential pressure gauges | 432.50, 732.51, 700.01, DPGT43 | Low pressures, viscous or dirty media, and filter differential pressure |
| Diaphragm seals | 990.10, 990.27 | Separating the gauge from corrosive, hot or clogging media |
| Transmitters, switches and test gauges | A-10, UPT-20, PSM01, CPG1500 | 4-20 mA pressure signals, switching, and precision calibration checks |
| Thermometers | TG54, Model 55, A52, 73 gas-actuated | Local temperature indication on pipes, vessels and HVAC |
| Temperature sensors and thermowells | TR10, TR12-B, TR33, TC10-B, TW10 flanged, TW15 threaded | RTD and thermocouple measurement in process lines |
The WIKA model number tells you the build. In 232.50, the first digit 2 means stainless steel wetted parts, the second digit 3 means a liquid-fillable case, and ".50" is the case style. The 111 series uses copper alloy wetted parts and suits water and air. Where the medium is corrosive, very hot or would block the gauge, a diaphragm seal such as the 990.27 keeps it away from the Bourdon tube. For temperature, a thermowell like the TW10 lets you remove the sensor without opening the process.
Where WIKA instruments are used
In Oman and the GCC, WIKA gauges, transmitters and thermometers are used in oil and gas, refining and petrochemical plants, power and desalination, water networks, district cooling and HVAC, and on skids and machines from OEMs.
Ordering WIKA instruments: what we need
Send the model, dial size (for example 63, 100 or 160 mm), range and unit, connection size and position (lower or back mount), accuracy class and whether liquid filling is needed. For diaphragm seals and thermowells, add the process connection, materials and insertion length.
Facts checked against WIKA company history, October 2026.
Browse WIKA products by category: Pressure Instrumentation, Temperature Instrumentation.
FAQ
Questions about the WIKA A2G-40 Differential Pressure Switch for HVAC
Answers from our engineering team on installation, compatibility and integration.
01What is the WIKA A2G-40?
A differential pressure switch for dry, clean, non-aggressive gases, mostly air, used to monitor filters, ventilators and blowers in air-conditioning and clean room applications.
02What ranges are available?
Six ranges: 20 to 200, 30 to 300, 30 to 500, 40 to 600, 100 to 1,500 and 500 to 4,500 Pa.
03What are the contact ratings?
For the lowest range 0.1 A resistive. For all other ranges 3 A resistive and 2 A inductive at AC 125 or 250 V and DC 30 V.
04What temperatures does it tolerate?
Medium -20 to +60 degrees C and ambient -20 to +85 degrees C, with humidity to 95 percent non-condensing.
05What ingress protection does it have?
IP54, with an ABS case, polycarbonate window and silicone diaphragm.