Schneider Electric XB4BS8444 E-Stop 40 mm Turn Release 2 NC

Description

XB4BS8444 emergency stop with 2 NC and turn to release reset

The XB4BS8444 is an emergency stop push-button from the Harmony XB4 metal range, with a red unmarked mushroom head of 40 mm diameter on a 22 mm mounting. It uses trigger action with mechanical latching, resets by a turn to release action, and carries 2 NC contacts. The datasheet lists it as both an emergency stop and an emergency switching-off push-button. Seven Star LLC supplies the XB4BS8444 in Oman and the GCC as an independent supplier based in Muscat.

This page uses the datasheet to explain what the 2 NC arrangement means for the wiring, how the reset action differs from its siblings and which standards are named on the document.

Latching and turn to release reset of the XB4BS8444

This unit latches down when struck and is reset by turning the head. Turn-to-release is the long-established style: the head cannot be pulled back, it has to be rotated deliberately, which discourages casual resetting. Operating travel is 1.5 mm (NC changing electrical state) and 4.3 mm (total travel). Mechanical life is 300000 cycles.

XB4BS8444 technical specifications

Parameter Specification
Manufacturer / part number Schneider Electric / XB4BS8444
Range Harmony XB4, 22 mm metal
Product type Emergency stop push-button; Emergency switching off push-button
Operator trigger action and mechanical latching
Operator profile Red mushroom Ø 40 mm, unmarked
Contacts 2 NC
Terminal marking (21-22)NC
Reset Turn to release
Operating travel 1.5 mm (NC changing electrical state); 4.3 mm (total travel)
Positive opening With (IEC 60947-5-1, appendix K)
Mechanical life 300000 cycles
Insulation voltage Ui 600 V (pollution degree 3)
Impulse withstand Uimp 6 kV
Short-circuit protection 10 A cartridge fuse type gG
Terminals Screw clamp terminals, ≤ 2 × 1.5 mm² with cable end; Screw clamp terminals, ≥ 1 × 0.22 mm² without cable end
Dimensions 47 mm x 40 mm x 82 mm (H x W x D)
Net weight 0.13 kg
Ambient temperature, operation -40–70 °C
Degree of protection IP66, IP67, IP69, IP69K
Impact protection IK06
Certifications listed CSA, LROS, BV, UL listed, DNV
Warranty 18 months

XB4BS8444 compared with the other XB4 emergency stops

Six emergency stops of the same 40 mm mushroom family are compared here: they differ in contact configuration and reset action.

Part number Contacts Reset Weight Force Impact
XB4BS8442 1 NC Turn to release 0.118 kg not listed IK06
XB4BS8444 (this page) 2 NC Turn to release 0.13 kg not listed IK06
XB4BS84441 2 NC + 1 NO Turn to release n/a not listed IK06
XB4BS8445 1 NO + 1 NC Turn to release 0.13 kg 44 N IK06
XB4BT842 1 NC Push-pull 0.125 kg not listed IK06
XB4BT845 1 NO + 1 NC Push-pull 0.136 kg 50 N IK03

Contact configuration of the XB4BS8444

This unit carries two NC contacts, so the stop command can be wired into two independent circuits when the machine safety concept asks for a dual-channel arrangement. The NC contacts are rated with positive opening per IEC 60947-5-1 appendix K. Terminal marking given for the first block is (21-22)NC. The safety function and any category or performance level belong to the machine’s risk assessment; the datasheet does not claim a safety category.

What this unit can switch is set by its contact block: slow-break action, silver alloy (Ag/Ni) contacts, a 10 A conventional thermal current, 600 V insulation voltage at pollution degree 3 and 6 kV impulse withstand. The datasheet names a 10 A gG fuse as short-circuit protection. The utilisation-category ratings below are what a designer needs when the contacts drive coils or logic inputs.

  • 3 A at 240 V, AC-15, A600
  • 6 A at 120 V, AC-15, A600
  • 0.1 A at 600 V, DC-13, Q600
  • 0.27 A at 250 V, DC-13, Q600
  • 0.55 A at 125 V, DC-13, Q600
  • 1.2 A at 600 V, AC-15, A600

Standards and environment of the XB4BS8444

The degree of protection is IP66, IP67, IP69, IP69K. The impact rating on the datasheet is IK06. Vibration resistance is 5 gn (f= 2–500 Hz). Shock resistance on the datasheet is 30 gn (duration = 18 ms) for half sine wave acceleration and 50 gn (duration = 11 ms) for half sine wave acceleration. The permitted operating ambient temperature is -40–70 °C. The standards named on the datasheet are: JIS C8201-5-1, IEC 60364-5-53, UL 508, IEC 60947-5-1, CSA C22.2 No 14, ISO 13850, IEC 60947-5-5, IEC 60947-1, IEC 60204-1, IEC 60947-5-4, JIS C8201-1.

Selection and installation of the XB4BS8444

  • Contacts: 2 NC.
  • Reset: turn to release.
  • Head: red mushroom, 40 mm, unmarked.
  • Panel hole: 22.5 mm; overall depth 82 mm.
  • Check the stop function against the machine safety concept before ordering.

Cut the panel opening to 22.5 mm and secure this unit with the fixing torque the datasheet specifies (0.8–1.2 N.m). Conductors go into screw clamps: ≤ 2 × 1.5 mm² with cable end and ≥ 1 × 0.22 mm² without cable end. Accepted screwdrivers are Philips and pozidriv no 1 and flat 4 mm or 5.5 mm. Mount it where it can be reached quickly and keep the area around the head free.

Before handover, operate the head, confirm the NC contacts open and stay open while latched, and test that the machine stops. Test again after any change to the control circuit. Keep the test result with the panel documentation and repeat the check after any wiring change.

Where the XB4BS8444 is used in Oman and the GCC

Emergency stops are fitted on pump skids, compressors, conveyors, cranes, packaging lines and process control stations. The IP66 to IP69K sealing in the datasheet suits washdown areas, and the metal body copes with sun, heat and fine sand in outdoor stations. Where the equipment is exported, check that the ordering reference and approvals match the destination rules.

The second NC contact of this unit doubles the stop path. In practice that means the two contacts can feed two relays or two inputs of a safety relay, so that a single wiring fault does not silently remove the stop function. Whether that is required depends on the safety concept of the machine, not on the button itself.

The value of an emergency stop is its reliability when it is needed, so test it on a schedule and not only at commissioning. Operate the head, confirm the machine stops, reset it, and record the test with the date and the name of the person doing it.

Information to send with an RFQ for the XB4BS8444

Please give us the exact reference XB4BS8444, how many pieces you need and where they are going in Oman or the GCC. State the contact configuration (NC, NO + NC, 2 NC, 2 NC + 1 NO), the reset type and the panel hole size. For a replacement job, a clear photo of the old device and its marking removes any doubt about the match.

Documents and quotation

A copy of the Schneider Electric datasheet of this unit is attached to this page for download, and every value quoted here comes from that document.

For a quotation, use the RFQ form and quote XB4BS8444 together with the quantity and the destination. Seven Star LLC will come back with stock status and delivery time.

Other Models in the Se Harmony Xb4 Es Range

Seven Star LLC supplies models from the Se Harmony Xb4 Es range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Schneider Electric XB4BS8442 E-Stop 40 mm Turn Release 1 NCAutomation AccessoriesView details
Schneider Electric XB4BS8444 E-Stop 40 mm Turn Release 2 NCAutomation AccessoriesYou are viewing this model
Schneider Electric XB4BS84441 E-Stop 40 mm Turn Release 2NC+1NOAutomation AccessoriesView details
Schneider Electric XB4BS8445 E-Stop 40 mm Turn Release 1NO+1NCAutomation AccessoriesView details
Schneider Electric XB4BT842 Emergency Stop 40 mm Push-Pull 1 NCAutomation AccessoriesView details
Schneider Electric XB4BT845 E-Stop 40 mm Push-Pull 1NO+1NCAutomation AccessoriesView details
Datasheets & Documents
  • PDF Datasheet Schneider Electric XB4BS8444 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric XB4BS8444 E-Stop 40 mm Turn

Answers from our engineering team on installation, compatibility and integration.

01What contact arrangement does the XB4BS8444 have?
The datasheet lists 2 NC, marked (21-22)NC. The contacts are slow-break with silver alloy (Ag/Ni) material and a 10 A thermal current.
02What electrical ratings does the XB4BS8444 contact block have?
The datasheet gives 3 A at 240 V AC-15 and 6 A at 120 V AC-15, with a rated insulation voltage of 600 V and a 10 A gG fuse for short-circuit protection. Check these against your control circuit.
03How well is the XB4BS8444 sealed?
The datasheet gives IP66, IP67, IP69, IP69K for the degree of protection and an operating range of -40…70 °C. Confirm the rating you need against the exact ordering reference.
04How is the XB4BS8444 reset?
The datasheet gives the reset as turn to release. The head is a red mushroom of 40 mm, with mechanical latching.
05What panel hole and wiring does the XB4BS8444 need?
The mounting diameter is 22.5 mm, and terminals take screw clamp conductors up to 2 x 1.5 mm² with cable ends. The tightening torque is 0.8…1.2 N.m.