Brand: Schneider Electric
Schneider Electric METSEPM1120HCL10RS EasyLogic PM1120H Meter
Description
METSEPM1120HCL10RS: EasyLogic PM1120H meter with THD and RS485
The METSEPM1120HCL10RS is a Schneider Electric EasyLogic PM1120H energy meter. The datasheet lists it as an energy meter in the EasyLogic PM11XXH RS family, for energy monitoring, with total harmonic distortion measurement and an RS485 Modbus port. The catalogue title adds class 1.0, which matches the datasheet statement of class 1 for active energy.
The PM1120H is a 96 × 96 mm flush-mounted device with a red 8-segment LED display, three display fields of four characters and a 12-digit counter. It is meant for panels where a power and energy readout, harmonic distortion and a serial link are needed without a full power-quality analyser.
METSEPM1120HCL10RS technical specifications
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Schneider Electric / METSEPM1120HCL10RS |
| Range / product name | EasyLogic / EasyLogic PM11XXH RS (PM1120H) |
| Product type | Energy meter |
| Application | Energy monitoring |
| Power quality analysis | Total harmonic distortion |
| Supply voltage [Us] | 48–277 V AC 45–65 Hz; 48–277 V DC |
| Rated current [In] | 1 A; 5 A |
| Network types | 1P+N; 2P; 2P+N; 3P; 3P+N |
| Maximum power consumption | 2 W at 240 V |
| Measurement voltage | 46–277 V AC phase-neutral; 80–480 V AC between phases; up to 999000 V AC with external VT |
| Measurement current | 5–6000 mA input (0.005–10 A) |
| Frequency range | 45–65 Hz |
| Sampling rate | 32 samples/cycle |
| Accuracy class | Class 1 active energy (IEC 62053-21); class 1 reactive energy (IEC 62053-24) |
| Display | 8-segment red LED, 3 fields of 4 characters, 12 digits 14.2 mm high |
| Communication | Modbus, RS485 screw connector, 4800 to 38400 bps, 2-wire, 2500 V insulation |
| Signalling | Green LED activity; red LED pulse output |
| Data recording | Energy consumption logs |
| Mounting | Flush-mounted |
| Dimensions H × W × D | @96 × 96 × 13 mm outside, 49 mm in panel |
| Net weight | 300 g |
| Material / flame retardance | Polycarbonate; V-0 to UL 94 |
| IP protection | IP51 front,; IP30 body |
| Operating / storage temperature | -10 to 60 °C / -20 to 70 °C |
| Relative humidity | 5–95 % at 50 °C |
| Pollution degree / altitude | 2 / up to 2000 m |
| Measurement / installation category | Category III 480 V / III |
| Service life | 7 year(s) |
| Certifications | CE conforming to IEC 61010-1, CULus conforming to UL 61010-1, CULus conforming to CSA C22.2 No 61010-1, C-Tick |
Wiring, inputs and supply of the METSEPM1120HCL10RS
Inputs are four voltage inputs with 5 megohm impedance and six current inputs for 0.005 to 10 A signals at 0.3 megohm, so measuring transformers rated 1 A or 5 A secondary are used for current. Above 480 V between phases, external voltage transformers are needed; the datasheet allows measurement up to 999000 V AC with an external VT. The supply can be 48 to 277 V AC or 48 to 277 V DC, a wide range that allows the meter to be powered from many auxiliary supplies.
Terminals are screw clamp: current circuit at the bottom for 2.08–3.31 mm² cables, voltage and control circuit at the top for 0.82–3.31 mm², and communication at the bottom for 0.33–3.31 mm². Tightening torque is 0.9–1 N.m for power terminals and 0.5–0.6 N.m for communication. Setting changes are protected by an access code.
Panel cut-out and installation of the METSEPM1120HCL10RS
The front is 96 × 96 mm, the thickness outside the panel is 13 mm and the depth behind the panel is 49 mm,. The housing is polycarbonate with V-0 flame retardance, protection is IP51 at the front and IP30 for the body, and the weight is 300 g.
The meter is for indoor installation, operates from -10 to 60 °C and tolerates 5–95 % humidity at 50 °C. It is double insulated (class II) and sits in overvoltage category III. A panel exposed to dust needs the door gasket to be kept in good order, because only the front face has the higher IP rating.
RS485 Modbus communication on the METSEPM1120HCL10RS
The serial port is RS485, 2-wire, with 2500 V insulation and Modbus at 4800, 9600, 19200 or 38400 bps, with even, odd or no parity. The datasheet lists the data available over the link: all counters, instantaneous and demand values, readings of measurements, the last cleared log and revolution speed.
A red LED can also emit pulses at 1 to 9999000 pulses per kWh, kVAh or kVARh, which allows a pulse input on a PLC or a data logger as a second, simple way to read energy. A green LED shows activity. Because the PM1120H has no digital inputs or outputs of its own listed, it is intended for monitoring, not control.
METSEPM1120HCL10RS against the PM2130 meter
Both meters are listed in this group as EasyLogic panel meters of the same 96 mm size. The table highlights where they differ, which is the main selection question.
| Feature | METSEPM1120HCL10RS | METSEPM2130 |
|---|---|---|
| Accuracy class active energy | Class 1 | Class 0.5S |
| Display | 8-segment red LED | 7-segment red LED |
| Sampling | 32 samples/cycle | 64 samples/cycle |
| Harmonics | THD of I and U | THD to the 31st harmonic |
| Supply | 48–277 V AC/DC | 80–277 V AC; 100–277 V DC |
| Real-time clock | Not listed | Yes |
| Storage temperature | -20 to 70 °C | -25 to 70 °C |
| Weight | 300 g | 300 g |
Measurements and accuracy of the METSEPM1120HCL10RS
The meter measures phase currents and phase voltages, frequency, power factor with sign over four quadrants, phase angle, active, reactive and apparent power with demand and peak demand, active, reactive and apparent energy, current and voltage unbalance, a calculated neutral current and total harmonic distortion of current and voltage. It also reports rotation speed (RPM) and counts on-load hours, on hours and power interruptions.
| Quantity | Accuracy |
|---|---|
| Current | ±0.5 % |
| Voltage | ±0.5 % |
| Frequency | ±0.05 % |
| Power factor | ±0.01 |
| Active power | ±1 % |
| Reactive power | ±2 % |
| Apparent power | ±1 % |
| Active energy | ±1 % |
| Reactive energy | ±2 % |
| Apparent energy | ±1 % |
| Harmonic distortion (I THD, U THD) | ±5 % |
These accuracy figures are the datasheet’s, and the energy classes are tested to IEC 62053-21 and 62053-24. Class 1 is suitable for monitoring and internal cost allocation; it is not the revenue-grade class of the PM2130 sibling, which reaches class 0.5S for active energy.
Selection checklist and RFQ details for the METSEPM1120HCL10RS
- Network type to be measured and nominal voltage, including any external VT ratio
- Current transformer secondary: 1 A or 5 A
- Auxiliary supply available in the panel, within 48–277 V AC or DC
- Whether class 1 accuracy is enough or a class 0.5S meter is required
- RS485 trunk and Modbus master that will read the meter
- Panel cut-out available for a 96 × 96 mm meter
Please include these in an enquiry:
- Part number METSEPM1120HCL10RS and quantity
- Application and system voltage
- Delivery location and required date
Using the METSEPM1120HCL10RS in Oman and the GCC
Panel meters of this kind are used on sub-distribution boards, air-conditioning plant, pump stations and factory feeders in Oman and the GCC to see how much energy each section consumes. The harmonic reading is a useful early warning for sites with many variable-speed drives and rectifiers, such as water pumping and desalination plants.
The operating range tops out at 60 °C, so a meter in a door of a hot outdoor kiosk should be checked against the temperature measured inside. An RS485 trunk to a gateway is the cheapest way to bring many meters into one monitoring system.
Documents and quotation
The Schneider Electric manufacturer datasheet for the METSEPM1120HCL10RS is attached on this page as a PDF. It is the reference for every rating quoted above, and it is worth checking the revision against your project documents before an order is placed. The accuracy table, wiring data and environmental limits are all in it.
Seven Star LLC is an independent supplier in Muscat that serves buyers in Oman and the GCC. Send the part number METSEPM1120HCL10RS, the quantity and the delivery site, and we will reply with a quotation and the availability we can confirm.
See also: Schneider Electric BLRCS050A060B44 5 kvar 440 V PFC Capacitor; Schneider Electric METSEPM2130 EasyLogic PM2130 Power Meter.
Datasheets & Documents
- Datasheet Schneider Electric METSEPM1120HCL10RS Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.
Schneider Electric company profile
| Origins | 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry |
|---|---|
| Headquarters | Rueil-Malmaison (Paris region), France |
| Ownership | Public company listed on Euronext Paris |
| Key acquisitions | Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software |
| Brand names still in use | Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform |
| Product families | Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software |
Milestones
- 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
- 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
- 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
- 1997: Modicon, the company behind the first programmable logic controller, joins the group.
- 1999: The group takes the name Schneider Electric.
- 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.
Choosing Schneider Electric breakers and motor control
Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.
Where Schneider Electric products are used
In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.
APC by Schneider Electric: UPS and critical power
Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.
Schneider Electric products we list
| Family | Examples |
|---|---|
| Circuit breakers | Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW |
| Motor control | TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480 |
| Drives | Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo |
| PLCs, HMIs and relays | Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655 |
| Protection, metering and power | Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS |
Ordering Schneider Electric products: what we need
Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.
Facts checked against Schneider Electric's published company history, October 2026.
Browse Schneider Electric products by category: Circuit Breaker, Electrical & Power Modules, AC Drives, PLC & I/O Cards, Metering Systems, UPS and Batteries.
FAQ
Questions about the Schneider Electric METSEPM1120HCL10RS EasyLogic
Answers from our engineering team on installation, compatibility and integration.
01What does the METSEPM1120HCL10RS measure?
Current, voltage, frequency, power factor, phase angle, active, reactive and apparent power, demand and peak demand, energy, unbalance, total harmonic distortion of current and voltage, and rotation speed.
02What accuracy class does the METSEPM1120HCL10RS have?
Class 1 for active energy (IEC 62053-21) and class 1 for reactive energy (IEC 62053-24), with the full accuracy list in the table above.
03Does the METSEPM1120HCL10RS have communication?
Yes, an RS485 port with Modbus at 4800 to 38400 bps, 2-wire, 2500 V insulation.
04What supply does the METSEPM1120HCL10RS need?
48 to 277 V AC at 45 to 65 Hz or 48 to 277 V DC, with a maximum consumption of 2 W at 240 V.
05What panel size does the METSEPM1120HCL10RS fit?
It is a 96 x 96 mm flush-mounted meter, 13 mm outside the panel and 49 mm behind it, weighing 300 g.