Schneider Electric GV2L04 TeSys GV2 0.63 A Motor Breaker
Description
GV2L04: rotary handle, magnetic only motor circuit breaker
In the TeSys GV2 family the GV2L04 is the magnetic version at 0.63 A. Its datasheet lists a rotary handle, a magnetic tripping current of 9.3 A and no thermal adjustment range, which is the visible sign that overload protection has to come from somewhere else in the motor circuit.
Reading the reference against the datasheet: the device short name is GV2L, which the datasheet pairs with a rotary handle and magnetic trip technology; the digits after the family letters follow the current band, here 0.63 A.
The datasheet gives the range as TeSys Deca and the product name as TeSys GV2, with the application stated as motor protection. Rated operational voltage is 690 V AC 50/60 Hz, rated insulation voltage 690 V AC 50/60 Hz and the rated impulse withstand 6 kV.
GV2L04 technical specifications
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Schneider Electric / GV2L04 |
| Range / product name | TeSys Deca / TeSys GV2 |
| Device short name | GV2L |
| Product type | Motor circuit breaker |
| Trip unit technology | Magnetic |
| Poles | 3P |
| Control | Rotary handle |
| Rated current [In] | 0.63 A |
| Magnetic tripping current | 9.3 A |
| Conventional thermal current [Ith] | 0.63 A |
| Rated operational voltage [Ue] | 690 V AC 50/60 Hz |
| Utilisation categories | Category A; AC-3; AC-3e |
| Suitability for isolation | Yes |
| Power dissipation per pole | 1.8 W |
| Mechanical durability | 100000 operating cycles |
| Electrical durability | 100000 cycles for AC-3 at 415 V In; 100000 cycles for AC-3e at 415 V In |
| Fixing | 35 mm symmetrical DIN rail: clipped | Panel: screwed (with 2 x M4 screws) |
| Mounting position | Horizontal or Vertical |
| Dimensions H × W × D | 89 × 45 × 97 mm |
| Net weight | 0.33 kg |
| Tightening torque | 1.7 N.m – on screw clamp terminal |
| IP / IK protection | IP20; IK04 |
| Operating temperature | -20 to 60 °C |
| Storage temperature | -40 to 80 °C |
| Operating altitude | ≤ 2000 m |
| Standards | EN/IEC 60947-2, EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, IEC/EN 60335-2-40:Annex JJ |
| Certifications | CB Scheme, CE, UKCA, CCC cULus, EAC, LROS (Lloyds register of shipping), BV, RINA, DNV-GL |
GV2L04 compared with neighbouring TeSys GV2 ratings
The table lists the closest GV2 references by current. Moving one step up or down changes the thermal range, the magnetic trip and the motor power it is intended for, while the frame stays the same. Neighbouring references are GV2P02, GV2P03, GV2P04 and GV2ME04.
| Reference | Type | Setting / rating | Magnetic trip | Motor kW at 400/415 V |
|---|---|---|---|---|
| GV2P02 | rotary handle, thermal-magnetic | 0.16–0.25 A | 3.08 A | 0.06 kW |
| GV2P03 | rotary handle, thermal-magnetic | 0.25–0.4 A | 5.8 A | 0.09 kW |
| GV2L04 (this page) | rotary handle, magnetic only | 0.63 A | 9.3 A | 0.12 / 0.18 kW |
| GV2P04 | rotary handle, thermal-magnetic | 0.4–0.63 A | 9.3 A | 0.12 / 0.18 kW |
| GV2ME04 | push-button, thermal-magnetic | 0.4–0.63 A | 9.3 A | 0.12 / 0.18 kW |
| GV2ME05 | push-button, thermal-magnetic | 0.63–1 A | 15.1 A | 0.25 kW |
Control style is part of the reference letters within the GV2 frame: GV2ME is push-button thermal-magnetic, GV2P rotary thermal-magnetic and GV2L rotary magnetic-only. Check the exact current band when changing style. The 0.4–0.63 A band exists in three styles in this group, GV2L04 (magnetic only, 9.3 A trip), GV2ME04 (push-button) and GV2P04 (rotary).
Dimensions, terminals and mounting of the GV2L04
The GV2L04 is 45 mm wide, 89 mm high and 97 mm deep. It clips onto a 35 mm symmetrical DIN rail and can also be screwed to a plate (two M4 screws). Mounting is horizontal or vertical. Power terminals are screw clamp terminals, with two conductors per terminal: 1–6 mm² solid; 1.5–6 mm² flexible without cable end; 1–4 mm² flexible with cable end.
Environmental limits from the datasheet are -20 to 60 °C in operation and -40 to 80 °C in storage, an altitude limit of up to 2000 m, and protection IP20. Power dissipation is 1.8 W per pole, so the heat released inside the enclosure at full load is about 5.4 W for the three poles; add this to the enclosure thermal budget in a Gulf plant room.
Motor ratings listed for the GV2L04
The datasheet ties this breaker to specific motor sizes at each supply voltage. These figures are the rated motor powers for the AC-3 category and are what a motor schedule should be matched against, not only the current.
| Supply voltage | Motor power in datasheet |
|---|---|
| 400/415 V AC | 0.12 / 0.18 kW |
| 690 V AC | 0.37 kW |
Rated duty is uninterrupted, and the durability figures are given in the table of specifications.
Selection checklist and RFQ details for the GV2L04
- Motor nameplate current and voltage, checked against the 0.63 A range and the motor kW table
- Required control style: rotary handle
- An overload relay is needed behind the breaker because this version has no thermal element
- Prospective short-circuit current at the board against the 100 kA rating at 400/415 V
- Terminals: screw clamp terminals; check the cable size and ferrule practice
- Space for a 45 mm wide device, 97 mm deep, and ambient heat inside the enclosure
- Accessories such as auxiliary contacts, trip indicators or busbar links if the design uses them
When requesting a quotation, include the following with the part number:
- Part number GV2L04 and quantity
- Motor power, voltage and full-load current
- Replacement or new build, and the existing breaker marking
- Delivery location and required date
Breaking capacity of the GV2L04 by voltage
Short-circuit breaking capacity falls as system voltage rises, which is the reason to read the whole table instead of a single headline value. The service breaking capacity Ics is shown as a percentage of Icu.
| Voltage | Icu | Ics as % of Icu |
|---|---|---|
| 230/240 V AC | 100 kA | 100 % |
| 400/415 V AC | 100 kA | 100 % |
| 440 V AC | 100 kA | 100 % |
| 500 V AC | 100 kA | 100 % |
| 690 V AC | 100 kA | 100 % |
At 400/415 V AC the rating is 100 kA, which is the figure that matters on most Gulf 400 V distribution boards; compare it with the prospective fault level at the point of installation and with any upstream protection before relying on it.
Using the GV2L04 in Oman and the GCC
Motor starters are everywhere in Gulf plants, and this breaker suits small dosing pumps, instrument-air and ventilation fans, valve actuators, conveyors and other fractional-kW drives. The datasheet lists motor powers up to 0.37 kW across its voltages, which is what the GV2 frame is built for. Typical sites are desalination and water treatment, power auxiliaries, oil and gas utilities, petrochemical units and commercial HVAC.
Heat and dust drive the real life of a breaker. With an operating limit of -20 to 60 °C and protection of IP20, the device belongs inside a ventilated or air-conditioned enclosure rather than on an open wall in summer sun. For a retrofit, send the nameplate and the old breaker marking and we will match it.
How the GV2L04 protects the motor feeder
The only trip element in the GV2L04 is magnetic. At 9.3 A the breaker opens instantly, which for a 0.63 A rating is a fixed threshold of roughly 14.8 times the rated current. There is no thermal setting dial, so there is nothing to adjust on site, and the datasheet does not list phase-failure sensitivity for this version.
This makes the GV2L04 a good fit where the motor is already protected against overload by a relay, a soft starter or a drive. The breaker then provides isolation and short-circuit protection, while the thermal function stays with the equipment that knows the real motor load. Do not use it alone as motor overload protection.
Documents and quotation
The Schneider Electric manufacturer datasheet for the GV2L04 is attached on this page as a PDF. It is the reference for every rating quoted above, and it is worth checking the revision against your project documents before an order is placed. The utilisation categories, breaking capacity table and environmental limits are all in it.
Seven Star LLC is an independent supplier in Muscat that serves buyers in Oman and the GCC. Send the part number GV2L04, the quantity and the delivery site, and we will reply with a quotation and the availability we can confirm.
Datasheets & Documents
- Datasheet Schneider Electric GV2L04 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.
Schneider Electric company profile
| Origins | 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry |
|---|---|
| Headquarters | Rueil-Malmaison (Paris region), France |
| Ownership | Public company listed on Euronext Paris |
| Key acquisitions | Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software |
| Brand names still in use | Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform |
| Product families | Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software |
Milestones
- 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
- 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
- 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
- 1997: Modicon, the company behind the first programmable logic controller, joins the group.
- 1999: The group takes the name Schneider Electric.
- 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.
Choosing Schneider Electric breakers and motor control
Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.
Where Schneider Electric products are used
In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.
APC by Schneider Electric: UPS and critical power
Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.
Schneider Electric products we list
| Family | Examples |
|---|---|
| Circuit breakers | Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW |
| Motor control | TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480 |
| Drives | Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo |
| PLCs, HMIs and relays | Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655 |
| Protection, metering and power | Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS |
Ordering Schneider Electric products: what we need
Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.
Facts checked against Schneider Electric's published company history, October 2026.
Browse Schneider Electric products by category: Circuit Breaker, Electrical & Power Modules, AC Drives, PLC & I/O Cards, Metering Systems, UPS and Batteries.
FAQ
Questions about the Schneider Electric GV2L04 TeSys GV2 0.63 A Motor
Answers from our engineering team on installation, compatibility and integration.
01What current range does the GV2L04 cover?
The GV2L04 is a magnetic-only breaker with a 0.63 A rating and a fixed magnetic trip of 9.3 A; it has no thermal adjustment.
02What is the breaking capacity of the GV2L04 at 400/415 V?
The datasheet gives 100 kA Icu at 400/415 V AC, with the service breaking capacity shown as a percentage of Icu in the table above.
03Does the GV2L04 provide overload protection?
No, it is a magnetic-only version. It trips on short-circuit and provides isolation, so a separate overload relay is needed.
04How is the GV2L04 operated and mounted?
It uses a rotary handle and mounts on a 35 mm DIN rail or on a panel. Size is 45 mm wide, 89 mm high and 97 mm deep.
05What motor powers is the GV2L04 listed for?
0.12 / 0.18 kW at 400/415 V; 0.37 kW at 690 V.