Schneider Electric GC2530M5 TeSys GC 25 A 3P Contactor

Description

GC2530M5 contactor: three-pole 25 A modular contactor on a 230 V coil

The GC2530M5 is a TeSys GC modular contactor with three normally open power poles, rated 25 A in AC-7a and 8.5 A in AC-7b, and a 220 to 240 V AC 50 Hz coil. It is the choice when a three-phase load, such as a bank of heaters or a lighting feeder, has to be switched from a 230 V control signal. Seven Star LLC supplies the GC2530M5 in Oman and the GCC as an independent supplier based in Muscat.

The 30 in the reference matches the three-pole 3 NO arrangement shown in the datasheet title, and M5 is the 220 to 240 V 50 Hz coil. The module is 36 mm wide, two 18 mm modules, 85 mm high and 62.5 mm deep, and the datasheet lists a net weight of 0.23 kg.

Technical specifications of the GC2530M5

Parameter Specification
Manufacturer / part number Schneider Electric / GC2530M5
Description Product datasheet TeSys GC – modular contactor – 25 A – 3 NO – coil 220 to 240 V AC
Range TeSys
Product name TeSys GC
Product or component type Modular contactor
Device short name GC25
Contactor application Motor control; Lighting; Heating
Utilisation category AC-7A; AC-7B
Poles description 3P
power pole contact composition 3 NO
[Ue] rated operational voltage <= 250 V AC
[Ie] rated operational current 25 A AC-7A; 8.5 A AC-7B
Operating position 30°/vertical
Control circuit type AC at 50 Hz
[Uc] control circuit voltage 220 to 240 V AC 50 Hz
[Uimp] rated impulse withstand 4 kV
[Ith] conventional free air thermal 25 A (at 50 °C) for power circuit
Irms rated making capacity 68 A at 400 V AC for power circuit conforming to IEC 61095
Rated breaking capacity 68 A at 400 V for power circuit conforming to IEC 61095
[Icw] rated short-time withstand 200 A 40 °C – 10 s for power circuit
Associated fuse rating 25 A gL at <= 440 V for power circuit
Average impedance 2.5 mOhm – Ith 25 A 50 Hz for power circuit
[Ui] rated insulation voltage 500 V conforming to IEC 61095; 500 V conforming to VDE 0110
Electrical durability AC-7A: 100000 cycles; AC-7B: 100000 cycles
Power dissipation per pole 1.6 W
Control type Remote control
Mounting mode Clip-on
Mounting support DIN rail; are subject to change – check with your local distributor.
Standards IEC 61095; IEC 60947-5
Connections – terminals Control circuit: screw clamp terminals 1 cable(s) 2.5 mm²flexible without cable end
Operating time 10 to 25 ms opening; 10 to 30 ms closing
Mechanical durability 1000000 cycles
Maximum operating rate 300 cyc/h 50 °C
Control circuit voltage limits Drop-out: 0.2 to 0.75 Uc at 50 Hz (at <50 °C); Operational: 0.85 to 1.1 Uc at 50 Hz (at <50 °C)
Inrush power in VA 34 VA 50 Hz (at 20 °C)
Hold-in power consumption in VA 4.6 VA 50 Hz (at 20 °C)

GC2530M5 selection steps

  • Count the poles: three 25 A poles, no auxiliary contact is built in.
  • Check the voltage across the poles against the 250 V AC maximum in the datasheet.
  • Use 8.5 A for motor loads, 25 A only for AC-7a resistive-type duty.
  • Control voltage: 220 to 240 V AC at 50 Hz.
  • Mounting space: 36 mm of rail width.
  • Compare with two-pole units such as the GC2520B5 if only one phase is switched.

GC modular contactor family compared with the GC2530M5

The five GC references below come from the same TeSys GC datasheet series and differ in current rating, pole count and coil. The highlighted row is the one on this page.

Reference Poles Rated current Coil Width Inrush Hold-in
GC2520B5 2P 25 A AC-7A / 8.5 A AC-7B 24 V AC 50 Hz 17.5 mm 15 VA 50 Hz (at 20 ° 3.8 VA 50 Hz (at 20
GC2520M6 2P 25 A AC-7A / 8.5 A AC-7B 220 to 240 V AC 60 Hz 17.5 mm 15 VA 50 Hz (at 20 ° 3.8 VA 50 Hz (at 20
GC2530M5 3P 25 A AC-7A / 8.5 A AC-7B 220 to 240 V AC 50 Hz 36 mm 34 VA 50 Hz (at 20 ° 4.6 VA 50 Hz (at 20
GC4020M5 2P 40 A AC-7A / 15 A AC-7B 220 to 240 V AC 50 Hz 36 mm 34 VA 50 Hz (at 20 ° 4.6 VA 50 Hz (at 20
GC4030M5 3P 40 A AC-7A / 15 A AC-7B 220 to 240 V AC 50 Hz 54 mm 53 VA 50 Hz (at 20 ° 6.5 VA 50 Hz (at 20

Three-phase duty for the GC2530M5

Three poles make the GC2530M5 suitable for a three-phase balanced load, but the rated operational voltage is listed as at most 250 V AC, so on a 400 V network the poles are intended for loads connected phase to neutral or line to line within that limit. Check the voltage across the poles against the datasheet before using it on a higher-voltage circuit.

If the load is a motor, the 8.5 A AC-7b figure applies, not 25 A. For larger motors a TeSys D contactor such as the LC1D09M7 is the more fitting product, with proper AC-3 ratings.

Coil and heat figures for the GC2530M5

The coil draws 34 VA 50 Hz (at 20 °C) at inrush and 4.6 VA 50 Hz (at 20 °C) when held in, according to the datasheet. Total heat dissipation is quoted as 1.6 W at 50/60 Hz, and each power pole dissipates 1.6 W at rated current. For a distribution board these numbers decide how many contactors can sit in one row before the enclosure needs ventilation.

The operating limits are written as Drop-out: 0.2 to 0.75 Uc at 50 Hz (at <50 °C); Operational: 0.85 to 1.1 Uc at 50 Hz (at <50 °C). At the lower edge, the contactor may not close on a sagging control supply, which is worth considering for sites with long control cables or weak generator supplies.

Wiring and protection of the GC2530M5

The power terminals take up to 6 mm² flexible conductor and are tightened to 0.8 N.m, as is the control terminal. Associated protection is a 25 A gL fuse for operation up to 440 V. The recommended mounting position is within 30 degrees of vertical so that the moving armature keeps its designed clearance.

Plan an interval for inspection of the poles on circuits that switch often. The datasheet states an electrical durability of 100000 cycles in AC-7a and AC-7b, which at one operation per hour would be several years, but at a few hundred per day is consumed quickly.

GC2530M5 in typical Gulf installations

Commercial buildings in Muscat and across the GCC use three-pole modular contactors for lighting groups, electric heating, air-curtain and small water-heating loads, usually controlled from a timer, BMS or photocell at 230 V.

In industrial sites the same module is common in small control boards, switching resistance heaters of tracing circuits and anti-condensation heaters in panels, where space on the rail is limited.

Information to send with an RFQ for the GC2530M5

  • Full reference and quantity required
  • Coil voltage and frequency available on site
  • Load type and current (resistive, lighting or motor)
  • Number of poles and enclosure space available
  • Delivery location and timing

Documents and quotation

A datasheet for the GC2530M5 is attached on this page. It carries the electrical, mechanical and environmental data summarised above, so the figures can be checked against your drawings.

Send the part number, quantity and application and we will confirm availability and a quotation. Seven Star LLC is an independent supplier in Muscat and is not affiliated with the manufacturer.

Other Models in the Se Tesys Gc Range

Seven Star LLC supplies models from the Se Tesys Gc range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Schneider Electric GC2520B5 TeSys GC 25 A 2P ContactorContactors & Overload RelaysView details
Schneider Electric GC2520M6 TeSys GC 25 A 2P 60 Hz ContactorContactors & Overload RelaysView details
Schneider Electric GC2530M5 TeSys GC 25 A 3P ContactorContactors & Overload RelaysYou are viewing this model
Schneider Electric GC4020M5 TeSys GC 40 A 2P ContactorContactors & Overload RelaysView details
Schneider Electric GC4030M5 TeSys GC 40 A 3P ContactorContactors & Overload RelaysView details
Datasheets & Documents
  • PDF Datasheet Schneider Electric GC2530M5 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric GC2530M5 TeSys GC 25 A 3P

Answers from our engineering team on installation, compatibility and integration.

01How many poles does the GC2530M5 have?
Three normally open power poles, rated 25 A in AC-7a.
02What coil does the GC2530M5 use?
The coil is 220 to 240 V AC at 50 Hz. See the datasheet linked on this page for the full figures.
03How wide is the GC2530M5?
36 mm, which is two 18 mm modules, 85 mm high and 62.5 mm deep.
04What is the coil consumption of the GC2530M5?
The datasheet lists 34 VA at inrush and 4.6 VA hold-in at 50 Hz and 20 degrees C.
05What is the weight of the GC2530M5?
The datasheet gives a net weight of 0.23 kg.