Brand: Schneider Electric
Schneider Electric A9F43102 Acti9 iC60N 1P 2A Curve B MCB
Description
A9F43102: Acti9 iC60N 1P 2 A curve B miniature circuit breaker
The A9F43102 is a Schneider Electric Acti9 iC60N miniature circuit-breaker with 1 protected pole, a rated current of 2 A and curve B tripping, using thermal-magnetic technology for overload and short-circuit protection on AC/DC networks. It clips onto a DIN rail and is white, with a toggle handle and a trip indicator. Seven Star LLC supplies the A9F43102 in Oman and the GCC as an independent supplier based in Muscat.
Reading the reference: across the iC60N references we reviewed, the fifth character shows the curve (3 for B, 4 for C), the sixth the number of poles, and the last two digits a rating code. That is our interpretation of the pattern, not a published ordering table, so always confirm against the datasheet. Lifecycle note: the datasheet carries a Discontinued label with the date 15 Aug 2025. Availability is therefore not guaranteed; send the reference and we will check what can be offered, including alternatives.
Technical specifications of the A9F43102
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Schneider Electric / A9F43102 |
| Range / product name | Acti9 / Disbo iC60 |
| Product type | Miniature circuit-breaker |
| Device short name | IC60N |
| Poles / protected poles | 1P / 1 |
| Rated current In | 2 A |
| Curve code | B |
| Trip unit | Thermal-magnetic |
| Magnetic tripping limit | 4 x In ± 20 % |
| Network type | AC/DC |
| Network frequency | 50/60 Hz |
| Rated operational voltage Ue | 12–60 V AC 50/60 Hz ; 100–133 V AC 50/60 Hz ; 220–240 V AC 50/60 Hz ; 12–60 V DC ; 60–72 V DC |
| Utilisation category | Category A (EN/IEC 60947-2) |
| Limitation class | 3 (EN/IEC 60898-1) |
| Rated insulation voltage Ui | 500 V AC |
| Rated impulse withstand Uimp | 6 kV |
| Terminals | Single terminal (top or bottom) 1–25 mm² rigid ; Single terminal (top or bottom) 1–16 mm² flexible |
| Wire stripping length | 14 mm |
| Tightening torque | 2 N.m top or bottom |
| Dimensions (H x W x D) | 85 × 18 × 78.5 mm |
| Net weight | 0.125 kg |
| Mechanical durability | 20000 cycles |
| Electrical durability | 10000 cycles |
| Padlocking | Padlockable |
| Protection / pollution degree | IP20 (IEC 60529) / degree 3 |
| Operating temperature | −35–70 °C |
| Storage temperature | −40–85 °C |
| Relative humidity | 95 % at 55 °C |
| Standards | EN/IEC 60898-1, EN/IEC 60947-2 |
| Warranty | 18 months |
Breaking capacity of the A9F43102
Breaking capacity is where iC60N references differ most, and the figures depend on the supply voltage. The rated ultimate values (Icu) and the household rating (Icn) listed in the datasheet for this reference are:
| Rating type | Value | Supply | Standard |
|---|---|---|---|
| Icu | 50 kA | 12–60 V AC 50/60 Hz | EN/IEC 60947-2 |
| Icu | 50 kA | 100–133 V AC 50/60 Hz | EN/IEC 60947-2 |
| Icu | 50 kA | 220–240 V AC 50/60 Hz | EN/IEC 60947-2 |
| Icu | 15 kA | 12–60 V DC | EN/IEC 60947-2 |
| Icu | 10 kA | 60–72 V DC | EN/IEC 60947-2 |
| Icn | 6000 A | 240 V AC 50/60 Hz | EN/IEC 60898-1 |
The service breaking capacity (Ics) states how much of that capability remains usable after a clearing operation:
| Supply | Service breaking capacity Ics |
|---|---|
| 12–60 V AC 50/60 Hz | 50 kA (100 % of Icu) |
| 100–133 V AC 50/60 Hz | 50 kA (100 % of Icu) |
| 220–240 V AC 50/60 Hz | 50 kA (100 % of Icu) |
| 12–60 V DC | 15 kA (100 % of Icu) |
| 60–72 V DC | 10 kA (100 % of Icu) |
Compare these numbers with the prospective short-circuit current at your board. At 220–240 V AC the A9F43102 is the relevant column for a 230 V Oman installation; the DC values apply only to specialist DC circuits.
Trip curve and pole arrangement of the A9F43102
Curve B is the lower-threshold characteristic: the datasheet gives a magnetic tripping limit of 4 x In ± 20 %, so the instantaneous trip operates at a low multiple of the rated current. That suits resistive loads, lighting, long cable runs and weak sources where a fault current may be modest, and it is a poor choice for loads with high inrush such as transformers or motors, which could cause nuisance trips.
This is a single-pole device with one protected pole, taking up 2 modules of 9 mm (18 mm wide). It switches one conductor, normally the phase of a 230 V circuit, so the neutral stays connected unless a separate arrangement disconnects it. Confirm the earthing system and local wiring rules before using a single-pole breaker as the only means of isolation.
The thermal element handles sustained overload by bending as the bimetal heats, so it reacts to current over time and is sensitive to ambient temperature, while the magnetic element reacts almost instantly to a short circuit. A contact position indicator and a trip indicator on the front show the state of the device without opening the board.
Where the 2 A rating is used
At 2 A this breaker sits at the very small end of the iC60N scale. Typical homes for it are control-transformer secondaries, instrument and PLC supply feeds, small signalling circuits and auxiliary supplies inside panels, where the job is to clear a fault on thin conductors quickly. The protected current is far below a socket-circuit rating, so the wiring downstream is normally light and the let-through behaviour matters more than raw capacity.
Oman and GCC sites add their own demands: high ambient temperature inside metal enclosures in summer, dust, and humid coastal air. The datasheet lists an operating range of −35 to 70 °C and tropicalisation 2, but a board that runs hot still needs ventilation margin and sensible spacing between breakers. Typical users are electrical contractors, panel shops and maintenance teams in oil and gas facilities, power and water plants, desalination units, petrochemical sites and commercial buildings.
Information to send with an RFQ for the A9F43102
- Exact reference A9F43102 and required quantity.
- Rated current and curve, so we can confirm the reference reads as intended.
- Supply voltage and prospective short-circuit current at the board.
- Any matching accessories such as combs, auxiliary contacts or add-on residual current blocks.
- Delivery location and required date.
Installation and maintenance of the A9F43102
Snap the A9F43102 onto the DIN rail, strip the conductor to 14 mm, and tighten terminals to the datasheet torque: 2 N.m top or bottom. Under-torqued lugs heat up, and over-torqued ones damage the clamp, so use a calibrated screwdriver. The handle accepts a padlock for lock-out during maintenance. After a trip, find the cause before resetting: the trip indicator tells you the breaker operated, not why.
Periodic checks include thermal imaging of terminals under load, retightening where the site procedure requires it, and operating the toggle occasionally to keep the mechanism free. Keep a spare of critical ratings on site, because a failed breaker on a main process circuit can stop a unit.
Selection and ordering checklist for the A9F43102
- Confirm the load current and choose 2 A only if cable and load allow it.
- Check that curve B suits the inrush of the load: low inrush, resistive or lighting.
- Verify the prospective short-circuit current against the breaking capacity table above.
- Match the number of poles (1) to the circuit and earthing system.
- Check the busbar or comb accessory fits the 2-module width.
- Confirm terminal capacity (1–25 mm² rigid) and use the stated torque of 2 N.m.
- Ask about availability and lifecycle status.
Related iC60N references to A9F43102
Within the references reviewed alongside this one, other 1-pole curve B breakers are A9F43101 (1 A), A9F43106 (6 A), A9F43110 (10 A), A9F43116 (16 A), A9F43120 (20 A), A9F43132 (32 A). They share the outline and terminals of the A9F43102 within the same size group but carry different rated currents. The datasheet also lists compatible add-on residual current devices: Vigi iC60 single terminal add-on residual current device 25/40/63 A; Quick Vigi iC60 single terminal add-on residual current device 25/40 A. Earth-leakage protection is a separate block, not built into this breaker, so the A9F43102 does not by itself provide residual-current protection.
Documents and quotation
A datasheet for the A9F43102 is attached on this page as a PDF. It covers the main characteristics, dimensions, environment and packaging data of this reference.
Send the part number A9F43102 and quantity, and we will respond with availability and a quotation. Seven Star LLC is an independent supplier in Muscat; confirm any approval or compliance requirement before ordering.
Other Models in the Se Ic60n 1p B Range
Seven Star LLC supplies models from the Se Ic60n 1p B range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Schneider Electric A9F43101 Acti9 iC60N 1P 1A Curve B MCB | Circuit Breakers | View details |
| Schneider Electric A9F43102 Acti9 iC60N 1P 2A Curve B MCB | Circuit Breakers | You are viewing this model |
Datasheets & Documents
- Datasheet Schneider Electric A9F43102 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.
Schneider Electric company profile
| Origins | 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry |
|---|---|
| Headquarters | Rueil-Malmaison (Paris region), France |
| Ownership | Public company listed on Euronext Paris |
| Key acquisitions | Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software |
| Brand names still in use | Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform |
| Product families | Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software |
Milestones
- 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
- 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
- 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
- 1997: Modicon, the company behind the first programmable logic controller, joins the group.
- 1999: The group takes the name Schneider Electric.
- 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.
Choosing Schneider Electric breakers and motor control
Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.
Where Schneider Electric products are used
In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.
APC by Schneider Electric: UPS and critical power
Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.
Schneider Electric products we list
| Family | Examples |
|---|---|
| Circuit breakers | Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW |
| Motor control | TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480 |
| Drives | Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo |
| PLCs, HMIs and relays | Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655 |
| Protection, metering and power | Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS |
Ordering Schneider Electric products: what we need
Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.
Facts checked against Schneider Electric's published company history, October 2026.
Browse Schneider Electric products by category: Circuit Breaker, Electrical & Power Modules, AC Drives, PLC & I/O Cards, Metering Systems, UPS and Batteries.
FAQ
Questions about the Schneider Electric A9F43102 Acti9 iC60N 1P 2A Curve
Answers from our engineering team on installation, compatibility and integration.
01What is the A9F43102?
It is a Schneider Electric Acti9 iC60N miniature circuit-breaker with 1 protected pole, 2 A rated current and curve B, thermal-magnetic, for DIN rail mounting. Overall width is 18 mm.
02What is the trip curve of the A9F43102?
The datasheet lists curve code B with a magnetic tripping limit of 4 x In ± 20 %. Curve B is chosen for resistive and lighting loads.
03What breaking capacity does the A9F43102 have?
The datasheet lists 50 kA Icu at 220–240 V AC 50/60 Hz per EN/IEC 60947-2. The full set of values by voltage is in the breaking-capacity table on this page.
04Does the A9F43102 include earth-leakage protection?
No. The datasheet lists earth-leakage protection as a separate block, and names compatible Vigi iC60 add-on devices. Send us the part number you need and we will compare options.
05What terminals and torque apply to the A9F43102?
Single terminal (top or bottom) 1–25 mm² rigid; tightening torque 2 N.m top or bottom, with 14 mm stripping length.