Pepperl+Fuchs KFD2-STC4-Ex1.H Transmitter Supply

Description

KFD2-STC4-Ex1.H: STC4 supply with extra field voltage

For transmitters with high minimum operating voltage the Pepperl+Fuchs KFD2-STC4-Ex1.H offers at least 17.6 V DC at 20 mA on terminals 1+ and 3. It is a single-channel isolated barrier that powers 2-wire and 3-wire SMART transmitters, or serves as a repeater for 2-wire SMART current sources, and delivers an isolated 0/4 to 20 mA signal to the control side.

Output terminals 7-, 8+ and 9 give access to the control-side loop and to a 250 ohm internal resistor that can provide HART communication resistance.

Highlights

  • Field voltage 17.6 V at 20 mA, the highest among the STC4 single-channel versions
  • Load 0 to 800 ohm at 20 mA; output overload above 25 mA
  • Deviation up to 10 microamps including calibration, linearity, hysteresis, load and supply influences
  • Input alternatives: terminals 1+, 2-, 3 for transmitters, or 5- and 6+ for current sources with up to 2.4 V voltage drop at 20 mA
  • Settling time 200 microseconds, rise and fall times 20 microseconds

KFD2-STC4-Ex1.H specifications

Parameter Value
Supply 20 to 35 V DC, terminals 14+ and 15-
Dissipation / consumption 1.5 W / 1.9 W
Input 0/4 to 20 mA
Input resistance up to 64 ohm (terminals 2-, 3); up to 500 ohm (terminals 1+, 3 with 250 ohm load)
Available field voltage at least 17.6 V at 20 mA
Output load 0 to 800 ohm at 20 mA
Ripple up to 50 microamps rms
Temperature influence 0.25 microamps per K
Bandwidth 0 to 7.5 kHz and 0.3 to 7.5 kHz (0.5 Vpp signal, 3 dB)
Insulation functional, 50 V AC output to supply
ATEX certificate BAS 99 ATEX 7060 X
Dimensions, mass 20 x 124 x 115 mm, about 200 g
Ambient -20 to 60 degrees C

Choosing high voltage deliberately

A higher field voltage means more dissipation in the barrier; at 1.5 W it runs warmer than a standard unit. It is therefore not a drop-in default for every loop. Use it when the field device, cable drop or an in-line surge protector would otherwise starve the transmitter of voltage. Typical examples include radar and guided-wave level transmitters in storage tanks, which often specify a minimum terminal voltage above 14 V, magnetic flow meters with loop-powered electronics and analysers with heated sensors.

Contrast with KFD2-STC4-Ex2 and the standard STC4 types

The two-channel KFD2-STC4-Ex2 offers only 16 V per channel at 20 mA and handles 2-wire transmitters, whereas KFD2-STC4-Ex1.H gives 17.6 V on one channel and also accepts 3-wire transmitters. Its mass of about 200 g exceeds the 150 g of the standard single-channel STC4, reflecting the added circuitry for the higher voltage. The certificate number also changes to BAS 99 ATEX 7060 X.

Wiring pointers

Choose between terminals 1+, 2- and 3 for transmitter operation and terminals 5- and 6+ for current-source repeater operation. Connect the supply to terminals 14+ and 15- or to the Power Rail. Observe the maximum safe voltage and the special conditions marked by X in the certificate.

Periodic checks

Measure the voltage at the transmitter terminals at 20 mA after any modification of cable or protection devices. Test the output with a simulator once a year.

Planning

Keep one spare for each voltage class used in the plant, stored with a tag that records the part number and the supply voltage, so that a failed high-voltage unit is replaced by the same type, not by a standard model that might leave the transmitter underpowered.

Relation to the newer STC5 model

The KFD2-STC5-Ex1.H delivers 17 V at 20 mA and 24 V open circuit with 500 microsecond settling, so STC4 and STC5 versions are not identical drop-ins; compare the figures in the tables before substituting.

Installation environment

The module is rated for -20 to 60 degrees C and IP20 protection, so it needs an enclosure with suitable ingress protection for dusty or humid sites. Clip it to a 35 mm DIN rail with the blue terminal block towards the hazardous-area wiring. Keep intrinsically safe wiring separated from other cables by the distance or barriers required by the installation standard, typically 50 mm for open wiring. Do not forget that a hot module running at the high-voltage setting loses accuracy only slightly, since the temperature influence is 0.25 microamps per K, but its life is shortened by persistent overheating. Where several of these modules sit side by side, check that the combined dissipation of about 1.5 W each does not push the cabinet over its temperature limit.

Questions buyers ask about KFD2-STC4-Ex1.H

What field voltage does KFD2-STC4-Ex1.H deliver? It delivers at least 17.6 V at 20 mA on terminals 1+ and 3.

What load can KFD2-STC4-Ex1.H drive? The output load range is 0 to 800 ohm at 20 mA with overload detection above 25 mA.

Can KFD2-STC4-Ex1.H be used with 3-wire transmitters? Yes, it supplies 2-wire and 3-wire SMART transmitters and can repeat 2-wire SMART current sources.

What is the supply range of KFD2-STC4-Ex1.H? The supply is 20 to 35 V DC with a power dissipation of 1.5 W and consumption of 1.9 W.

Which certificate applies to KFD2-STC4-Ex1.H? The datasheet lists EU-type examination certificate BAS 99 ATEX 7060 X.

Documents and quotation

The manufacturer datasheet for KFD2-STC4-Ex1.H accompanies this listing as a PDF so your engineers can verify terminals, ratings and approvals before purchase. Add the transmitter model and cable length for a voltage check. To request a quotation, send the RFQ with the exact part number KFD2-STC4-Ex1.H, the quantity, the delivery location in Oman or the GCC and any project reference. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer.

Installation and Commissioning Planning

Planning ahead shortens downtime when a Pepperl+Fuchs KFD2-STC4-Ex1.H goes into service. Confirm the available mounting space, cable entry or process connection, and the tools and spare seals needed on the day. Keep the existing configuration or calibration data so the new unit can be set up to match, and check that loop drawings and the asset register are updated after the swap. If the installation has to fit a short shutdown window, tell us the date when you request a quotation so that delivery of the Pepperl+Fuchs equipment can be planned around it.

Other Models in the Stc4 Transmitter Range

Seven Star LLC supplies models from the Stc4 Transmitter range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Pepperl+Fuchs KFD2-STC4-Ex1.H Transmitter SupplyIsolator & BarrierYou are viewing this model
Pepperl+Fuchs KFD2-STC4-Ex2 2-Channel Transmitter SupplyIsolator & BarrierView details
Datasheets & Documents
  • PDF Datasheet Pepperl+Fuchs KFD2-STC4-Ex1.H Transmitter Supply Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Pepperl+Fuchs is a German manufacturer of industrial sensors and explosion protection equipment, founded in 1945 in Mannheim by Walter Pepperl and Ludwig Fuchs as a radio repair shop. Defective transformers led them into manufacturing, and the company developed its first proximity switch in the late 1950s. Pepperl+Fuchs is headquartered in Mannheim and is a pioneer of intrinsically safe electrical equipment for hazardous areas.

Seven Star LLC lists Pepperl+Fuchs sensors, isolated barriers, power supplies and hazardous-area mobile devices, and supplies them to instrument and automation teams in Oman by exact model designation.

Pepperl+Fuchs company profile

Founded 1945, Mannheim-Sandhofen, Germany, by Walter Pepperl and Ludwig Fuchs
Headquarters Mannheim, Germany
Ownership Privately owned (Pepperl+Fuchs SE)
Origins Radio repair workshop that began making replacement transformers
Product families Inductive, capacitive, ultrasonic and photoelectric sensors, rotary encoders, R2000 LiDAR scanners, KFD and HiC isolated barriers, Zener barriers, remote I/O, purge and pressurization systems, Ex-rated enclosures

Milestones

  • 1945: Walter Pepperl and Ludwig Fuchs open their radio repair shop in Mannheim.
  • 1958: The first proximity switch is developed (some company sources say 1959).

Pepperl+Fuchs product families on this page

On the interface side there are two systems. The K-System mounts on DIN rail and is represented here by the KFD2-UT2-Ex2 universal temperature converter. The H-System plugs into termination boards and is represented by the HiD2030 SMART transmitter power supply with HART. The PS1000-A6-24.20 is a 24 VDC, 20 A power supply for cabinets. Sensors listed include the NJ2-12GK-SN NAMUR inductive sensor, the R101 retro-reflective photoelectric sensor and the R2000 2-D LiDAR scanner. For field staff there are the Tab-Ex 05 DZ1 tablet for Zone 1/21 areas and the Smart-Ex 03 DZ2 smartphone for Zone 2/22 and Division 2 areas.

Where Pepperl+Fuchs equipment is used

Isolated barriers sit between field instruments in Zone 0 or Zone 1 and the DCS or safety system in refineries, gas plants and chemical works. NAMUR sensors report valve position and machine states in classified areas. Photoelectric sensors and LiDAR scanners work in conveying, packaging, warehousing and vehicle guidance. Ex-rated tablets and phones are carried on operator rounds and maintenance jobs.

Pepperl+Fuchs products we list

Family Examples
Isolator & Barrier HiD2030 SMART Transmitter Power Supply w…, KFD2-SR2-Ex2.W K-System Isolated Switch…, KFD2-UT2-Ex2 Universal Temperature Conve…
Industrial Computers Tab-Ex 05 DZ1 WWAN Hazardous Area Tablet, Smart-Ex® 03 DZ2 smartphone for Zone 2/2…
Inductive Proximity Sensors NJ2-12GK-SN NAMUR Inductive Sensor
Power Modules PS1000-A6-24.20 Power Supply 24 VDC 20 A
Photoelectric Sensors R101 Retro-Reflective Photoelectric Sensor
Laser Distance, LiDAR & Radar Sensors R2000 2-D LiDAR Laser Scanner

Ordering Pepperl+Fuchs parts: what we need

Send the complete model designation as printed on the device, including every suffix; a single letter can change the supply voltage or the output type. Add the part number if the label shows one. For barriers, tell us the field device and signal type, the number of channels and whether the safety loop needs a SIL-assessed module. For mobile devices, state the zone or division and the regional radio version.

Facts checked against Pepperl+Fuchs's own chronicle pages, October 2026.

FAQ

Questions about the Pepperl+Fuchs KFD2-STC4-Ex1.H Transmitter Supply

Answers from our engineering team on installation, compatibility and integration.

01What field voltage does KFD2-STC4-Ex1.H deliver?
It delivers at least 17.6 V at 20 mA on terminals 1+ and 3.
02What load can KFD2-STC4-Ex1.H drive?
The output load range is 0 to 800 ohm at 20 mA with overload detection above 25 mA.
03Can KFD2-STC4-Ex1.H be used with 3-wire transmitters?
Yes, it supplies 2-wire and 3-wire SMART transmitters and can repeat 2-wire SMART current sources.
04What is the supply range of KFD2-STC4-Ex1.H?
The supply is 20 to 35 V DC with a power dissipation of 1.5 W and consumption of 1.9 W.
05Which certificate applies to KFD2-STC4-Ex1.H?
The datasheet lists EU-type examination certificate BAS 99 ATEX 7060 X.