Brand:

Omron MY2N-CR-GS AC Relay with Built-In CR Surge Circuit

Description

MY2N-CR-GS: AC-coil relay with a built-in CR absorber

The Omron MY2N-CR-GS is a DPDT miniature power relay for AC coils with a built-in CR (capacitor and resistor) circuit that absorbs coil switching surges. It also has a LED operation indicator and mechanical indicators. It is selected when the coil is driven by a solid-state output or a long cable where turn-off transients cause nuisance. Seven Star LLC supplies the MY2N-CR-GS in Oman and the GCC as an independent supplier in Muscat.

  • MY is the miniature plug-in power relay series.
  • 2 means two poles (DPDT) and an 8-pin footprint.
  • N means LED operation indicator and mechanical indicators.
  • CR means a built-in CR circuit for coil surge absorption.
  • GS is the series suffix; AC coil versions listed are 100/110, 110/120, 200/220 and 220/240 V.

The CR circuit is designed for AC coils; for DC coils the datasheet uses a diode instead, with MY2N-D1-GS and MY2N-D2-GS selected by polarity.

MY2N-CR-GS technical specifications

Parameter Specification
Manufacturer / part number Omron MY2N-CR-GS (datasheet ordering code MY2N-CR-GS-R with coil voltage)
Poles / contact form 2 poles, DPDT
Coil surge absorption Built-in CR circuit
Coil voltages 100/110, 110/120, 200/220, 220/240 VAC
Contact rating, resistive 10 A at 250 VAC; 10 A at 30 VDC
Max. switching capacity 2,500 VA / 300 W
Max. contact voltage 250 VAC, 220 VDC
Coil power consumption Approx. 0.9 to 1.3 VA at 60 Hz (AC coils)
Operating temperature −40 to 70°C for models with LED
Operate / release time 20 ms max. / 20 ms max.
Contact resistance 100 mΩ max.
Contact material Ag
Insulation resistance 1,000 MΩ min.
Dielectric strength 2,000 VAC coil to contacts; 2,000 VAC between different poles; 1,000 VAC same pole
Mechanical endurance 50,000,000 operations
Max. frequency 18,000 operations/h mechanical; 2,400 operations/h at rated load
Minimum load (reference) 1 mA at 5 VDC
Humidity 5% to 85%
Weight Approx. 35 g

CR types are listed only for the high-voltage AC coils. Because the CR circuit leaks a small current through the coil, release behaviour with solid-state outputs should be checked against the datasheet release voltage of 30% minimum of rated voltage.

How MY2N-CR-GS works and what the indicators show

An AC relay coil stores energy that, when switched off, can generate a voltage spike that stresses the switching device and radiates noise. A series capacitor and resistor in parallel with the coil absorbs this energy locally, protecting contacts or solid-state outputs upstream.

The built-in circuit also provides a path for a small leakage current when the coil is switched by a solid-state output, so the user must verify that the coil releases reliably. The relay itself still operates in the normal way, with indicators showing contact position and LED lit when energised.

Coil ratings for MY2N-CR-GS

MY2N-CR-GS is available only with AC coils of 100 V and above. The table lists the AC coil data from the datasheet.

AC coil data from the datasheet (rated current measured at 23°C):

Rated voltage (AC) Current 50 Hz / 60 Hz (mA) Coil resistance (ohm)
12 V 106.5 / 91 46
24 V 53.8 / 46 180
48 V 25.7 / 21.1 788
100/110 V 11.7/12.9 / 10.0/11.0 3,750
110/120 V 9.9/10.8 / 8.4/9.2 4,430
200/220 V 6.2/6.8 / 5.3/5.8 12,950
220/240 V 5.2/6.2 / 4.3/5.0 15,920

Must-operate voltage is 80% of rated voltage maximum for AC coils (30% minimum must-release) and the same 80% maximum for DC coils with 10% minimum must-release. Maximum voltage is 110% of rated. For specified characteristics, apply the rated voltage to the coil.

Sockets and related parts for MY2N-CR-GS

The relay is a plug-in match for MY2 sockets (PYFZ-08-E, PYF08A-N, PYF-08-PU, PY08-02). If your coil is DC, use the diode versions MY2N-D1-GS or MY2N-D2-GS; for no suppression at all choose MY2N-GS. The latching version with CR is MY2IN-CR-GS.

Mounting 8-pin (MY2 types)
Front, finger-safe PYFZ-08-E, PYF08A-N
Front, Push-In Plus PYF-08-PU
Back, PCB PY08-02

Sockets are ordered separately. The datasheet also mentions the PYC-A1 and PYC-P retaining parts for joining socket and relay, and notes that a relay with a latching lever and a PCB-terminal socket need the PYC-P mounting bracket to be checked first.

Selection and ordering checklist for MY2N-CR-GS

Settle the following before requesting a quotation for MY2N-CR-GS.

  • Confirm that the coil supply is AC at 100/110, 110/120, 200/220 or 220/240 V.
  • Verify that the coil driver (contact or solid-state) is compatible with a built-in CR leakage current.
  • Check release voltage in your circuit; the must-release value is 30% min. of rated voltage.
  • Check load against 10 A at 250 VAC.
  • Select an 8-pin socket.
  • If you want a latching lever, request MY2IN-CR-GS instead.

Installation, commissioning and maintenance of MY2N-CR-GS

Install in an 8-pin socket and connect the coil to the correct terminals; polarity does not matter for AC coils. Check that no extra external RC network duplicates the built-in circuit.

  • Measure coil voltage with the relay installed; leakage can hold the relay if too high.
  • Use the mechanical indicator to confirm release when the control signal is removed.
  • Keep AC and DC relay spares separate and labelled.
  • Record the coil voltage on the panel label.
  • Replace on schedule where coil circuits are noisy.

Typical MY2N-CR-GS applications in Oman and the GCC

This relay is used where AC coils are switched by electronic modules, such as PLC triac outputs or timers, and where inductive kick-back could disturb neighbouring circuits. It is also suited to long coil cables in field-mounted panels. In Oman and the GCC typical sites include water-pumping stations, substation auxiliary panels and HVAC control cabinets.

Mains conditions in the region can be noisy near large motors and variable-speed drives, so surge-absorbing coils help keep control circuits stable.

MY-GS family compared with MY2N-CR-GS

The MY-GS series covers several versions of the same relay body. This table shows where MY2N-CR-GS sits among them.

Model Poles Extras Coil types
MY2-GS 2 (DPDT) Mechanical indicator only AC and DC
MY2N-GS 2 (DPDT) LED + mechanical indicator AC and DC
MY2IN-GS 2 (DPDT) LED, indicator and latching lever AC and DC
MY2N-D1/D2-GS 2 (DPDT) LED, built-in diode (polarity 13+ or 14+) DC
MY2N-CR-GS 2 (DPDT) LED, built-in CR circuit AC 100 V and above
MY4N-GS / MY4IN-GS 4 (4PDT) LED; latching lever on IN AC and DC

Information to send with an RFQ for MY2N-CR-GS

  • Part number MY2N-CR-GS and AC coil voltage.
  • Quantity of relays and sockets.
  • Type of coil driver (contact, triac, timer).
  • Load on contacts.
  • Socket mounting.
  • Delivery location.

Documents and quotation

A datasheet for the MY-GS series is attached on this page with the model legend, coil data, contact ratings, certified ratings, socket list and precautions relevant to MY2N-CR-GS.

Seven Star LLC is an independent supplier in Muscat and is not affiliated with the manufacturer. Send the part number MY2N-CR-GS with the coil voltage and quantity, and we will confirm availability and lead time for Oman and the GCC.

Other Models in the Omron My Gs Relays Range

Seven Star LLC supplies models from the Omron My Gs Relays range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Omron MY2N-GS DPDT Miniature Power Relay with LEDAutomation AccessoriesView details
Omron MY4N-GS 4PDT Miniature Power Relay with LEDAutomation AccessoriesView details
Omron MY2IN-GS DPDT Relay with Latching Lever and LEDAutomation AccessoriesView details
Omron MY2N-CR-GS AC Relay with Built-In CR Surge CircuitAutomation AccessoriesYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Omron MY2N-CR-GS Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Omron is a Japanese electronics and automation company, founded in 1933 in Osaka by Kazuma Tateisi and now headquartered in Kyoto. Its industrial automation business makes PLCs, I/O, sensors, relays, safety components, motion control and robots. Omron's CJ and NX series controllers and I/O units are widely used in machine building.

Seven Star LLC lists Omron PLC input and output units from the CJ and NX series and supplies them to panel builders and maintenance teams in Oman.

Omron company profile

Founded 1933, Osaka, Japan
Founder Kazuma Tateisi
Headquarters Kyoto, Japan
Business Industrial automation, healthcare, electronic components
Product families CJ1/CJ2 PLCs and I/O units, NX and NJ controllers, NX I/O, E2E proximity sensors, G2R and MY relays

Omron CJ-series and NX-series units listed here

Three I/O units are on this page. The CJ1W-ID211 is a CJ-series 16-point 24 VDC input unit and the CJ1W-OC211 is a CJ-series 16-point relay output unit. The NX-ID5442 is an NX-series 16-point 24 VDC digital input unit for PNP wiring, 12 mm wide with push-in terminals. CJ and NX units belong to different hardware platforms and do not plug into each other's racks.

Omron products we list

Family Examples
PLC & I/O Cards CJ1W-ID211 CJ-Series 16-Point 24 VDC Inp…, CJ1W-OC211 CJ-Series 16-Point Relay Outp…, NX-ID5442 NX-Series 16-Point Digital Inp…

Ordering Omron PLC modules: what we need

Send the complete model number from the front or side label of the unit, including every suffix. If you are replacing a failed card, add the CPU or coupler model it is mounted with, and tell us if the terminal block or connector is needed as well. For obsolete Omron PLC parts we check which successor the manufacturer documents. Requests from other GCC countries are handled the same way.

Facts checked against Omron's published company history, October 2026.

FAQ

Questions about the Omron MY2N-CR-GS AC Relay with Built-In CR Surge

Answers from our engineering team on installation, compatibility and integration.

01What does CR mean in MY2N-CR-GS?
CR means the relay contains a built-in capacitor-resistor circuit across the coil to absorb switching surges on AC coils.
02Which coil voltages are available for MY2N-CR-GS?
The datasheet lists 100/110, 110/120, 200/220 and 220/240 VAC for the CR models.
03Can I use MY2N-CR-GS with a DC coil?
No. The CR type is for AC coils. For DC the datasheet lists diode types, MY2N-D1-GS and MY2N-D2-GS, depending on polarity.
04Does the CR circuit affect release with solid-state outputs?
It can allow leakage current through the coil. The must-release voltage is 30% min. of rated voltage, so release should be checked in the actual circuit.
05Which sockets fit MY2N-CR-GS?