Brand:

KRACHT AS 8 U 230 PUR / F Mixing Ratio Controller

Description

Ratio control from one panel instrument: AS 8 U 230 PUR / F

KRACHT AS 8 U 230 PUR / F is the PUR program of the AS 8 series on a 230 VAC supply. It controls the mixing ratio between a leading component A and a second component B, measuring both with volume counters and displaying flow A, flow B and the ratio A/B.

The function is general: wherever two liquids must be held at a ratio, the instrument compares the measured ratio with the set one and adjusts the output.

Code: AS 8, U (voltage output of up to plus-minus 10 V), 230 (230 V, 50/60 Hz), PUR (flow and ratio control), F (membrane keyboard).

Control principle of AS 8 U 230 PUR / F

The target mixing ratio between the leading component A and component B is set on the AS 8. The volume flows are measured by two volume counters and delivered as square-wave signals. The instrument filters and converts the signals and computes flow A, flow B and the mixing ratio A/B; the datasheet example shows 10 l/min of A, 5 l/min of B and a ratio of 2.000.

The control output goes to a steady valve through a regulating transformer or controls the speed of a transfer pump. Two relay contacts signal when the permissible error tolerances are exceeded, so the process can be stopped if the ratio leaves the tolerance.

A note on dynamics: the instrument adjusts the output continuously, but a slow valve or a long pipe between the dosing point and the counter delays the effect. Place the counter for component B close to the injection point to keep the loop quick, and avoid compressible volumes such as air in the dosing line.

Technical data of AS 8 U 230 PUR / F

Parameter Value
Type code AS 8 U 230 PUR / F
Output signal Voltage, plus-minus 10 V / 0 to 10 V / 2 to 10 V
Supply voltage 230 V AC, 50/60 Hz
Program version PUR flow and mixing ratio control
Keyboard Membrane keyboard (F)
Display 7-segment LED, 13.2 mm, red, 0.000 to 9999 with floating point
Power consumption approx. 3.5 W
Sensor supply 24 VDC plus/minus 20 percent, 50 mA
Relays 2 relay contacts, 24 V / 1 A
Digital inputs 2, input amplitude min up to 9 V, max from 12 V
Counter input frequency 1 Hz to 2500 Hz
Front frame 96 x 48 mm (DIN 43700)
Installation depth approx. 122 mm with connector strip
Panel cut-out 92 x 45 mm
Protection IP 54 with correct panel assembly
Operating temperature 0 to 60 C
Weight approx. 0.4 kg

Where AS 8 U 230 PUR / F sits in the AS 8 family

V2F shows flow and mixing ratio but does not control; VA shows ratio between components; PUR adds the control output. Compared with D2F, which displays only difference, PUR closes a loop. It needs two counters, like D2F, and differs from the single-counter RP program, which controls absolute flow instead of ratio.

This code uses the 230 V supply. If the control cabinet has a 24 VDC rail, the code 24 version avoids a mains connection.

Use cases for AS 8 U 230 PUR / F

Blending of additives into base oil, dosing of hardener into resin, fuel additive injection, and chemical dilution all rely on a stable ratio rather than a stable absolute flow. In a plant where the main flow varies with demand, the ratio controller adjusts the minor component automatically.

For installations in Oman, small blending skids for lubricants and chemical dosing for water treatment are typical, where a dedicated ratio unit is quicker to commission than programming a PLC.

Think of a lube oil blending skid. Base oil is the leading component A at 100 l/min and the additive B must follow at 2 percent. The operator enters the ratio, the leading flow changes with the tank outlet, and the instrument keeps the additive flow proportional. If the additive tank runs empty the ratio drifts outside tolerance and a relay trips the line, so no off-specification batch is produced.

In water treatment the same function holds a chemical dose proportional to water throughput, so the residual stays constant when the plant load changes. The leading component is the water and the chemical is component B.

Selection and installation notes

Choose volume counters whose measuring range covers both flows; a very small second flow needs a small counter, otherwise its pulses become too sparse for stable control. The encoder supply of 24 V at 50 mA feeds both counters directly.

Wire the control output to the valve amplifier or pump drive and set the output range to match. Keep the instrument in a 92 x 45 mm cut-out with 122 mm of depth behind the panel.

Commissioning AS 8 U 230 PUR / F

Enter the pulse constants of both counters, the target ratio and the tolerances, then run with water or the process fluid at low rate and observe whether the ratio settles. Check the relay thresholds by deliberately disturbing the component B flow.

Record the settings and the first stable readings in the commissioning sheet. These numbers become the benchmark for later fault finding, for example when the valve sticks and the ratio needs a long time to settle.

Maintenance and ordering

No maintenance beyond periodic counter checks. Quote the full code AS 8 U 230 PUR / F with quantity, and compare with AS 8 U 24 D2F / F, AS 8 I 24 RP, AS 8 U 230 DOS / F and AS 8 I 24 ZM / F.

Documents and quotation

The datasheet is attached. Send an RFQ naming AS 8 U 230 PUR / F to Seven Star LLC, an independent supplier serving Oman and the GCC and not affiliated with the manufacturer.

Spares and Lifecycle Considerations

For critical service, many plants hold one KRACHT AS 8 U 230 PUR / F as an operational spare rather than waiting for a failure. When you plan spares, look at how many identical flow computers units are installed, how long a replacement would take to arrive, and the cost of an unplanned stop. Store spare units in their original packaging in a dry, temperature-controlled area and record the part number and serial number in your maintenance system. We can quote single units or a small spares package and confirm the lead time for each item in writing.

Other Models in the Kracht As8 Electronics Range

Seven Star LLC supplies models from the Kracht As8 Electronics range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
KRACHT AS 8 I 24 ZM / F Cylinder Stroke Measuring UnitFlow ComputersView details
KRACHT AS 8 U 230 DOS / F Dosing Controller 230 VFlow ComputersView details
KRACHT AS 8 I 24 RP Flow and Speed Controller 24 VDCFlow ComputersView details
KRACHT AS 8 U 24 D2F / F Flow Difference DisplayFlow ComputersView details
KRACHT AS 8 U 230 PUR / F Mixing Ratio ControllerFlow ComputersYou are viewing this model
KRACHT SD 1 R 24 Plug-On Flow Display Square-Wave OutputFlow ComputersView details
Datasheets & Documents
  • PDF Datasheet KRACHT AS 8 U 230 PUR / F Mixing Ratio Controller Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

KRACHT is the German maker of gear pumps, gear flow meters, hydraulic valves, motors and cylinders. The company was entered in the trade register in 1911 as Hillebrand & Kracht OHG and is based in Werdohl, in the Sauerland region of Germany. For most of its history it was a medium-sized family company; in January 2024 it became part of the Atlas Copco Group, in the Power and Flow division.

Seven Star LLC lists KRACHT pumps, flow meters, valves and hydraulic motors, and sources them by type key for machinery and marine users in Oman.

KRACHT company profile

Founded 1911, registered as Hillebrand & Kracht OHG
Headquarters Werdohl, North Rhine-Westphalia, Germany; in today's premises since 1971
Ownership Atlas Copco Group since January 2024 (Power and Flow division, Power Technique business area); previously a family company
Size About 440 employees and revenue of about EUR 72 million in 2022, as reported by Atlas Copco
Subsidiaries USA, China and Hungary (KRACHT Hidraulik Kft.)
Product families External gear pumps for lube oil, fuel and process duty, VC and VZ gear flow meters, pressure and flow control valves, hydraulic motors and cylinders

Milestones

  • 1911: Hillebrand & Kracht OHG is entered in the trade register.
  • 1971: The company moves into its present premises in Werdohl.
  • 1992: A gear manufacturer in Hungary is acquired, today KRACHT Hidraulik Kft.
  • 2023–2024: Atlas Copco agrees to buy KRACHT in December 2023 and completes the deal in January 2024.

KRACHT pumps, flow meters and valves listed

The listing follows four product groups, pumps, fluid measurement, valves and drives:

  • Pump technology: KF gear pumps for transfer of lubricating and other fluids, the KF-F version for fuels, and KP high pressure gear pumps
  • Fluid measurement technology: gear type flow meters such as the VCA in aluminum
  • Valve technology: SPV and SPVF pressure relief valves, the DBD directly controlled poppet valve, HV and HVF pilot operated valves and the DV B hydraulically pilot controlled valve
  • Drive technology: KM hydraulic gear motors

Where KRACHT equipment is used

KRACHT equipment serves the marine, renewable energy, process technology and hydraulics industries. In practice that means lube oil and fuel oil transfer on engines, gearboxes and compressors, oil supply units, and metering of oils, resins, paints and other viscous media with gear flow meters in dosing and test bench systems. Enquiries from the GCC are mostly for a KRACHT pump or valve fitted to an imported machine or a ship's auxiliary system.

KRACHT products we list

Family Examples
Pumps BT / BTH Low-Speed Gear Pump, DT DuroTec Gear Pump for Abrasive Fluids, KD1 Gear Metering Pump, KF 0 Stainless Steel Process Gear Pump, KF Series Modular Gear Pump, KF-F Fuel Gear Pump Series, KF80RF2-D15 Gear Pump, KM Series Hydraulic Gear Motor and 2 more
Flowmeters Fluid Measurement Technology Series, SVC Screw Type Flow Meter, TM Turbine Flow Meter, VC 0.01 Micro Gear Type Flow Meter, VC Gear Type Flow Meter, VCA Aluminum Gear Flow Meter, VCM Gear Flow Meter
Safety Relief Valves DBD Directly Controlled Poppet Valve, DV B Hydraulically Pilot Controlled Valve, HV/HVF Pilot Operated Slide Valve, SPV 10 L1G 1 A 12 Pressure Relief Valve, SPV/SPVF Directly Controlled Slide Valve, Valve Technology Series
Hydraulic Valves & Components CNL Hydraulic Cylinder, DV S Pressure Stage Control Valve
Gear Units & Reducers Drive Technology Series

Ordering KRACHT parts: what we need

KRACHT products carry a type key on the nameplate that encodes size, direction of rotation, shaft end, housing and seal material, connections and special numbers. An example from this page is SPV 10 L1G 1 A 12. Send the complete key and the serial or order number shown with it. If the plate is damaged, send the fluid and viscosity, flow rate, operating pressure and temperature, drive speed, port type and size, and photos with main dimensions. For KRACHT flow meters add the measuring range and the pickup or electronics required. We compare the key with KRACHT documentation and supply the manufacturer's data sheet on request.

Frequently requested KRACHT models: KRACHT Pump Technology Series.

Facts checked against KRACHT company literature and Atlas Copco's acquisition announcements, October 2026.

FAQ

Questions about the KRACHT AS 8 U 230 PUR / F Mixing Ratio Controller

Answers from our engineering team on installation, compatibility and integration.

01What does the PUR program of KRACHT AS 8 U 230 PUR / F do?
It controls the mixing ratio between two components and displays flow A, flow B and the ratio A/B.
02How many counters are needed for AS 8 U 230 PUR / F?
Two volume counters, one for each component, each with a square-wave output.
03What does AS 8 U 230 PUR / F output to the process?
A control output to a steady valve through a regulating transformer, or to the speed of a transfer pump, plus two relays for tolerance alarms.
04What supply does AS 8 U 230 PUR / F use?
It runs from a 230 V AC mains supply at 50/60 Hz and provides a 24 V encoder supply for the two counters.
05How is the ratio set on AS 8 U 230 PUR / F?
Through the three buttons of the membrane keyboard, where the target mixing ratio and tolerances are entered in menus.