Kentec Sigma CP-R K01040M2 4-Zone Fire Alarm Repeater Panel
Description
The Kentec Sigma CP-R K01040M2 is a four-zone repeater panel with its own mains power supply, designed to give remote control and indication for a Sigma CP conventional fire alarm panel. The datasheet DS39 states that it provides full control over the main panel, volt-free fire and fault contacts, and a two-wire serial connection. It carries EN54-2 and EN54-4 marks on the datasheet, matching the Sigma CP range it repeats.
Product overview
The repeater is compatible with all Sigma CP control panels that have operating software version 2.0 or above. Repeaters come with 2, 4 or 8 zones, in mains powered K versions or 24 V powered E versions. A mains powered repeater needs only a two core data cable from the main panel, whereas a 24 V DC version needs two additional cores for power from the main panel or another 24 V DC source. The same datasheet covers the Sigma CP ancillary PCB, which adds open collector zonal fault outputs and volt-free fire, coincidence and common fault contacts.
Repeater functions
- Two-wire serial connection to the main Sigma CP panel.
- Up to seven repeater panels per system.
- 230 V AC or 24 V DC powered versions.
- Full control over the main panel from the repeater.
- Volt-free fire and fault contact outputs.
- Each device is given an address from 1 to 7 with a binary coded DIL switch.
Technical specification
Repeater models from DS39:
| Product code | Description | Supply | Standby current | Alarm current |
|---|---|---|---|---|
| E01020L2 / E01040L2 / E01080L2 | 2 / 4 / 8 zone repeater | 24 V DC | 0.075 A | 0.094 / 0.098 / 0.11 A |
| K01020M2 | 2 zone repeater with PSU | 230 V AC | 0.075 A | 0.094 A |
| K01040M2 | 4 zone repeater with PSU | 230 V AC | 0.075 A | 0.098 A |
| K01080M2 | 8 zone repeater with PSU | 230 V AC | 0.075 A | 0.11 A |
| Parameter | Specification |
|---|---|
| Size | 385 x 310 x 60 mm; weight 6 kg |
| Construction | 1.2 mm mild sheet steel, epoxy powder coated; IP30 |
| Supply voltage | K models 230 V AC (+10 percent / -15 percent); E models 20 to 30 V AC |
| Mains fuse | 1.6 A 250 V |
| Power supply DC rating | 24 V, 1 A |
| Maximum battery size | 7 Ah 12 V, two per panel (datasheet); manual specifies 2.3 Ah minimum |
| Fault and fire contact ratings | 30 V DC, 1 A each |
| Cable capacity | 2.5 mm2 per terminal |
| Data cable length | Maximum 1200 m from the main panel to the last repeater |
| Operating temperature | -5 to +40 degrees C |
| Operating humidity | Below 95 percent, non-condensing |
| Manual: mains consumption | 230 V AC +10 / -15 percent, 30 W maximum |
| Manual: battery charge | 27.6 V DC nominal, 0.6 A maximum; fuse 3.15 A |
Choosing a repeater
Pick the zone count to match the main panel: 2, 4 or 8 zones. Then choose between the K version, which has its own mains supply, and the E version, which is powered at 24 V. K01040M2 is the four-zone repeater with PSU. A mixture of repeaters, ancillary boards or sounder boards, to a maximum of seven of each type, can be connected to one control panel.
Installation notes
The total length of the data cable from the main panel to the last repeater must not exceed 1200 metres. Man-1093 (issue 06, May 2016) describes connecting the repeater to the main panel and to other repeaters, the 24 V input and the relay contacts, and the panel operation, watchdog reset and troubleshooting indications.
Typical applications
Reception areas, security rooms, building entrances or separate wings where staff need to see zone status and silence, reset or test the system without walking to the main panel.
Selection and installation notes
A fire alarm control panel is selected from the number of loops or zones, the devices to be connected, the standby battery duration and the standard the project requires. It must be designed, installed, programmed and commissioned by competent fire system engineers to the code and authority rules for the project, with a cause and effect plan, correct battery sizing, cable of the specified type and a full test of every device and output before handover. Confirm the certification needed for the project with the authority before purchase.
A repeater panel is connected to its parent panel by the data cable the maker specifies, so check the cable type, the length limit and the addressing before installation.
Information needed for a quotation
Send the full model code, the quantity, the delivery location in Oman or the GCC, the intended use and any accessories needed, so that the complete package can be quoted together.
Documents and supply information
The manufacturer data sheet is attached to this page and should be read together with the project specification and the site risk assessment before a purchase is confirmed. Ratings, standards and dimensions are quoted as printed on that sheet. Lead time, stock position and certificates available with the shipment are confirmed in the quotation, and we supply to Oman and the wider GCC region for industrial, utility and building services projects.
Related Kentec products: Kentec Sigma CP K11040M2 4-Zone Conventional Fire Alarm Panel, Kentec Sigma XT+ K21042M3 4-Zone 2-Area Extinguishant Panel, Kentec Sigma A-CP K1844-11 4-Zone UL864 Conventional Fire Panel, Kentec Sigma A-XT K1810-13 UL/FM Extinguishant Releasing Panel, Kentec Sigma ZXT K192311XM2 Single-Area Extinguishant Panel and Kentec Syncro ASM MA80162M2 Marine Fire Panel, 2 Loop.
Documents and quotation
You will find the datasheet and the repeater manual on this page. Seven Star LLC is an independent supplier located in Muscat. Pair it with a main panel from the fire alarm panels in the Logic Controllers category and tell us the zone count and supply type for pricing.
Datasheets & Documents
Reviews (0)
How would you rate this product? Cancel reply
About brand
Kentec Electronics is a British manufacturer of fire alarm and extinguishant control panels, founded in 1985 in Kent and headquartered in Dartford. It began by assembling its first panel in a converted shed to give independent installers an alternative to the large manufacturers. Kentec exports to more than 80 countries and received the King's Award for Enterprise in International Trade in 2026.
Seven Star LLC is an independent supplier in Muscat. We list Kentec panels with the manufacturer datasheet and manual on each page, for fire alarm contractors and facilities in Oman and the GCC.
Kentec company profile
| Founded | 1985, Kent, England |
|---|---|
| Headquarters | Dartford, Kent |
| Exports | More than 80 countries |
| Approvals | EN 54 and UL/FM listed panels |
| Product families | Sigma conventional fire panels, Sigma XT and ZXT extinguishant release panels, Syncro AS addressable fire panels, Syncro XT+ extinguishant panels, UL864 panels, repeaters and marine panels |
Milestones
- 1985: Kentec builds its first panel in Kent.
- 2026: Kentec receives the King's Award for International Trade.
Kentec product series
Fire alarm panels include the Syncro AS two-loop addressable panel, the Syncro ASM marine version, the Sigma CP four-zone conventional panel with the Sigma CP-R repeater, and the UL864 listed Sigma A-CP conventional panel.
Extinguishant control panels include the Sigma XT+ four-zone two-area panel, the Syncro XT+, the single-area Sigma ZXT and the UL/FM Sigma A-XT releasing panel, and the Sigma Si is a six-lamp extinguishant status unit for doors of protected rooms. Datasheets state the standards by model, such as EN 54-2, EN 54-4, EN 12094-1 and UL864.
Where Kentec panels are used
Fire alarm systems in commercial and industrial buildings, and gas suppression release for server rooms, control rooms, switchgear rooms and archives, as well as marine installations.
Kentec products we list
Ordering Kentec panels: what we need
Send the Kentec part number, the number of loops or zones, the detector protocol for addressable panels, the extinguishing agent and number of areas for release panels, and the standard (EN or UL) required.
Facts checked against Kentec's catalogues and the 2026 King's Awards profile, October 2026.
Browse Kentec products by category: Logic Controllers.
Related products
Frequently Asked Questions
Sigma CP control panels with operating software version 2.0 or above.
Up to seven repeaters per system. A mix of repeaters, ancillary boards and sounder boards can be fitted, up to seven of each type.
The total length from the main panel to the last repeater must not exceed 1200 metres.
K models are mains powered (230 V AC) and E models are 24 V powered, needing two extra cores for power.
Fault and fire contacts are rated 30 V DC, 1 A each.