Brand:

Pepperl+Fuchs KFD2-STC5-Ex1.H High Voltage Supply

Description

KFD2-STC5-Ex1.H: higher voltage for demanding transmitters

Some SMART transmitters, especially older analyser heads, flow meters with heaters or devices with long cable runs, need more voltage than a standard supply provides. The Pepperl+Fuchs KFD2-STC5-Ex1.H raises the available field voltage to 17 V DC at 20 mA and 21 V at 4 mA (24 V open circuit), against 16 V and 20 V for the standard model.

In every other respect it is a one-channel barrier with a 4 to 20 mA output that can be configured as sink or source on the safe side.

Selected features

  • High field voltage 17 V DC at 20 mA
  • Output 4 to 20 mA into 0 to 800 ohm; overload above 25 mA
  • If the external supply is above 19 V, a load of at least (V minus 19) divided by 0.02 ohm is required, and the internal 250 ohm resistor at terminal 9 may serve as that load
  • HART, BRAIN and Foxboro supported
  • Extended ambient range up to 70 degrees C under the mounting conditions described in the manual

KFD2-STC5-Ex1.H figures

Parameter Value
Supply 18 to 30 V DC, up to 1 W dissipation, up to 1.6 W consumption
Input 4 to 20 mA, terminals 1+, 2-, 3
Open-circuit voltage / short-circuit current 24 V / 25 mA
Available voltage 17 V at 20 mA, 21 V at 4 mA
Output 4 to 20 mA sink or source, 0 to 800 ohm
Settling time 500 microseconds
Safe-side values Uo 27.2 V, Io 93 mA, Po 633 mW
Certificate CML 17 ATEX 2029X
Ambient -20 to 60 degrees C (up to 70 degrees C with mounting conditions)
Dimensions, mass 20 x 124 x 115 mm, about 200 g

Deciding whether you need the H version

Add up the minimum operating voltage of the transmitter and the voltage drop of the cable at 20 mA. A transmitter that needs 15.5 V and sits on a 100 ohm cable loop (2 V drop) would be at the edge with a supply that delivers 16 V, but gets 1.5 V of margin with 17 V. In practice the H variant is the safe pick when the transmitter datasheet quotes a minimum of 15 V or more, or when a hazardous-area junction box adds protective components in series.

KFD2-STC5-Ex1.H compared with other versions

Against KFD2-STC5-Ex1 the available voltage is 1 V higher and the open-circuit voltage 24 V instead of 23 V, but settling slows from 200 to 500 microseconds and the normal ambient limit drops from 70 to 60 degrees C. Against KFD2-STC5-Ex1.2O it keeps a single output and a load limit of 0 to 800 ohm.

Installation

The wiring diagram mirrors the standard STC5. Use the sink or source terminals according to the control system and add the series resistor if the external voltage exceeds 19 V. Fit to a 35 mm rail or Power Rail, observing the spacing that permits the 70 degrees C operation described in the manual.

Upkeep

Check transmitter voltage at the field terminals with a loop at 20 mA and confirm that it exceeds the device minimum. Document the result.

Selection summary

Choose this variant for demanding transmitters; select the standard type for speed and the widest temperature range.

Voltage budget example

Consider a transmitter that needs at least 16.5 V at the terminals and sits at the end of 800 m of cable with 0.1 ohm per metre per conductor, giving 160 ohm of loop resistance. At 20 mA the cable drops 3.2 V, so the barrier must offer at least 19.7 V at its field terminals. The H version supplies 17 V at 20 mA in the datasheet, so a shorter cable or a transmitter with a lower minimum voltage is still necessary; the example shows why the budget has to be calculated and not guessed. Larger conductors or a transmitter local to the junction box restore the margin.

Mounting for the extended temperature range

The datasheet states that operation up to 70 degrees C is possible, but only when the mounting conditions in the manual are observed, typically meaning spacing between devices and the use of a specific orientation. In an Omani coastal cabinet with high humidity and sun load, assume the standard 60 degrees C limit unless the cabinet temperature is measured and proven. Mounting each module on a DIN rail with free air at the sides reduces self-heating from the roughly 1 W dissipation. Mixed rows with high-dissipation power supplies are best avoided.

Questions buyers ask about KFD2-STC5-Ex1.H

What field voltage does KFD2-STC5-Ex1.H deliver? It provides at least 17 V at 20 mA and 21 V at 4 mA on terminals 1+ and 3, with a 24 V open-circuit voltage.

When is a series resistor needed with KFD2-STC5-Ex1.H? If the external voltage is above 19 V, a load of at least (V minus 19) divided by 0.02 ohm is required, and the internal 250 ohm resistor can be used.

What is the settling time of KFD2-STC5-Ex1.H? The settling time is 500 microseconds, slower than the 200 microseconds of the standard STC5 model.

What ambient temperature applies to KFD2-STC5-Ex1.H? The standard range is -20 to 60 degrees C, with an extended range up to 70 degrees C under mounting conditions in the manual.

What output load can KFD2-STC5-Ex1.H drive? The load range is 0 to 800 ohm with overload above 25 mA.

Documents and quotation

The manufacturer datasheet for KFD2-STC5-Ex1.H accompanies this listing as a PDF so your engineers can verify terminals, ratings and approvals before purchase. Quote the transmitter minimum voltage with your request. To request a quotation, send the RFQ with the exact part number KFD2-STC5-Ex1.H, the quantity, the delivery location in Oman or the GCC and any project reference. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer.

Datasheets & Documents
  • PDF Datasheet Pepperl+Fuchs KFD2-STC5-Ex1.H High Voltage Supply Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Pepperl+Fuchs is a German manufacturer of industrial sensors and explosion protection equipment, founded in 1945 in Mannheim by Walter Pepperl and Ludwig Fuchs as a radio repair shop. Defective transformers led them into manufacturing, and the company developed its first proximity switch in the late 1950s. Pepperl+Fuchs is headquartered in Mannheim and is a pioneer of intrinsically safe electrical equipment for hazardous areas.

Seven Star LLC lists Pepperl+Fuchs sensors, isolated barriers, power supplies and hazardous-area mobile devices, and supplies them to instrument and automation teams in Oman by exact model designation.

Pepperl+Fuchs company profile

Founded 1945, Mannheim-Sandhofen, Germany, by Walter Pepperl and Ludwig Fuchs
Headquarters Mannheim, Germany
Ownership Privately owned (Pepperl+Fuchs SE)
Origins Radio repair workshop that began making replacement transformers
Product families Inductive, capacitive, ultrasonic and photoelectric sensors, rotary encoders, R2000 LiDAR scanners, KFD and HiC isolated barriers, Zener barriers, remote I/O, purge and pressurization systems, Ex-rated enclosures

Milestones

  • 1945: Walter Pepperl and Ludwig Fuchs open their radio repair shop in Mannheim.
  • 1958: The first proximity switch is developed (some company sources say 1959).

Pepperl+Fuchs product families on this page

On the interface side there are two systems. The K-System mounts on DIN rail and is represented here by the KFD2-UT2-Ex2 universal temperature converter. The H-System plugs into termination boards and is represented by the HiD2030 SMART transmitter power supply with HART. The PS1000-A6-24.20 is a 24 VDC, 20 A power supply for cabinets. Sensors listed include the NJ2-12GK-SN NAMUR inductive sensor, the R101 retro-reflective photoelectric sensor and the R2000 2-D LiDAR scanner. For field staff there are the Tab-Ex 05 DZ1 tablet for Zone 1/21 areas and the Smart-Ex 03 DZ2 smartphone for Zone 2/22 and Division 2 areas.

Where Pepperl+Fuchs equipment is used

Isolated barriers sit between field instruments in Zone 0 or Zone 1 and the DCS or safety system in refineries, gas plants and chemical works. NAMUR sensors report valve position and machine states in classified areas. Photoelectric sensors and LiDAR scanners work in conveying, packaging, warehousing and vehicle guidance. Ex-rated tablets and phones are carried on operator rounds and maintenance jobs.

Pepperl+Fuchs products we list

Family Examples
Isolator & Barrier HiD2030 SMART Transmitter Power Supply w…, KFD2-SR2-Ex2.W K-System Isolated Switch…, KFD2-UT2-Ex2 Universal Temperature Conve…
Industrial Computers Tab-Ex 05 DZ1 WWAN Hazardous Area Tablet, Smart-Ex® 03 DZ2 smartphone for Zone 2/2…
Inductive Proximity Sensors NJ2-12GK-SN NAMUR Inductive Sensor
Power Modules PS1000-A6-24.20 Power Supply 24 VDC 20 A
Photoelectric Sensors R101 Retro-Reflective Photoelectric Sensor
Laser Distance, LiDAR & Radar Sensors R2000 2-D LiDAR Laser Scanner

Ordering Pepperl+Fuchs parts: what we need

Send the complete model designation as printed on the device, including every suffix; a single letter can change the supply voltage or the output type. Add the part number if the label shows one. For barriers, tell us the field device and signal type, the number of channels and whether the safety loop needs a SIL-assessed module. For mobile devices, state the zone or division and the regional radio version.

Facts checked against Pepperl+Fuchs's own chronicle pages, October 2026.

FAQ

Questions about the Pepperl+Fuchs KFD2-STC5-Ex1.H High Voltage Supply

Answers from our engineering team on installation, compatibility and integration.

01What field voltage does KFD2-STC5-Ex1.H deliver?
It provides at least 17 V at 20 mA and 21 V at 4 mA on terminals 1+ and 3, with a 24 V open-circuit voltage.
02When is a series resistor needed with KFD2-STC5-Ex1.H?
If the external voltage is above 19 V, a load of at least (V minus 19) divided by 0.02 ohm is required, and the internal 250 ohm resistor can be used.
03What is the settling time of KFD2-STC5-Ex1.H?
The settling time is 500 microseconds, slower than the 200 microseconds of the standard STC5 model.
04What ambient temperature applies to KFD2-STC5-Ex1.H?
The standard range is -20 to 60 degrees C, with an extended range up to 70 degrees C under mounting conditions in the manual.
05What output load can KFD2-STC5-Ex1.H drive?
The load range is 0 to 800 ohm with overload above 25 mA.