Brand: Moore Industries
SLA/6PRG/4PRG/10-30DC/-3AO [DIN] Safety Logic Solver
Description
Moore SLA/6PRG/4PRG/10-30DC/-3AO [DIN] overview
The Moore SLA/6PRG/4PRG/10-30DC/-3AO [DIN] is a multiloop safety logic solver and alarm from the Moore Industries functional safety series. The manufacturer describes it as exida certified and SIL 2/3 capable, acting on hazardous process conditions, warning of unwanted parameters, performing on/off control and providing emergency shutdown in safety instrumented systems and traditional alarm trip applications.
It is programmed through FDT/DTM and accepts up to four discrete and six analog inputs. The -3AO option adds three analog outputs, and the Ethernet port supports MIIP (DTM), HTTP and Modbus/TCP.
The part number SLA/6PRG/4PRG/10-30DC/-3AO [DIN] follows the ordering pattern of the manufacturer datasheet, which lists the fields in this order: unit, input, output, power, options and housing (Unit / Input / Output / Power / Options [Housing]). The string written as SLA/6PRG/4PRG/10-30DC/-3AO [DIN] is the model example printed in that datasheet, so it describes one complete configuration. If your plant needs a different input, output, supply, option or housing, send the configuration with your RFQ and it will be checked against the ordering table.
- SLA: SIL 2/3 capable programmable safety logic solver and alarm
- 6PRG: six programmable analog inputs (mA, V, RTD, T/C, ohm, mV, potentiometer)
- 4PRG: four SPDT relays
- 10-30DC: dc power supply option
- -3AO: three isolated, linearised analog outputs
- [DIN]: DIN-style housing for 35 mm Top Hat rail
Key features of the Moore Industries SLA/6PRG/4PRG/10-30DC/-3AO [DIN]
- Up to six analog inputs on three dual-input isolated channels with failover.
- Four discrete channels configurable as failsafe or non-failsafe input or output.
- Four process relays; the fourth is jumper-selectable as a fault relay.
- Alarm voting, latching, suppression, delay and startup delay of 0 to 120 seconds.
- 10/100Base-T Ethernet with Modbus/TCP, HTTP and MIIP (DTM).
- Three isolated analog outputs (-3AO).
Technical specifications for SLA/6PRG/4PRG/10-30DC/-3AO [DIN]
| Parameter | Value |
|---|---|
| Model string | Moore SLA/6PRG/4PRG/10-30DC/-3AO [DIN] |
| Analog input channels | Three dual-input isolated channels, switch-selectable for HLPRG (mA/V) or TPRG (RTD, T/C, ohm, mV, potentiometer) |
| Reference junction compensation accuracy | plus or minus 0.45 degrees C |
| Discrete I/O | Four non-isolated channels; input contact closure 26 Vdc (Voc), 5 mA (Isc); output 30 Vdc, 120 mA maximum sink |
| Relays | Four SPDT relays, 1 form C, 3 A at 250 Vac or 3 A at 30 Vdc, 50/60 Hz, non-inductive |
| Trip response time (typical) | TPRG one sensor per channel 750 ms; HLPRG one sensor per channel 450 ms |
| Ethernet | 10/100Base-T, RJ-45, auto negotiation, auto MDIX, DHCP or fixed IP |
| Power supply effect | plus or minus 0.002% of span per 1% line voltage change |
The values above come from the manufacturer datasheet for the SLA family. Specifications can differ by input type and option, so read the matching page of the datasheet before finalising a purchase specification and keep the complete model string on your purchase documents. Where a value is not listed here it was not stated clearly enough in the datasheet to repeat.
Typical applications of the SLA/6PRG/4PRG/10-30DC/-3AO [DIN] in Oman and the GCC
With six analog inputs and four relays, one SLA can replace several single-loop trip alarms on a skid or in a safety panel.
In oil and gas facilities across Oman and the GCC, a programmable alarm trip such as the SLA/6PRG/4PRG/10-30DC/-3AO [DIN] is used as a stand-alone high or low limit device on temperature, pressure, level and flow signals. It can drive a shutdown relay, a horn or beacon, or a lamp on a local annunciator without loading the main control system.
Power utilities and desalination and water plants use alarm trips to protect motors, pumps and heat exchangers: for example a winding or bearing temperature limit, a tank level limit, or a discharge pressure limit that must act even when the DCS is offline. Manufacturing and process plants use the same idea for batch limits, furnace over-temperature cut-outs and dosing interlocks.
Because the SLA/6PRG/4PRG/10-30DC/-3AO [DIN] sets up from its front panel or from PC software, one unit stocked in the store room can cover many different duties, which is helpful for remote sites where spare lead times matter.
Selection and compatibility notes for SLA/6PRG/4PRG/10-30DC/-3AO [DIN]
Safety use needs a documented SIL assessment. A and B inputs on each channel share a common ground; only the three channels are isolated from each other.
Confirm the input type first. The SLA family has different model strings for current and voltage inputs and for temperature and resistance inputs, so the input field of the part number must match the sensor or transmitter you are wiring.
Check the relay contact rating against the load you intend to switch. The relays are rated for the values shown in the specifications table; for inductive loads such as contactor coils or solenoids, use an interposing relay or suppression as your plant standard requires.
Decide whether the unit is a replacement or a new installation. For replacements, compare the supply range, relay count, analog output option and housing against the nameplate of the unit being removed. Send the old nameplate details together with your RFQ and we will compare them with the datasheet ordering table.
Installation and commissioning
Mount the SLA/6PRG/4PRG/10-30DC/-3AO [DIN] on its rail or bracket in a clean, ventilated panel, away from heavy switchgear and power cables where possible. Leave room for the front-panel buttons and for the viewing angle of the display.
Wire the supply, input and relay terminals according to the terminal drawing in the manufacturer manual. Use the wire size range given in that manual and tighten terminals to the stated torque. Keep the input cable separate from relay and power cabling and use shielded cable on long sensor or signal runs.
On power-up, set the input type and range, assign each relay to a high or low trip with its trip point and dead band, choose normally open or closed and failsafe behaviour, and set any trip delay. Test every relay by moving the input signal through the trip point, and record the final settings and password in your commissioning file.
Maintenance and spares
Alarm trips are low-maintenance devices, but a safety or shutdown duty deserves a documented proof-test. Plan a periodic functional check of each relay by simulating the input at and beyond the trip points, and verify that the downstream shutdown or alarm action really occurs.
Check terminals for tightness and corrosion during planned outages, keep the front window and vents free of dust, and record the as-found and as-left settings. If a unit is replaced, load the saved configuration or re-enter the recorded settings and repeat the functional test before returning the loop to service.
Related products and ordering notes
Single-loop safety trip alarms in the same series include the STA. The datasheet is available on request.
Unit and accessory part numbers such as those named above are separate line items. Please list each one with its quantity so that the quotation covers the complete package. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer.
Frequently asked questions about SLA/6PRG/4PRG/10-30DC/-3AO [DIN]
- What is the SLA/6PRG/4PRG/10-30DC/-3AO [DIN]? A multiloop SIL 2/3 capable safety logic solver and alarm with up to six analog and four discrete inputs.
- How many relays does the SLA/6PRG/4PRG/10-30DC/-3AO [DIN] have? Four SPDT process relays; the fourth can be jumper-selected as the fault relay.
- What communications does the SLA/6PRG/4PRG/10-30DC/-3AO [DIN] offer? 10/100Base-T Ethernet supporting MIIP (DTM), HTTP and Modbus/TCP.
- What does -3AO add on the SLA/6PRG/4PRG/10-30DC/-3AO [DIN]? Three isolated and linearised analog outputs.
- How do I order the SLA/6PRG/4PRG/10-30DC/-3AO [DIN]? Send an RFQ with the part number, quantity and delivery location in Oman or the GCC.
Documents and quotation
The manufacturer datasheet for the SLA family is available from us on request and a copy is attached to this page. It contains the full ordering table, specifications and dimension drawings, and we suggest reading it before you decide on the final configuration.
To request a quotation, send an RFQ that includes the part number SLA/6PRG/4PRG/10-30DC/-3AO [DIN], the quantity, the delivery location in Oman or the GCC and any special requirement such as certification documents or a required delivery date. Our team will confirm availability and lead time and reply with a written offer.
Datasheets & Documents
- Datasheet SLA SIL 2/3 Capable Safety Logic Solver and Alarm Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Moore Industries is an American manufacturer of signal interface instruments, founded in 1968 by engineer Leonard W. Moore in North Hills, California. Its first product was the SCT signal converter, built in a friend's workshop. The company has been at its North Hills headquarters since 1974 and still designs and builds its products there, known for rugged aluminium housings.
Seven Star LLC, an independent supplier in Oman, lists Moore Industries temperature transmitters, limit alarm trips, isolators and a PID backup controller, and sources units and replacements by full model number.
Moore Industries company profile
| Founded | 1968, North Hills, California, USA, by Leonard W. Moore |
|---|---|
| Headquarters | North Hills, California, since 1974 |
| Ownership | Privately owned (Moore Industries-International, Inc.) |
| First product | SCT signal converter |
| Product families | Signal isolators and converters (ECT, SCT), temperature transmitters (TRY, THZ), alarm trip units (SPA), miniMOORE multichannel signal conditioners, HART interfaces, SIL-rated safety logic solvers (STA) |
Milestones
- 1968: Leonard W. Moore founds the company and builds the first SCT signal converter.
- 1974: The company moves into its North Hills headquarters.
- 2009: miniMOORE wins a Control Engineering Engineers' Choice Award.
Moore Industries product families on this page
The manufacturer's catalog is arranged by function, and many of the items listed here map onto it directly:
- Temperature transmitters: the TRX, and the STZ functional safety dual input smart HART transmitter
- Alarm trips: the SPA2 programmable limit alarm trip, including an SPA2 with HLPRG input and four relay outputs
- Signal isolators, repeaters and converters: the SIX
- PID controllers and backup stations: the 535 in 1/4 DIN format
Other catalog groups include temperature assemblies and sensors, I/P and P/I converters, remote I/O, HART gateways and interfaces, indicators, and fieldbus device couplers.
Where Moore Industries instruments are used
These are control room and marshalling cabinet devices, plus field-mounted transmitters. Typical jobs are isolating a 4-20 mA loop between two systems, converting a thermocouple or RTD signal for a DCS input, adding an independent high or low trip next to the control system, and keeping a control loop running on a backup station when the main controller is out of service. Process plants in oil and gas, chemicals and power across the GCC use them for exactly these tasks.
Moore Industries products we list
Ordering Moore Industries instruments: what we need
Moore Industries model numbers are built from fields separated by slashes: unit, input, output, power and options, followed by the housing code in brackets. Every field matters. Send the complete string from the label, the serial number, and for programmable units the input type and range you want set. State any hazardous area or functional safety requirement, because approved versions are ordered with their own option codes.
Facts checked against trade press obituaries of Leonard W. Moore (Control Engineering, Control Global), October 2026.
Browse Moore Industries products by category: Temperature Instrumentation, Controllers & Data Acquisition, Isolator & Barrier.
FAQ
Questions about the SLA/6PRG/4PRG/10-30DC/-3AO [DIN] Safety Logic Solver
Answers from our engineering team on installation, compatibility and integration.
01What is the SLA/6PRG/4PRG/10-30DC/-3AO [DIN]?
A multiloop SIL 2/3 capable safety logic solver and alarm with up to six analog and four discrete inputs.
02How many relays does the SLA/6PRG/4PRG/10-30DC/-3AO [DIN] have?
Four SPDT process relays; the fourth can be jumper-selected as the fault relay.
03What communications does the SLA/6PRG/4PRG/10-30DC/-3AO [DIN] offer?
10/100Base-T Ethernet supporting MIIP (DTM), HTTP and Modbus/TCP.
04What does -3AO add on the SLA/6PRG/4PRG/10-30DC/-3AO [DIN]?
Three isolated and linearised analog outputs.
05How do I order the SLA/6PRG/4PRG/10-30DC/-3AO [DIN]?
Send an RFQ with the part number, quantity and delivery location in Oman or the GCC.