Brand: Moore Industries
STA/TPRG/3PRG/U/-AO [DIN] Safety Trip Alarm
Description
Moore STA/TPRG/3PRG/U/-AO [DIN] overview
The Moore STA/TPRG/3PRG/U/-AO [DIN] is the temperature-input version of the STA programmable safety trip alarm from Moore Industries. The manufacturer places the STA in its functional safety series and states that it is certified by exida to IEC 61508:2010 for systematic integrity up to SIL 3 and random integrity up to SIL 2, which means single use in safety instrumented systems up to SIL 2 and use in redundant architectures such as 1oo2 and 2oo3 up to SIL 3.
It accepts an RTD or thermocouple directly, as well as ohms, millivolt and potentiometer signals, and acts on them with two configurable process alarms plus one input or instrument fault alarm. The -AO option adds an isolated analog retransmission of the input.
The unit is line-powered and fits a metal, RFI and EMI resistant DIN-style housing with a display. Buyers typically search for this exact string when they need a safety-rated temperature trip for a shutdown loop or a like-for-like replacement of an installed STA.
The part number STA/TPRG/3PRG/U/-AO [DIN] follows the ordering pattern of the manufacturer datasheet, which lists the fields in this order: unit, input, output, power, options and housing (Unit / Input / Output / Power / Options [Housing]). The string written as STA/TPRG/3PRG/U/-AO [DIN] is the model example printed in that datasheet, so it describes one complete configuration. If your plant needs a different input, output, supply, option or housing, send the configuration with your RFQ and it will be checked against the ordering table.
- STA: SIL 2 and SIL 3 capable programmable safety trip alarm
- TPRG: programmable temperature input: RTD, thermocouple, ohms, millivolt or potentiometer
- 3PRG: two process relays and one fault relay
- U: universal power input, 21.6 to 375 Vdc or 90 to 260 Vac
- -AO: isolated, linearised analog output option
- [DIN]: DIN-style housing for 35 mm Top Hat rail
Key features of the Moore Industries STA/TPRG/3PRG/U/-AO [DIN]
- exida certified to IEC 61508:2010: systematic integrity to SIL 3, random integrity to SIL 2.
- Two programmable process alarms (high or low, normally open or closed, failsafe) plus a third relay used as an input or instrument fault alarm.
- 20-bit input resolution with long-term stability and, according to the datasheet, up to 5 years between scheduled calibrations.
- Direct RTD (2-, 3- and 4-wire) and thermocouple inputs, plus ohms, millivolt and potentiometer inputs, with metal terminal blocks that support reference junction compensation.
- Front-panel pushbutton setup with password protection, or PC configuration software through a serial or USB cable.
- Alarm trip delay programmable from 0 to 120 seconds (0 to 60 seconds for firmware 1.1.2 and earlier).
- Backlit alphanumeric LCD of 2 x 5 14-segment characters and status LEDs for ready, input, alarm and fault.
- Optional isolated analog output that is user-scalable and can be set to drive upscale, downscale or hold last value on input failure.
Technical specifications for STA/TPRG/3PRG/U/-AO [DIN]
| Parameter | Value |
|---|---|
| Model string | Moore STA/TPRG/3PRG/U/-AO [DIN] |
| Input types | RTD (2-, 3-, 4-wire; platinum, copper, nickel), thermocouple J, K, E, T, R, S, N, C, B, ohms 0 to 4000, millivolt -50 to +1000 mV, potentiometer up to 4000 ohms |
| Reference junction compensation accuracy (T/C) | plus or minus 0.45 degrees C |
| RTD and ohms excitation current | 250 microamps, plus or minus 10% |
| T/C and mV input resistance | 40 Mohm nominal |
| Input over-range protection | plus or minus 5 Vdc maximum |
| Outputs | Two process relays and one fault relay, SPDT, 3 A at 250 Vac 50/60 Hz or 3 A at 30 Vdc, non-inductive |
| Analog output (-AO) | Current 0 to 21.6 mA (minimum span 4 mA) or voltage -0.2 to 10.5 V (minimum span 1 V); accuracy plus or minus 0.01% of maximum span |
| Trip response time | 256 ms maximum from input step to alarm change |
| Alarm trip delay | 0 to 120 seconds programmable |
| Power supply | Universal 21.6 to 375 Vdc or 90 to 260 Vac; 5 W maximum |
| Isolation | 500 Vrms between case, input, output and power |
| Dielectric strength | 1966 Vdc for 2 seconds |
| Operating temperature | -40 to +85 degrees C (-40 to +185 degrees F) |
| Relative humidity | 5 to 95%, non-condensing |
| Display | LCD 2 x 5 alphanumeric characters, backlit, range -99999 to 99999 |
| Weight | 513 g to 564 g (18.1 oz to 19.9 oz) |
The values above come from the manufacturer datasheet for the STA family. Specifications can differ by input type and option, so read the matching page of the datasheet before finalising a purchase specification and keep the complete model string on your purchase documents. Where a value is not listed here it was not stated clearly enough in the datasheet to repeat.
Typical applications of the STA/TPRG/3PRG/U/-AO [DIN] in Oman and the GCC
The SIL capability makes this STA a candidate for emergency shutdown duty on temperature signals, such as high-high temperature on a furnace, reactor, compressor bearing or heat-transfer fluid loop, where a certified logic solver is needed in a safety instrumented function.
In oil and gas facilities across Oman and the GCC, a programmable alarm trip such as the STA/TPRG/3PRG/U/-AO [DIN] is used as a stand-alone high or low limit device on temperature, pressure, level and flow signals. It can drive a shutdown relay, a horn or beacon, or a lamp on a local annunciator without loading the main control system.
Power utilities and desalination and water plants use alarm trips to protect motors, pumps and heat exchangers: for example a winding or bearing temperature limit, a tank level limit, or a discharge pressure limit that must act even when the DCS is offline. Manufacturing and process plants use the same idea for batch limits, furnace over-temperature cut-outs and dosing interlocks.
Because the STA/TPRG/3PRG/U/-AO [DIN] sets up from its front panel or from PC software, one unit stocked in the store room can cover many different duties, which is helpful for remote sites where spare lead times matter.
Selection and compatibility notes for STA/TPRG/3PRG/U/-AO [DIN]
A safety function needs a safety review. The datasheet states the integrity levels and offers FMEDA data on request, but the responsible functional safety practitioner must decide if the STA meets the required SIL for each loop, including proof-test interval, architecture and diagnostics.
The datasheet notes that the 24 Vdc and UAC power supply options are no longer available for purchase, so the universal power range is the one to specify.
Confirm the input type first. The STA family has different model strings for current and voltage inputs and for temperature and resistance inputs, so the input field of the part number must match the sensor or transmitter you are wiring.
Check the relay contact rating against the load you intend to switch. The relays are rated for the values shown in the specifications table; for inductive loads such as contactor coils or solenoids, use an interposing relay or suppression as your plant standard requires.
Decide whether the unit is a replacement or a new installation. For replacements, compare the supply range, relay count, analog output option and housing against the nameplate of the unit being removed. Send the old nameplate details together with your RFQ and we will compare them with the datasheet ordering table.
Installation and commissioning
Mount the STA/TPRG/3PRG/U/-AO [DIN] on its rail or bracket in a clean, ventilated panel, away from heavy switchgear and power cables where possible. Leave room for the front-panel buttons and for the viewing angle of the display.
Wire the supply, input and relay terminals according to the terminal drawing in the manufacturer manual. Use the wire size range given in that manual and tighten terminals to the stated torque. Keep the input cable separate from relay and power cabling and use shielded cable on long sensor or signal runs.
On power-up, set the input type and range, assign each relay to a high or low trip with its trip point and dead band, choose normally open or closed and failsafe behaviour, and set any trip delay. Test every relay by moving the input signal through the trip point, and record the final settings and password in your commissioning file.
Maintenance and spares
Alarm trips are low-maintenance devices, but a safety or shutdown duty deserves a documented proof-test. Plan a periodic functional check of each relay by simulating the input at and beyond the trip points, and verify that the downstream shutdown or alarm action really occurs.
Check terminals for tightness and corrosion during planned outages, keep the front window and vents free of dust, and record the as-found and as-left settings. If a unit is replaced, load the saved configuration or re-enter the recorded settings and repeat the functional test before returning the loop to service.
Related products and ordering notes
Related Moore Industries items printed in the STA datasheet include the FMEDA report (part number 700-702-32, one copy provided free with each order on request), the Intelligent PC Configuration Software (750-75E05-01, one copy provided with each order), the serial configuration cable (803-053-26) and a fuse-protected non-isolated USB cable (804-030-26). For mA or voltage inputs, the HLPRG version of the same family is the alternative.
If the DIN housing does not match your panel, the datasheet also lists an FLB flange bracket option for high-vibration mounting.
Unit and accessory part numbers such as those named above are separate line items. Please list each one with its quantity so that the quotation covers the complete package. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer.
Frequently asked questions about STA/TPRG/3PRG/U/-AO [DIN]
- What does the STA/TPRG/3PRG/U/-AO [DIN] do? It is a line-powered safety trip alarm that monitors an RTD, thermocouple or similar input and drives two process relays and one fault relay.
- What safety integrity does the STA/TPRG/3PRG/U/-AO [DIN] family have? The STA datasheet states exida certification to IEC 61508:2010 for systematic integrity up to SIL 3 and random integrity up to SIL 2.
- Which power range does the STA/TPRG/3PRG/U/-AO [DIN] accept? The universal option accepts 21.6 to 375 Vdc or 90 to 260 Vac, and power consumption is stated as 5 W maximum.
- What does the -AO option add? It adds an isolated and linearised analog output, scalable from 0 to 21.6 mA or -0.2 to 10.5 V.
- How do I get a quote for the STA/TPRG/3PRG/U/-AO [DIN]? Send an RFQ with the part number, the quantity and the delivery location in Oman or the GCC, and mention if the FMEDA report is needed.
Documents and quotation
The manufacturer datasheet for the STA family is available from us on request and a copy is attached to this page. It contains the full ordering table, specifications and dimension drawings, and we suggest reading it before you decide on the final configuration.
To request a quotation, send an RFQ that includes the part number STA/TPRG/3PRG/U/-AO [DIN], the quantity, the delivery location in Oman or the GCC and any special requirement such as certification documents or a required delivery date. Our team will confirm availability and lead time and reply with a written offer.
Datasheets & Documents
- Datasheet STA SIL 2/3 Capable Temperature Safety Trip Alarm Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Moore Industries is an American manufacturer of signal interface instruments, founded in 1968 by engineer Leonard W. Moore in North Hills, California. Its first product was the SCT signal converter, built in a friend's workshop. The company has been at its North Hills headquarters since 1974 and still designs and builds its products there, known for rugged aluminium housings.
Seven Star LLC, an independent supplier in Oman, lists Moore Industries temperature transmitters, limit alarm trips, isolators and a PID backup controller, and sources units and replacements by full model number.
Moore Industries company profile
| Founded | 1968, North Hills, California, USA, by Leonard W. Moore |
|---|---|
| Headquarters | North Hills, California, since 1974 |
| Ownership | Privately owned (Moore Industries-International, Inc.) |
| First product | SCT signal converter |
| Product families | Signal isolators and converters (ECT, SCT), temperature transmitters (TRY, THZ), alarm trip units (SPA), miniMOORE multichannel signal conditioners, HART interfaces, SIL-rated safety logic solvers (STA) |
Milestones
- 1968: Leonard W. Moore founds the company and builds the first SCT signal converter.
- 1974: The company moves into its North Hills headquarters.
- 2009: miniMOORE wins a Control Engineering Engineers' Choice Award.
Moore Industries product families on this page
The manufacturer's catalog is arranged by function, and many of the items listed here map onto it directly:
- Temperature transmitters: the TRX, and the STZ functional safety dual input smart HART transmitter
- Alarm trips: the SPA2 programmable limit alarm trip, including an SPA2 with HLPRG input and four relay outputs
- Signal isolators, repeaters and converters: the SIX
- PID controllers and backup stations: the 535 in 1/4 DIN format
Other catalog groups include temperature assemblies and sensors, I/P and P/I converters, remote I/O, HART gateways and interfaces, indicators, and fieldbus device couplers.
Where Moore Industries instruments are used
These are control room and marshalling cabinet devices, plus field-mounted transmitters. Typical jobs are isolating a 4-20 mA loop between two systems, converting a thermocouple or RTD signal for a DCS input, adding an independent high or low trip next to the control system, and keeping a control loop running on a backup station when the main controller is out of service. Process plants in oil and gas, chemicals and power across the GCC use them for exactly these tasks.
Moore Industries products we list
Ordering Moore Industries instruments: what we need
Moore Industries model numbers are built from fields separated by slashes: unit, input, output, power and options, followed by the housing code in brackets. Every field matters. Send the complete string from the label, the serial number, and for programmable units the input type and range you want set. State any hazardous area or functional safety requirement, because approved versions are ordered with their own option codes.
Facts checked against trade press obituaries of Leonard W. Moore (Control Engineering, Control Global), October 2026.
Browse Moore Industries products by category: Temperature Instrumentation, Controllers & Data Acquisition, Isolator & Barrier.
FAQ
Questions about the STA/TPRG/3PRG/U/-AO [DIN] Safety Trip Alarm
Answers from our engineering team on installation, compatibility and integration.
01What does the STA/TPRG/3PRG/U/-AO [DIN] do?
It is a line-powered safety trip alarm that monitors an RTD, thermocouple or similar input and drives two process relays and one fault relay.
02What safety integrity does the STA/TPRG/3PRG/U/-AO [DIN] family have?
The STA datasheet states exida certification to IEC 61508:2010 for systematic integrity up to SIL 3 and random integrity up to SIL 2.
03Which power range does the STA/TPRG/3PRG/U/-AO [DIN] accept?
The universal option accepts 21.6 to 375 Vdc or 90 to 260 Vac, and power consumption is stated as 5 W maximum.
04What does the -AO option add?
It adds an isolated and linearised analog output, scalable from 0 to 21.6 mA or -0.2 to 10.5 V.
05How do I get a quote for the STA/TPRG/3PRG/U/-AO [DIN]?
Send an RFQ with the part number, the quantity and the delivery location in Oman or the GCC, and mention if the FMEDA report is needed.