Brand: Pepperl+Fuchs
Pepperl+Fuchs KHA6-SH-Ex1 Switch Amplifier, 115/230 V AC, SIL 3
Description
Pepperl+Fuchs KHA6-SH-Ex1 overview
The Pepperl+Fuchs KHA6-SH-Ex1 is a one-channel isolated switch amplifier from Pepperl+Fuchs that runs directly from an AC supply of 85 to 253 V AC. It transfers digital signals from SN or S1N proximity sensors, or approved dry contacts, from a hazardous area to a safe area. The input controls one relay output with three normally open contacts, one of which is connected in series with both output relays for the safety function, a second relay output with one normally open contact, and a passive transistor output used as the fault indication output.
Lead breakage and short-circuit of the control circuit are monitored continuously. In a fault condition the fault output energises and outputs I and II de-energise. For safety functions up to SIL 3 output I must be used, and for functions up to SIL 2 outputs I and II can both be used. The datasheet released on 4 February 2025 states SIL 3 with systematic capability SC 3 and performance level PL d, and the device has integrated terminals in the 40 mm wide housing type E.
Key features of the Pepperl+Fuchs KHA6-SH-Ex1
- Direct AC supply of 85 to 253 V AC at 45 to 65 Hz, so no 24 V DC supply is needed
- SN and S1N sensor input or approved dry contacts, with continuous lead breakage and short-circuit monitoring
- Output I with three NO contacts for safety use, output II with one NO contact, and a transistor fault output
- SIL 3 with systematic capability SC 3 and performance level PL d
- Response delay of 1 ms or less
- Relay contact rating 253 V AC at 1 A or 24 V DC at 1 A resistive, mechanical life 50 million cycles
- Integrated terminals in housing type E, 40 mm wide
- Ambient temperature minus 20 to 60 degrees C
KHA6-SH-Ex1 technical specifications
The values below are taken from the manufacturer datasheet of the KHA6-SH-Ex1, release date 2025-02-04. Always confirm the current datasheet and the certificates before final engineering.
| Parameter | Value |
|---|---|
| Model | KHA6-SH-Ex1, Switch Amplifier, 1-channel isolated barrier |
| Signal type | Digital input |
| Safety Integrity Level / systematic capability / PL | SIL 3 / SC 3 / PL d |
| Rated supply voltage | 85 to 253 V AC, 45 to 65 Hz; terminals 22, 23, 24 |
| Rated current | 30 mA plus or minus 5 mA |
| Power dissipation / consumption | 2.2 W / up to 2.3 W |
| Input | Terminals 10+, 12-; SN/S1N sensor or dry contact |
| Open circuit voltage / short-circuit current | Approx. 8.4 V DC / approx. 11.7 mA |
| Lead resistance | Up to 50 ohm |
| Relay de-energised | Input current below 2.1 mA and above 5.9 mA |
| Relay energised | Input current between 2.8 mA and 5.3 mA |
| Response delay | Up to 1 ms |
| Outputs | I: terminals 13, 14; II: terminals 15, 21; III: terminals 16+, 17- (fault, passive transistor) |
| Contact loading (outputs I and II) | 253 V AC / 1 A / cos phi 0.7 or more; 24 V DC / 1 A resistive |
| Mechanical life | 50 million switching cycles |
| Hazardous-area marking | (1)G [Ex ia Ga] IIC; certificate PTB 00 ATEX 2043 |
| Input Ex ia values | Uo 9.56 V, Io 16.8 mA, Po 41 mW (linear characteristic) |
| Ambient temperature | Minus 20 to 60 degrees C |
| Dimensions / mass | 40 x 93 x 115 mm (W x H x D), housing type E / approx. 280 g |
| Mounting | 35 mm DIN rail |
The safety function relies on specific contacts. For SIL 3 use output I and the terminals the datasheet names, and follow the test documents when the module is part of a safety loop.
Typical applications in oil and gas, utilities, water and manufacturing
Position and process switching in hazardous areas relies on NAMUR proximity sensors and dry contacts, from valve limit switches on ESD valves at wellheads to level switches on storage tanks and flow switches on cooling water lines. The KHA6-SH-Ex1 passes these signals out of the hazardous area to relays, PLC inputs or annunciators, and its line fault detection tells operators when a cable is open or shorted instead of leaving them with a silent failure.
In power stations, water treatment plants and manufacturing facilities around the GCC, the same module is common on package units, burner management panels and compressor skids. Because the signal is a simple switching state, the KHA6-SH-Ex1 is easy to commission, and spare units are often held on the shelf because a failed channel can stop a whole skid.
Selection and compatibility notes for KHA6-SH-Ex1
Check the sensor type first. The input is designed for NAMUR sensors according to EN 60947-5-6 and for mechanical contacts with the resistor network shown in the wiring diagram, so a three-wire sensor or a powered contact needs a different interface. Next check what the safe-area load requires, because a relay output and a transistor output behave very differently with PLC cards, solenoids and counters.
If the signal is part of a safety function, read the functional safety data in the datasheet, including the SIL value and the conditions attached to it, and compare it with your safety requirement specification. When the KHA6-SH-Ex1 replaces an older module, compare terminal numbers and the supply arrangement, since the Power Rail option changes how power and the collective error message are wired.
The AC supply makes the KHA6-SH-Ex1 useful where a 24 V DC supply is not available in the panel, for example in older motor control rooms. Verify the supply tolerance of 85 to 253 V AC before you connect it to a local supply.
Installation and commissioning of the KHA6-SH-Ex1
Before mounting the KHA6-SH-Ex1, confirm the field device and cable parameters against the entity values in the datasheet and the certificate, and decide whether the module will be powered from a Power Rail or from its own supply terminals. Mount it on a 35 mm DIN rail in a clean, ventilated cabinet in the safe area, keep hazardous-area and safe-area wiring physically separated and labelled, and respect the spacing and marking required by your site rules for intrinsically safe circuits. Use terminals 13 and 14 for single-channel operation up to SIL 3 on the KHA6-SH-Ex1, and use the centre tap terminals 19 and 20 only where a redundant branch is designed.
Wire the KHA6-SH-Ex1 only to the terminal assignment printed in the wiring diagram, tighten the screws and check that no strands are left outside the clamp. After applying the supply, check the power indication, then simulate the field signal and prove the complete loop from field to control system before the plant is handed over. Record the as-found readings so that later loop checks of the KHA6-SH-Ex1 can be compared with the commissioning values.
Maintenance and service life
The KHA6-SH-Ex1 has no serviceable parts, so maintenance is mostly inspection. During planned shutdowns, check terminals for looseness and corrosion, verify the supply voltage at the module, and repeat the loop check that was recorded at commissioning. In coastal and humid locations such as Muscat, Sohar and Duqm, a clean, dry and sealed cabinet greatly extends the life of any electronic interface. For safety applications, follow the proof-test guidance in the test documents for the KHA6-SH-Ex1 and keep the proof-test records in the safety file.
If a loop drifts out of tolerance or the unit shows no power indication with a healthy supply, replace the module instead of attempting a repair, and keep the replacement documentation in the loop folder. Certified intrinsically safe equipment must not be modified, and any change to cabling, load or field device should be re-assessed against the KHA6-SH-Ex1 entity parameters before it returns to service.
Related products and ordering notes
Customers who ask for the KHA6-SH-Ex1 often need neighbouring models or accessories from the same system, such as other KHA6 and KFD2 switch amplifiers, SN and S1N proximity sensors, and the KFD2-SH-Ex1 family. If you are standardising a cabinet on one family, send us the loop list and we can quote the matching modules together.
When you send an enquiry for the KHA6-SH-Ex1, quote the full part number exactly as printed on the nameplate, the quantity and the intended application. If you are replacing an installed unit, a photograph of the nameplate helps us confirm the exact variant you need. We can arrange a quotation with delivery to Oman and across the GCC.
Frequently asked questions about KHA6-SH-Ex1
The KHA6-SH-Ex1 is a SIL 3 and PL d one-channel switch amplifier with an 85 to 253 V AC supply, relay outputs rated 253 V AC at 1 A, a fault output and a 40 mm wide housing.
Documents and quotation
A copy of the manufacturer datasheet for the KHA6-SH-Ex1 is attached to this page for your engineering review. To request a quotation, send the RFQ with the part number KHA6-SH-Ex1, the quantity, the delivery location and any certification or documentation requirements, and we will reply with availability and lead time. Please check the specification against your loop or system requirements before ordering.
Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with Pepperl+Fuchs. Product names and part numbers are used only to identify the item you ask for.
Other Models in the K System Range
Seven Star LLC supplies models from the K System range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
Datasheets & Documents
- Datasheet KHA6-SH-Ex1 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Pepperl+Fuchs is a German manufacturer of industrial sensors and explosion protection equipment, founded in 1945 in Mannheim by Walter Pepperl and Ludwig Fuchs as a radio repair shop. Defective transformers led them into manufacturing, and the company developed its first proximity switch in the late 1950s. Pepperl+Fuchs is headquartered in Mannheim and is a pioneer of intrinsically safe electrical equipment for hazardous areas.
Seven Star LLC lists Pepperl+Fuchs sensors, isolated barriers, power supplies and hazardous-area mobile devices, and supplies them to instrument and automation teams in Oman by exact model designation.
Pepperl+Fuchs company profile
| Founded | 1945, Mannheim-Sandhofen, Germany, by Walter Pepperl and Ludwig Fuchs |
|---|---|
| Headquarters | Mannheim, Germany |
| Ownership | Privately owned (Pepperl+Fuchs SE) |
| Origins | Radio repair workshop that began making replacement transformers |
| Product families | Inductive, capacitive, ultrasonic and photoelectric sensors, rotary encoders, R2000 LiDAR scanners, KFD and HiC isolated barriers, Zener barriers, remote I/O, purge and pressurization systems, Ex-rated enclosures |
Milestones
- 1945: Walter Pepperl and Ludwig Fuchs open their radio repair shop in Mannheim.
- 1958: The first proximity switch is developed (some company sources say 1959).
Pepperl+Fuchs product families on this page
On the interface side there are two systems. The K-System mounts on DIN rail and is represented here by the KFD2-UT2-Ex2 universal temperature converter. The H-System plugs into termination boards and is represented by the HiD2030 SMART transmitter power supply with HART. The PS1000-A6-24.20 is a 24 VDC, 20 A power supply for cabinets. Sensors listed include the NJ2-12GK-SN NAMUR inductive sensor, the R101 retro-reflective photoelectric sensor and the R2000 2-D LiDAR scanner. For field staff there are the Tab-Ex 05 DZ1 tablet for Zone 1/21 areas and the Smart-Ex 03 DZ2 smartphone for Zone 2/22 and Division 2 areas.
Where Pepperl+Fuchs equipment is used
Isolated barriers sit between field instruments in Zone 0 or Zone 1 and the DCS or safety system in refineries, gas plants and chemical works. NAMUR sensors report valve position and machine states in classified areas. Photoelectric sensors and LiDAR scanners work in conveying, packaging, warehousing and vehicle guidance. Ex-rated tablets and phones are carried on operator rounds and maintenance jobs.
Pepperl+Fuchs products we list
Ordering Pepperl+Fuchs parts: what we need
Send the complete model designation as printed on the device, including every suffix; a single letter can change the supply voltage or the output type. Add the part number if the label shows one. For barriers, tell us the field device and signal type, the number of channels and whether the safety loop needs a SIL-assessed module. For mobile devices, state the zone or division and the regional radio version.
Facts checked against Pepperl+Fuchs's own chronicle pages, October 2026.
Browse Pepperl+Fuchs products by category: Sensors & Transmitters, Industrial Computer, Isolator & Barrier, Power Modules.
FAQ
Questions about the Pepperl+Fuchs KHA6-SH-Ex1 Switch Amplifier, 115/230
Answers from our engineering team on installation, compatibility and integration.
01What supply does the KHA6-SH-Ex1 use?
It runs from 85 to 253 V AC at 45 to 65 Hz on terminals 22, 23 and 24, with a rated current of 30 mA.
02What SIL level does the KHA6-SH-Ex1 reach?
The datasheet states SIL 3 with systematic capability SC 3 and performance level PL d, using output I for SIL 3 applications.
03Which sensors can be connected?
SN and S1N proximity sensors or approved dry contacts; a mechanical contact needs the 10 kilohm and 1.5 kilohm resistors shown in the diagram.
04How fast does it respond?
The datasheet gives a response delay of up to 1 ms for this switch amplifier.
05How do I order the KHA6-SH-Ex1?
Send an RFQ with the part number KHA6-SH-Ex1, the quantity and the delivery location in Oman or the GCC, and Seven Star LLC will reply with availability and lead time.


















Reviews