Schneider Electric C16N32D160 NSX160N 3P 160 A MicroLogic 2.2

Description

C16N32D160 explained: a 160 A three-pole NSX160N with MicroLogic 2.2

The C16N32D160 is a complete Schneider Electric ComPacT NSX160N moulded-case circuit breaker, fitted at the factory with a MicroLogic 2.2 electronic trip unit rated 160 A. The datasheet title is: Circuit breaker ComPacT NSX160N, 50kA at 415VAC, MicroLogic 2.2 trip unit 160A, 3 poles 3d. It is a fixed three-pole breaker for AC distribution at up to 690 V and carries an N breaking-capacity class of 50 kA at 415 V AC. Seven Star LLC supplies the C16N32D160 in Oman and the GCC as an independent supplier in Muscat.

In the reference, C16 points to the NSX160 frame, N to the breaking-capacity class (datasheet code N 50 kA 415 V AC), 3 to three poles, 2D to the MicroLogic 2.2 trip unit with all three poles protected (3D), and 160 to the trip unit rating in amperes. All statements here come from the C16N32D160 datasheet.

Technical specifications of the C16N32D160

Parameter Specification
Manufacturer / part number Schneider Electric / C16N32D160
Range / product name ComPacT / ComPacT NSX
Device short name NSX160N
Product type Circuit breaker, distribution application
Poles / protected poles 3P / 3D
[In] rated current 160 A at 40 °C
[Ue] rated operational voltage 690 V AC 50/60 Hz
Breaking capacity code N 50 kA 415 V AC
Trip unit MicroLogic 2.2, electronic, protection functions LSoI
[Ir] long-time pick-up 63 to 160 A, 9 settings
Long-time delay [tr] 400 s at 1.5 x Ir; 16 s at 6 x Ir; 11 s at 7.2 x Ir (delay fixed)
Thermal memory 20 minutes before and after tripping
[Isd] short-time pick-up 1.5 to 10 x Ir, 9 settings; fixed delay
[Ii] instantaneous pick-up 2400 A, fixed
Earth-leakage / ZSI Without / without
Suitability for isolation Yes, EN/IEC 60947-2; Category A
[Ui] / [Uimp] 800 V AC 50/60 Hz / 8 kV
Mechanical durability 40000 cycles
Electrical durability 40000 cycles at 440 V In/2; 20000 at 440 V In; 15000 at 690 V In/2; 7500 at 690 V In
Power dissipation per pole 9.2 W
Control / mounting mode Toggle / fixed, on backplate
Connections Front, upside and downside; pitch 35 mm
Number of slots 5
Local signalling Green flashing LED ready; red LED 105 % Ir; orange LED 90 % Ir
Dimensions W x H x D 105 x 161 x 86 mm
Net weight 2.2 kg
Protection degree IP40 (IEC 60529); IK07; Class II on front face
Overvoltage category / pollution degree III / 3
Relative humidity 0 to 95 %
Operating altitude 0 to 2000 m without derating; 2000 to 5000 m with derating

Breaking capacity of the C16N32D160 by voltage

The datasheet gives IEC 60947-2 values for each voltage band. The service breaking capacity Ics equals the ultimate breaking capacity Icu at every voltage listed, so no reduction factor has to be applied for the service value. The fault level at the installation point should be compared with the row that matches the real system voltage; in a 400/415 V network the relevant value is 50 kA.

Voltage Icu Ics
220/240 V AC 90 kA 90 kA
380/415 V AC 50 kA 50 kA
440 V AC 50 kA 50 kA
500 V AC 36 kA 36 kA
525 V AC 35 kA 35 kA
660/690 V AC 10 kA 10 kA

The datasheet also lists values to UL 60947-4-1: 85 kA at 240 V AC, 50 kA at 480 V AC and 10 kA at 600 V AC.

How the MicroLogic 2.2 trip unit protects the C16N32D160

MicroLogic 2.2 is an electronic trip unit with protection functions LSoI: L (long time overload), So (short time short-circuit with fixed delay) and I (instantaneous short-circuit). It has no earth-leakage protection and no zone selective interlocking according to the datasheet. The long-time pick-up Ir is set on a dial with nine positions covering 63 to 160 A. The long-time delay is fixed, with 400 s at 1.5 x Ir, 16 s at 6 x Ir and 11 s at 7.2 x Ir. Thermal memory is 20 minutes before and after tripping, so a breaker that has just cleared an overload does not restart from a cold curve.

The short-time pick-up Isd is adjustable from 1.5 to 10 x Ir in nine settings with a fixed delay, and the instantaneous pick-up is fixed at 2400 A. Three front LEDs give a quick status: a flashing green LED for ready, an orange one at 90 % of Ir and a red one at 105 % of Ir.

Setting the C16N32D160 on site

Because the long-time dial on the C16N32D160 runs from 63 A to 160 A, a breaker bought at 160 A can still be set down to match a smaller cable or load. A load of 100 A, for example, can be set on the 100 A position rather than needing a different breaker. Whenever Ir is lowered, Isd, which is a multiple of Ir, shifts with it, so the short-time level in amperes falls as well. Record the settings on the panel documents and check them again when the load changes.

Coordination with devices upstream and downstream depends on those settings and on the fixed 2400 A instantaneous level; coordination data is outside the datasheet and is taken from the manufacturer coordination tables.

Mounting, connection and durability of the C16N32D160

The C16N32D160 is a fixed breaker for mounting on a backplate in horizontal, vertical or flat-on-back positions. Connections are at the front at both ends on a 35 mm pitch. The body is 105 mm wide, 161 mm high, 86 mm deep and weighs 2.2 kg. Mechanical durability is 40000 cycles; electrical durability is 40000 cycles at 440 V and half of In, 20000 at 440 V and In, 15000 at 690 V and In/2 and 7500 at 690 V and In. Power dissipation is 9.2 W per pole, which should be added to the heat budget of the enclosure.

The datasheet gives IP40, IK07, Class II on the front face, overvoltage category III and pollution degree 3. Full rating applies to 2000 m and derating from 2000 to 5000 m.

Applications of the C16N32D160 in Oman and the GCC

A 160 A electronic breaker with 50 kA at 415 V fits main and sub-distribution boards in industrial buildings, motor control centre incomers, utility auxiliary boards, water and desalination plants and process facilities across Oman and the GCC. The adjustable Ir helps where cable sizes vary between feeders. For boards installed in desert or coastal sites, the enclosure should handle dust and humidity, since IP40 protects only against solid objects larger than 1 mm.

Related NSX160 and NSX250 references to the C16N32D160

The same MicroLogic 2.2 concept appears at the NSX160B and NSX160F levels (for example C16B32D160 and C16F32D160) with lower breaking classes, and in the NSX250 range with 250 A trip units such as C25N32D250. The C16N32D160 sits at 50 kA with 160 A. MicroLogic 2.2 also has no earth-fault protection; where that is required, a trip unit like the MicroLogic 6.2 E (see C2536E250) is a different product with different functions.

Selection and RFQ checklist for the C16N32D160

  • Part number C16N32D160, quantity, and fixed or other mounting requirement.
  • System voltage, frequency and prospective short-circuit current at the board.
  • Load current and the Ir setting that the design intends to use.
  • Whether earth-fault or ZSI functions are needed, since they are absent here.
  • Enclosure ventilation, ambient temperature and altitude.
  • Delivery location and documents required.

Documents and quotation

A datasheet for this product is attached on this page. It lists the electrical, mechanical and environmental data summarised above, and it is the document to check against your own drawings.

Send us the part number, quantity and application and we will confirm availability and a quotation. Seven Star LLC is an independent supplier in Muscat and is not affiliated with the manufacturer.

Datasheets & Documents
  • PDF Datasheet Schneider Electric C16N32D160 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric C16N32D160 NSX160N 3P 160 A

Answers from our engineering team on installation, compatibility and integration.

01What is the adjustment range of the C16N32D160?
The long-time pick-up Ir is adjustable from 63 to 160 A in nine settings and the short-time pick-up Isd from 1.5 to 10 x Ir, according to the datasheet.
02What is the breaking capacity of the C16N32D160 at 415 V?
The datasheet gives 50 kA Icu at 380/415 V AC under IEC 60947-2, and the Ics is also 50 kA.
03Does the C16N32D160 have earth-fault protection?
No. MicroLogic 2.2 provides LSoI functions only; the datasheet lists earth-leakage protection and ZSI as absent.
04What are the size and weight of the C16N32D160?
105 mm wide, 161 mm high and 86 mm deep, net weight 2.2 kg, as listed in the datasheet.
05What does the C16N32D160 draw as heat?
Power dissipation is 9.2 W per pole according to the datasheet. Include it in enclosure temperature calculations.