Lovato P5ME3PS0630 630 A Moulded Case Circuit Breaker

Description

Lovato P5ME3PS0630 moulded case circuit breaker, 630 A

The Lovato P5ME3PS0630 is a three-pole moulded case circuit breaker rated at 630 A with an electronic trip unit. The overload threshold is adjustable from 252 to 630 A and the short-circuit threshold from 378 to 6300 A. It is a main or feeder breaker for low-voltage switchboards. Seven Star LLC supplies the P5ME3PS0630 in Oman and the GCC as an independent supplier in Muscat.

The code is read from the catalogue family, P5ME being the electronic-trip moulded case series, then 3P for three poles, S for the breaking-capacity level and 0630 for 630 A. A sibling already in our range is the P5ME3PS0250, a 250 A frame, and the series continues with the P5ME3PS0400 and P5ME3PS0800.

P5ME3PS0630 technical specifications

Parameter Specification
Manufacturer / part number Lovato / P5ME3PS0630
Poles 3
Rated current (up to 40 °C) 630 A
Electronic overload adjustment 252 to 630 A
Electronic short-circuit adjustment 378 to 6300 A
Rated operating voltage Ue 690 V AC
Insulation Ui / Uimp 1000 V / 8 kV
Icu = Ics at 220-240 V 100 kA
Icu = Ics at 380-415 V and 440-460 V 65 kA
Icu = Ics at 480-500 V / 525 V / 660-690 V 42 / 22 / 10 kA
Heat dissipation per pole (max) 83 W
Terminals Screw M10 x 30, 8 mm Allen key, up to 48 Nm
Life 20,000 mechanical and 6,000 electrical cycles
Dimensions (W x H x D) 140 x 260 x 110 mm
Weight 5400 g
Temperature and protection -20 to +70 °C operating; IP20 on the front

Reading the P5ME3PS0630 trip settings

The electronic trip unit lets the user choose a long-time pickup between 252 A and 630 A, which is 40 to 100 percent of the frame current, and a short-time level from 378 A to 6300 A, which is 1.5 to 10 times the rating. This wide window allows coordination with downstream feeders: a downstream branch breaker can be set to trip first, leaving the main closed so other loads stay energised.

Because the breaker is electronic, the thermal characteristic does not depend on ambient heat in the way a thermal-magnetic unit does, but the frame itself still derates. The catalogue gives the permitted current as 591 A at 50 °C, 555 A at 60 °C and 517 A at 70 °C.

Breaking capacity of the P5ME3PS0630

At 400 V the breaker is rated for 65 kA for both ultimate and service duty, and the Icu equals Ics at every voltage given. A service rating equal to ultimate means the device is intended to remain in service after interrupting a fault of the listed level. Even at 690 V the breaker is rated for 10 kA.

When a design needs higher values, such as in a substation next to a large transformer, the designer should check the let-through energy and consider current-limiting upstream devices.

Where the P5ME3PS0630 fits

Use it as the incomer of a sub-distribution board, as a feeder to a motor control centre or to a large process motor with its own starter. The 5.4 kg frame is mounted on a vertical plane or in any permitted orientation and is connected to its M10 screw terminals. Smaller breakers in the family, the P5ME3PS0250 and P5ME3PS0400, serve the downstream feeders.

P5ME3PS0630 selection checklist

  • Load current including diversity at ambient temperature
  • Long-time and short-time settings needed for coordination
  • System voltage and prospective fault current
  • Lug or busbar connection method and cable size
  • Panel space of 140 x 260 x 110 mm per pole group
  • Required accessories such as shunt trips or motor operators
  • Altitude and temperature derating

Installation and maintenance of the P5ME3PS0630

Tighten the M10 terminal screws to the torque stated in the instruction sheet, with a maximum of 48 Nm, and use the proper Allen key. Loose joints at this current level overheat and often cause failures long before the trip unit has a chance to act.

Exercise the handle during shutdowns, inspect for dust and discoloration, and verify the settings after any change in the downstream network. Thermographic checks under load are a good routine for 630 A joints.

Typical P5ME3PS0630 applications in Oman and the GCC

The breaker serves as an incomer in building services panels, a feeder in industrial MCCs, a main for desalination pump rooms and a protective device for transformer secondaries up to roughly 430 kVA at 400 V. In hot switch rooms, the derating table above decides the usable current.

P5ME family ratings in the catalogue

Part Rating Use
P5ME3PS0250 250 A Feeders and small incomers
P5ME3PS0400 400 A Medium feeders
P5ME3PS0630 630 A This part: main and large feeders
P5ME3PS0800 800 A Larger incomers

Documentation should follow the breaker into the project file. Record the pickup values chosen, the time delays, the date of commissioning and the measured load at handover. Years later, when a feeder is changed or a new motor is added, this record saves time and avoids nuisance trips or, worse, an upstream trip that blacks out a whole board. A single-line diagram with coordination curves marked is the best companion to the physical breaker.

Information to send with an RFQ for the P5ME3PS0630

  • Part number P5ME3PS0630 and quantity
  • Load current and settings required
  • Voltage and fault level
  • Connection type
  • Accessories wanted
  • Delivery location and project

Documents and quotation

Send the part number P5ME3PS0630 and we will confirm the documents available for it, such as the technical data sheet, wiring diagram and instruction sheet, together with availability and lead time.

Seven Star LLC is an independent supplier in Muscat and is not an official channel of the manufacturer. Share the quantity, delivery location and project reference with the request and we will answer with a formal quotation.

Other Models in the Lovato P5me Mccb Range

Seven Star LLC supplies models from the Lovato P5me Mccb range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Lovato P5ME3PS0250 Moulded Case Circuit Breaker 250 ACircuit BreakersView details
Lovato P5ME3PS0630 630 A Moulded Case Circuit BreakerCircuit BreakersYou are viewing this model
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Lovato Electric is the Italian manufacturer of low-voltage electrical components for industrial automation and power distribution: contactors, motor protection circuit breakers, soft starters, variable speed drives, power factor controllers, transfer switch and generator controllers, and energy meters. It was founded in Bergamo in 1922 and has been run by the same family for four generations. Its headquarters is in Gorle, near Bergamo, and it celebrated its centenary in 2022.

Seven Star LLC is an independent supplier in Muscat. We list Lovato motor control, drives and power management products, and supply them to panel builders, contractors and maintenance teams in Oman and the GCC by order code.

Lovato Electric at a glance

Established 1922, Bergamo, Italy
Headquarters Gorle (Bergamo), Italy
Ownership Private, family-run for four generations
Product families Contactors and relays, motor protection circuit breakers, motor starters, soft starters, variable speed drives, power factor controllers, ATS and gen-set controllers, multimeters and energy meters, micro PLCs

Lovato products we list

Family Models Typical use
Contactors BF0910A230, BF1810A230, BF2510A230, BF2600A230, BF09T4A230 4-pole, BFS0923A024, 11BG0910A230 mini, 11BGR0901A048 reversing Switching motors, heaters, lighting and capacitor banks
Motor protection and starters SM1P0650, SM1P1000, SM1P3200, M1P enclosed DOL starter, ME024FD024, ME070RSD024, 31L48 time relay Short-circuit and overload protection and direct starting of motors
Soft starters ADXL0030600, ADXL0085600, ADXL0135600, ADXT0034, ADXT0084, ADXT0139 Reducing starting current and mechanical shock on pumps, fans and compressors
Variable speed drives VLA1, VLB1, VLB3 0.75 kW, VLB3 2.2 kW, VLB3 5.5 kW, VLB3 22 kW, VT1 Speed control of pumps, fans and conveyors to save energy
Power management and control DCRG8, DCRL8 PF controllers, ATL600 ATS controller, RGK600 gen-set controller, DMG200 multimeter, DMED300T2 energy meter, LRD20 micro PLC Power factor correction, mains/generator changeover and energy monitoring

Lovato order codes describe the product. On a contactor such as BF0910A230, "BF09" is the frame and rated current (9 A in AC-3), "10" is the built-in auxiliary contact (one normally open), "A" means an AC coil and "230" is the coil voltage. The coil voltage must match the control circuit exactly, so it is the most common detail to check when replacing one. For motors, a soft starter limits the inrush current at start and stop, while a variable speed drive controls the speed continuously and saves energy on pumps and fans that do not need full flow all the time.

Where Lovato products are used

In Oman and the GCC, Lovato components are built into motor control centres, pump and HVAC panels, capacitor banks for power factor correction, generator and ATS panels, and machine control panels for industry, water and buildings.

Ordering Lovato products: what we need

Send the full Lovato order code. For contactors and starters, confirm the coil or control voltage. For drives and soft starters, send the motor power, current and supply voltage. For power factor controllers, send the number of steps and the CT ratio.

Facts checked against Lovato Electric company profile brochures, October 2026.

FAQ

Questions about the Lovato P5ME3PS0630 630 A Moulded Case Circuit

Answers from our engineering team on installation, compatibility and integration.

01What are the trip settings of the P5ME3PS0630?
The electronic overload threshold is adjustable from 252 to 630 A and the short-circuit threshold from 378 to 6300 A.
02What is its breaking capacity at 400 V?
The catalogue lists Icu and Ics as 65 kA at 380 to 415 V and 65 kA at 440 to 460 V.
03How does temperature affect the current rating?
The catalogue lists 591 A at 50 degrees C, 555 A at 60 degrees C and 517 A at 70 degrees C.
04What terminals does it have?
It has M10 x 30 screw terminals tightened with an 8 mm Allen key up to 48 Nm.
05What is its size and weight?
The frame measures 140 x 260 x 110 mm and weighs 5400 g.