Schneider Electric BMXDDO1602 X80 16-Output Transistor Module

Description

BMXDDO1602 16-channel 24 V DC discrete output module for X80

The BMXDDO1602 is a Schneider Electric product listed in the datasheet as: discrete output module, Modicon X80, 16 transistor outputs, 24V DC positive. The BMXDDO1602 is a 16-output discrete output module for the X80 platform. It uses positive-logic transistor outputs at 24 V DC, with reverse-polarity protection, for driving relays, contactor coils, solenoid valves and indicator lamps. Seven Star LLC supplies the BMXDDO1602 in Oman and the GCC as an independent supplier based in Muscat.

Reading the reference: BMX is the X80 hardware, DDO the discrete output module type, 16 the number of channels and 02 the version. The datasheet states positive logic.

Technical specifications of the BMXDDO1602

Parameter Specification
Manufacturer / part number Schneider Electric / BMXDDO1602
Description discrete output module, Modicon X80, 16 transistor outputs, 24V DC positive
Range of Product Modicon X80
Product or Component Type Discrete output module
Discrete output logic Positive
Response time on output 1.2 ms
Maximum voltage drop <1.2 V at state 1
Insulation resistance > 10 MOhm 500 V DC
Current per channel 0.625 A
Maximum current per module 10 A
Paralleling of outputs Yes : 2 maximum
Switching frequency 0.5/LI² Hz
Load impedance ohmic > 48 Ohm
Reverse polarity protection Reverse mounted diode
MTBF reliability 410000 H
Protection type External fuse reverse polarity protection short-circuit protection overload protection overvoltage protection
Voltage detection threshold < 14 V DC preactuator fault; > 18 V DC preactuator at state 0
Net Weight 0.12 kg
IP Degree of Protection IP20
Dielectric strength 1500 V AC 50/60 Hz 1 minute, output/ground; 1500 V AC 50/60 Hz 1 minute, output/internal logic
Relative humidity 5 to 95 % 55 °C without condensation

Output ratings and protection

Output logic: Positive. Current per channel: 0.625 A. Maximum current per module: 10 A. Response time: 1.2 ms. Voltage drop: <1.2 V at state 1. Protection: External fuse reverse polarity protection short-circuit protection overload protection overvoltage protection. Paralleling: Yes : 2 maximum.

The module does not include a fuse in the output path, so external protection is part of the design: the datasheet lists external fuse and reverse-polarity protection. A fuse per group of outputs avoids a short on one valve cable taking down all.

Placement of the BMXDDO1602 and wiring to actuators

The module plugs into a rack slot and takes backplane power. Field wiring uses a 20-way or 40-way connector according to the installation guide; a pre-wired cable and terminal block simplifies maintenance.

The counterpart for field signals is a discrete input module such as BMXDDI1602. Keep inductive loads suppressed with diodes to protect the transistor outputs.

Selection checklist for the BMXDDO1602

  • Channels needed and the current per channel (0.625 A).
  • Load type: lamps, coils or valves; inductive suppression.
  • 24 V DC sensor/actuator supply and fusing.
  • Positive versus negative logic: this is positive.
  • Connector and pre-wired cable option.
  • Rack power budget.

Installation and maintenance of the BMXDDO1602

Insert in the rack, connect the field cable, feed the actuator supply and configure the channels. Check each output with a forced value from the engineering software.

If an output fails, check the fuse and suppression diodes first. Use the LED indicators and the preactuator voltage-detection status to find missing field supply.

Typical applications of the BMXDDO1602 in Oman and the GCC

Solenoid valves on skids, contactor coils, alarms and beacons across plants in the region. Racks that control many valves are often installed in climate-controlled shelters.

Dimensions, environment and approvals of the BMXDDO1602

The BMXDDO1602 weighs 0.12 kg. Mounting, derating and enclosure choices follow the environmental data below, which should be compared with the actual panel temperature and the dust and humidity of the site in Oman and the GCC.

Relative humidity: 5 to 95 % 55 °C without condensation. Ingress protection: IP20.

Output modules often fail because of the field side, not the module itself. Typical causes are an inductive load without a suppression diode, a short on a long field cable, or an actuator supply that is missing or reversed. Before replacing the BMXDDO1602, measure the actuator supply on the connector, check the fuse in the supply path and look at the preactuator status information in the program. Group outputs by function on the connector so that a single fuse protects related loads only. Labelling each wire at both ends and keeping a terminal list with the channel number turns a module swap into a ten-minute job. When the module drives valves that must go to a safe position, decide what each output should do on a processor stop or a communication loss: the rack configuration offers fallback settings per channel, and the choice should follow the process safety review rather than the default. Keep the wiring list and the force-output test result in the maintenance file so that a technician on night shift can verify each valve without the engineering laptop. A spare module and a spare pre-wired cable are cheap compared with an unplanned stop.

Information to send with an RFQ for the BMXDDO1602

  • Full reference and quantity required
  • Existing equipment, panel or rack it must fit
  • Supply voltage, load or signal details of the application
  • Required delivery location and timing
  • Whether a spare, a replacement or a new installation

Site conditions in Oman for the BMXDDO1602

Control cabinets in Gulf plants often run hot, because many sit in outdoor kiosks or in rooms where air conditioning is not always reliable. Before you finalise the BMXDDO1602, check the permitted ambient range and any derating stated by the manufacturer against the real temperature inside your panel, and leave the recommended spacing around the device so that heat can escape. Long cable runs between the field and the marshalling cabinet are common on large sites, so confirm the signal types, wiring limits and earthing arrangement early in the design.

It also helps to standardise on a small number of part numbers across a project. Keeping a few spare BMXDDO1602 units on site in Oman shortens recovery time after a fault, and documenting configuration settings makes replacement faster for the maintenance team.

Documents and quotation

A datasheet for this product is attached on this page. It lists the electrical, mechanical and environmental data summarised above.

Send us the part number, quantity and application and we will confirm availability and a quotation. Seven Star LLC is an independent supplier in Muscat and does not represent itself as an official channel of the manufacturer.

Datasheets & Documents
  • PDF Datasheet Schneider Electric BMXDDO1602 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric BMXDDO1602 X80 16-Output

Answers from our engineering team on installation, compatibility and integration.

01How many channels has the BMXDDO1602?
The module has 16 channels; per-channel current is 0.625 A.
02What is the output logic?
It is Positive.
03What is the response time?
Listed: 1.2 ms.
04Is there reverse polarity protection?
Datasheet: Reverse mounted diode.
05What is the weight?