- Automation & ControlView all 1,920 products
- AC Drives
- PLC & I/O Cards
- Industrial Communications
- Vibration Monitoring
- Automation Accessories
- Controllers & Data Acquisition
- Isolator & Barrier
- CCTV & Security
- Safety Switches & Guard Locking
- Encoders
- HMI Displays
- Industrial Computers
- Motor Soft Starters
- Servo Drives
- Pneumatic Cylinders
- Machine Vision
- Automation Software
- Robotics
Brand: Pepperl+Fuchs
Pepperl+Fuchs KFD2-ST3-Ex2 2-Channel Switch Amplifier
Description
KFD2-ST3-Ex2 two-channel switch amplifier with active outputs
The KFD2-ST3-Ex2 is the two-channel, active-output member of the Pepperl+Fuchs K-System switch amplifier series. Two NAMUR sensor or dry-contact inputs from a hazardous area each switch one transistor output that is fed from the module supply, so a PLC or relay coil can be driven without an external voltage source on the output side.
In the part number, KFD2 is the 24 V DC isolated barrier line, ST3 the active-transistor switch amplifier generation 3 and Ex2 the two-channel version. Its passive-output counterpart is the KFD2-SOT3-Ex2, and the single-channel versions carry Ex1 in the name.
Seven Star LLC supplies this barrier in Oman and the GCC as an independent supplier based in Muscat.
Technical specifications of the KFD2-ST3-Ex2
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Pepperl+Fuchs KFD2-ST3-Ex2 |
| Channels | 2 |
| Input | Dry contact or NAMUR, EN 60947-5-6; terminals 1+, 2+, 3- and 4+, 5+, 6- |
| Switching point / hysteresis | 1.2 to 2.1 mA / approx. 0.2 mA |
| Line fault detection | Breakage I ≤ 0.1 mA, short-circuit I ≥ 6.5 mA |
| Outputs | Active transistor, terminals 7+ and 9+; 30 V DC, 100 mA |
| Signal level | 1-signal: supply voltage minus about 3 V at 100 mA; 0-signal: blocked, leakage ≤ 10 µA |
| Response time / frequency | ≤ 200 µs / ≤ 5 kHz |
| Supply | 19 to 30 V DC, Power Rail or terminals 14+/15-; ≤ 900 mW including output dissipation |
| Functional safety | SIL 2, SC 3 acc. to IEC/EN 61508 |
| Hazardous area data | Ex ia input Uo 10.5 V, Io 17.1 mA, Po 45 mW; II 3(1)G Ex nA [ia Ga] IIC T4 Gc; EXA 16 ATEX 0016 X |
| Ambient temperature | -20 to 60 °C |
| Housing | Type B2, 20 x 119 x 115 mm, IP20, approx. 150 g |
How the active output of the KFD2-ST3-Ex2 behaves
Each input of the KFD2-ST3-Ex2 is monitored for the NAMUR current band and, if enabled, for wire break and short-circuit. The output transistors are supplied from the 24 V rail: when active, the output terminal sits at roughly the supply voltage minus 3 V at full 100 mA load, and when blocked it leaks no more than 10 µA. This allows direct drive of PLC inputs of the sinking type, small relays, or indicator lamps.
Faults are shown on LEDs following NAMUR NE44 and signalled to the shared error line of the Power Rail. DIP switches select the output action and line fault detection for each channel. Because the supply sets the output level, any supply sag below 19 V reduces the output voltage and can trip a sensitive PLC input, so confirm rail voltage during commissioning.
Where it fits and which parts are related
Use the KFD2-ST3-Ex2 when the receiving device has no supply of its own on that input, for instance a hard-wired alarm panel or a sinking PLC card. If the control card needs its own field voltage, move to the KFD2-SOT3-Ex2, and where a potential-free relay is required choose the KFD2-SR2-Ex2.W. All three share the 20 mm housing, so a layout change is easy.
Selection and ordering checklist
- Confirm that both field devices are NAMUR sensors or resistor-wired contacts.
- Check the receiving device can accept a supply-fed 24 V transistor output up to 100 mA.
- Confirm the rail voltage stays within 19 to 30 V DC.
- Check sensor Ex ia entity values against Uo, Io and Po.
- Confirm normal or reversed action per channel.
- Allow for the 0.9 W dissipation when sizing panel heat load.
Installation and maintenance of the KFD2-ST3-Ex2
Clip the module on a DIN rail, wire the field cables to the blue terminals and the output terminals to the control side, and set the DIP switches. During commissioning, simulate loop break and short, verify the LED indications, and check the output voltage under real load. Keep ventilation space around the module in warm cabinets, because the -20 to 60 °C range is measured at the module.
Hazardous-area data and isolation of the KFD2-ST3-Ex2
The input of the KFD2-ST3-Ex2 is intrinsically safe Ex ia with Uo 10.5 V, Io 17.1 mA and a linear Po of 45 mW, so the sensor and cable parameters must stay within those limits. The marking II 3(1)G Ex nA [ia Ga] IIC T4 Gc allows the module itself in Zone 2 while the sensor loop may reach Zone 0, and the dust and mining markings listed on the datasheet extend this to dust atmospheres and Group I. Certificate reference EXA 16 ATEX 0016 X carries special conditions of use that should be read from the certificate before installation.
Between input and output and between input and supply the module provides reinforced insulation for 300 Veff under IEC/EN 61010-1, and safe electrical isolation with a 375 V peak value under IEC/EN 60079-11 for the intrinsically safe circuit. The practical meaning is that a fault on the 24 V rail or on the output side cannot place hazardous energy on the field cable.
Typical applications in Oman and the GCC
The KFD2-ST3-Ex2 is used where small panels collect many NAMUR signals: well pad junction cabinets, pump station limit switches, LNG and gas plant packaged skids, and utilities in power and desalination plants. Two channels per slot reduce rack cost in large instrument rooms.
Family comparison
| Part | Key difference |
|---|---|
| KFD2-ST3-Ex2 (this part) | 2 channels, active supply-fed outputs |
| KFD2-SOT3-Ex2 | 2 channels, passive outputs |
| KFD2-SOT3-Ex1.LB | 1 channel, 2 passive outputs |
| KFD2-SR2-Ex2.W | 2 channels, relay outputs |
Information to send with an RFQ
- Part number KFD2-ST3-Ex2 and quantity
- Sensor models and entity data
- Receiving device and input type
- Zone and gas group
- Rail or discrete supply
- Delivery location
Documents and quotation
The manufacturer datasheet for KFD2-ST3-Ex2 is attached on this page, so you can check wiring, approvals and dimensions before ordering. Send the exact part number, quantity and delivery location in Oman or the GCC and Seven Star LLC will reply with a quotation.
Seven Star LLC is an independent supplier in Muscat and is not the manufacturer; confirm availability, lead time and any project approval requirements in your RFQ.
Other Models in the Pf Kfd2 Sot3 Range
Seven Star LLC supplies models from the Pf Kfd2 Sot3 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Pepperl+Fuchs KFD2-SOT3-Ex2 2-Channel Switch Amplifier | Isolator & Barrier | View details |
| Pepperl+Fuchs KFD2-SOT3-Ex1.LB Switch Amplifier | Isolator & Barrier | View details |
| Pepperl+Fuchs KFD2-ST3-Ex2 2-Channel Switch Amplifier | Isolator & Barrier | You are viewing this model |
Datasheets & Documents
- Datasheet Pepperl+Fuchs KFD2-ST3-Ex2 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Pepperl+Fuchs is a German manufacturer of industrial sensors and explosion protection equipment, founded in 1945 in Mannheim by Walter Pepperl and Ludwig Fuchs as a radio repair shop. Defective transformers led them into manufacturing, and the company developed its first proximity switch in the late 1950s. Pepperl+Fuchs is headquartered in Mannheim and is a pioneer of intrinsically safe electrical equipment for hazardous areas.
Seven Star LLC lists Pepperl+Fuchs sensors, isolated barriers, power supplies and hazardous-area mobile devices, and supplies them to instrument and automation teams in Oman by exact model designation.
Pepperl+Fuchs company profile
| Founded | 1945, Mannheim-Sandhofen, Germany, by Walter Pepperl and Ludwig Fuchs |
|---|---|
| Headquarters | Mannheim, Germany |
| Ownership | Privately owned (Pepperl+Fuchs SE) |
| Origins | Radio repair workshop that began making replacement transformers |
| Product families | Inductive, capacitive, ultrasonic and photoelectric sensors, rotary encoders, R2000 LiDAR scanners, KFD and HiC isolated barriers, Zener barriers, remote I/O, purge and pressurization systems, Ex-rated enclosures |
Milestones
- 1945: Walter Pepperl and Ludwig Fuchs open their radio repair shop in Mannheim.
- 1958: The first proximity switch is developed (some company sources say 1959).
Pepperl+Fuchs product families on this page
On the interface side there are two systems. The K-System mounts on DIN rail and is represented here by the KFD2-UT2-Ex2 universal temperature converter. The H-System plugs into termination boards and is represented by the HiD2030 SMART transmitter power supply with HART. The PS1000-A6-24.20 is a 24 VDC, 20 A power supply for cabinets. Sensors listed include the NJ2-12GK-SN NAMUR inductive sensor, the R101 retro-reflective photoelectric sensor and the R2000 2-D LiDAR scanner. For field staff there are the Tab-Ex 05 DZ1 tablet for Zone 1/21 areas and the Smart-Ex 03 DZ2 smartphone for Zone 2/22 and Division 2 areas.
Where Pepperl+Fuchs equipment is used
Isolated barriers sit between field instruments in Zone 0 or Zone 1 and the DCS or safety system in refineries, gas plants and chemical works. NAMUR sensors report valve position and machine states in classified areas. Photoelectric sensors and LiDAR scanners work in conveying, packaging, warehousing and vehicle guidance. Ex-rated tablets and phones are carried on operator rounds and maintenance jobs.
Pepperl+Fuchs products we list
Ordering Pepperl+Fuchs parts: what we need
Send the complete model designation as printed on the device, including every suffix; a single letter can change the supply voltage or the output type. Add the part number if the label shows one. For barriers, tell us the field device and signal type, the number of channels and whether the safety loop needs a SIL-assessed module. For mobile devices, state the zone or division and the regional radio version.
Facts checked against Pepperl+Fuchs's own chronicle pages, October 2026.
Browse Pepperl+Fuchs products by category: Sensors & Transmitters, Industrial Computer, Isolator & Barrier, Power Modules.
FAQ
Questions about the Pepperl+Fuchs KFD2-ST3-Ex2 2-Channel Switch
Answers from our engineering team on installation, compatibility and integration.
01What makes the KFD2-ST3-Ex2 different from the passive version?
Its transistor outputs take their voltage from the module supply and deliver supply minus about 3 V at 100 mA, so no external voltage is needed on the output side.
02How many channels does it have?
Two independent channels, each with a NAMUR input and its own output. Inputs are on terminals 1+, 2+, 3- and 4+, 5+, 6-.
03What load can the outputs drive?
Up to 100 mA at 30 V DC rating. In the blocked state the leakage is at most 10 µA.
04Is line fault detection available?
Yes. Breakage below 0.1 mA and short-circuit above 6.5 mA are detected and can be switched off by DIP switches.
05What is the power consumption?
The datasheet gives power dissipation up to 900 mW including output dissipation, with supply 19 to 30 V DC.


















Reviews
There are no reviews yet.