Brand:

Danfoss 131B8972 FC 202 AQUA Drive 7.5 kW 380-480 V IP55

Description

FC 202 7.5 kW in IP55: a pump drive for a wall-mounted booster station

The 131B8972 is an FC-202P7K5T4E55H1XG: 7.5 kW (10 HP), 380 to 480 V, IP55 / Type 12 and the A5 frame. Because the housing is IP55 the drive can hang on the wall of a pump house or a pumping station next to the motor, which saves a cabinet and shortens the motor cable.

Store data: 16 A continuous, 24 A for 60 s at high overload, 17.6 A at normal overload, 11.1 kVA and a loss of 225 W. Mass is 12.49 kg.

Technical specifications

Parameter Specification
Danfoss code number 131B8972
Type code FC-202P7K5T4E55H1XGXXXXSXXXXAXBXCXXXXDX
Series VLT AQUA Drive FC 202
Power rating 7.5 KW / 10 HP
Mains voltage 380 – 480 VAC
Enclosure IP55 / Type 12
RFI filter RFI Class A1/B (C1)
Brake chopper / safe stop No brake chopper
Control panel / display Graphical Loc. Cont. Panel
PCB coating Not coated PCB
Mains option No Mains Option
B option No B Option
Frame size A5
Dimensions 420 x 242 x 200 mm (H x W x D)
Continuous current, high overload 16 A
Intermittent current, high overload 24 A
Continuous current, normal overload 16 A
Intermittent current, normal overload 17.6 A
Apparent power 11.1 kVA
Power loss 225 W
Net weight 12.49 kg
EAN = 5702427379527

Pumping duty and the overload rating

Centrifugal pumps are normally run at the lighter normal-overload rating, with 110 % current for a minute, while positive-displacement pumps and screw pumps need the high-overload rating with 150 %. Because this drive publishes both ratings, the same code can serve a booster pump or a progressive-cavity pump, but the motor current has to be checked against the figures in the table.

The AQUA guide includes a cascade controller for several pumps, a sleep mode to stop the pump when demand is low, short-cycle protection and a broken-belt detection. Those functions are set through parameters, not extra hardware.

Mounting an IP55 drive in a hot climate

IP55 does not mean unlimited ambient temperature. The guide gives derating curves, and an IP55 drive mounted in direct sun on a Gulf site can overheat. Shade the drive and keep the free space around the heat sink. The type code has the coat position X, so the boards are not conformal coated; for a coastal or chemically aggressive site ask for a coated variant.

The drive is 420 x 242 x 200 mm (H x W x D) in the A5 frame, the same footprint as the 4 kW FC 102 in the HVAC line, which helps if you standardise a panel layout.

Commissioning a pump drive starts with the motor nameplate data, followed by a short automatic motor adaptation, the ramp times and the minimum speed that keeps the pump cooled and lubricated. Set the minimum speed deliberately, as a pump run too slowly can overheat its seal. Record the final parameter set with the date and the engineer name.

We prefer to confirm the application before quoting 131B8972: the medium or load, the supply or pressure, the ambient temperature and the standards that apply. A short message with these points avoids the wrong variant being ordered and keeps the project schedule safe.

Ordering notes

Confirm supply, motor data and enclosure before ordering. Seven Star LLC is an independent supplier in Muscat and can quote 131B8972 against your data. The attached file is the Danfoss FC 202 operating guide AQ267037400115; related drives are under AC drives.

Datasheets & Documents
  • PDF Operating Guide Danfoss VLT AQUA Drive FC 202 Operating Guide AQ267037400115, 0.25-90 kW (manufacturer, unaltered) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Danfoss is the Danish engineering group that makes refrigeration and air-conditioning controls, heating components, variable speed drives and mobile hydraulics. Mads Clausen founded it on 1 September 1933 at his parents' farm in Nordborg on the island of Als, after making his first refrigeration expansion valve in 1932. Nordborg is still the group's headquarters, and Danfoss remains controlled by the Clausen family through the Bitten & Mads Clausen Foundation.

Danfoss company profile

Founded 1 September 1933, Nordborg, Denmark, by Mads Clausen (1905–1966)
First product Thermostatic expansion valve for refrigeration
Headquarters Nordborg, Denmark
Ownership Private; majority controlled by the Bitten & Mads Clausen Foundation and the Clausen family
Size About 42,000 employees (2023)
Business segments Danfoss Climate Solutions (refrigeration, air conditioning and heating), Danfoss Drives (VLT and VACON frequency converters, soft starters), Danfoss Power Solutions (mobile and industrial hydraulics)
Brands in the group VLT, VACON, Eaton Hydraulics (bought 2021), Ikusi radio remote controls

Milestones

  • 1932–1933: First expansion valve; the company is founded in Nordborg.
  • 1939: 26 employees. By the 10th anniversary in 1943 the company has 179.
  • 1950s: Rapid growth turns Nordborg into a Danfoss town with housing and schools for its workforce.
  • 1968: Danfoss launches its VLT frequency converter, one of the first mass-produced AC drives.
  • 2014: Acquisition of the Finnish drives maker Vacon, now the VACON brand.
  • 2021: Acquisition of Eaton's hydraulics business.

Choosing Danfoss products

For solenoid valves, check the operating principle. A direct-operated valve such as EV210B opens even at 0 bar differential pressure. A servo-operated valve such as EV220B needs a minimum differential (typically about 0.3 bar) to open, while an assisted-lift valve such as EV250B works from 0 bar. Coils are ordered separately, so the voltage on the coil (for example 230 V AC or 24 V DC) must match the control circuit. For drives, the VLT family is split by application: FC 51 Micro Drive for small machines, FC 102 HVAC Drive for fans and pumps in buildings, FC 202 AQUA Drive for water, and FC 302 AutomationDrive for demanding industrial duty.

Where Danfoss products are used

In Oman and the GCC, Danfoss drives run pumps, fans and compressors in district cooling plants, water and wastewater stations, desalination and building HVAC. Danfoss pressure switches, transmitters and solenoid valves are built into chillers, refrigeration plants, boilers and hydraulic systems, and AB-QM valves balance chilled-water circuits in large buildings.

Danfoss products we list

Family Examples
Variable speed drives and soft starters VLT Micro Drive FC 51, VLT HVAC Drive FC 102, VLT AQUA Drive FC 202, VLT AutomationDrive FC 302, FC 280, iC2-Micro, VACON NXP, MCD 600 soft starter
Solenoid valves and coils EV220B, EV210B, EV250B, EV225B steam, EVR 25, AM230C coil
Pressure switches and thermostats KP 37, KP 44, RT 200, CS, MBC 5000, KPS 77, RT 101
Pressure transmitters MBS 3000, MBS 5100, MBS 3250, MBS 4251 Ex, AKS 33, DST P92S SIL 2
HVAC and refrigeration valves AB-QM PICV, NovoCon S, AB-PM, AVTA, ICV, TE 5 element

Ordering Danfoss products: what we need

Send the Danfoss code number from the label (for example 032U7115 or 131B0149) or the full drive type code (FC-302P3K0T5...). For drives, add the motor power, supply voltage and any fieldbus option. For valves, add the size, connection, medium and coil voltage. For pressure switches and transmitters, add the range, output and pressure connection.

Facts checked against Danfoss's company history pages and published company data, October 2026.

Frequently Asked Questions

What is Danfoss 131B8972?
An FC-202P7K5T4E55H1XG AQUA drive: 7.5 kW, 380-480 V, IP55 / Type 12, A5 frame.
Why does it show two current ratings?
The drive has dual power ratings: high overload and normal overload, with different intermittent currents.
Can it control several pumps?
The guide includes a cascade controller parameter group for multi-pump control.
Are the boards coated?
No, the type code shows an uncoated board.
Which document is included?