Finder 62.32.9.024.4800 16 A Magnetic Blow DC Power Relay
Description
A 16 A power relay built for switching DC loads
The 62.32.9.024.4800 is a two-pole power relay from the Finder 62 series in the magnetic blow version. Both poles are normally open, rated 16 A at 250 V AC, and a permanent magnet in the contact chamber drives the arc away from the contacts so the relay can break direct current loads far above what an ordinary 16 A relay manages. The coil is 24 V DC and the terminals are plug-in or Faston 187 (4.8 x 0.5 mm).
Ordinary relay contacts that break DC at 125 or 220 V struggle because a DC arc does not extinguish at a current zero. The magnetic blow version of the 62.32 is rated 16 A / 12 A / 6 A resistive (DC1) at 24 / 125 / 220 V, and 10 A / 2 A / 1.2 A for inductive loads (L/R = 40 ms) at the same voltages. The standard 62.32 is rated only 0.6 A at 110 V DC, so the magnetic version is the one to specify for battery-fed and other DC-bus load switching.
Technical specifications
| Parameter | Specification |
|---|---|
| Order code | 62.32.9.024.4800 |
| Decoding | 62 series; 3 = plug-in; 2 = 2 pole; 9 = DC coil; 024 = 24 V; contact material 4 = AgSnO2; contact circuit 8 = NO with magnetic blow; option 0 and special version 0 = standard |
| Contact configuration | 2 NO (DPST-NO), contact gap at least 2.1 mm |
| Rated current / peak current | 16 A / 30 A |
| Rated voltage / maximum switching voltage | 250 V AC / 400 V AC |
| Rated load AC1 | 4000 VA |
| DC1 breaking capacity (24 / 125 / 220 V) | 16 A / 12 A / 6 A |
| DC inductive breaking capacity (L/R 40 ms; 24 / 125 / 220 V) | 10 A / 2 A / 1.2 A |
| Minimum switching load | 1000 mW (10 V / 10 mA) |
| Contact material | AgSnO2, cadmium free |
| Coil | 24 V DC nominal; operating range 20.4 to 26.4 V; resistance 445 ohm; 54 mA; 1.3 W |
| Holding / drop-out voltage | 0.6 UN / 0.1 UN |
| Operate / release time | 16 ms / 5 ms |
| Mechanical life | 10 million operations |
| Electrical life at rated load DC1 | 100,000 operations |
| Insulation, coil to contacts | Reinforced, 6 kV (1.2/50 microseconds), 6 mm clearance and 8 mm creepage |
| Dielectric strength, open contacts | 2000 V AC (2.5 kV impulse) |
| Ambient temperature | -40 to +70 degC |
| Environmental protection | RT I |
| Power lost to the environment | 1.3 W without contact current; 3.3 W at rated current |
| Vibration / shock resistance | 20 g (10 to 150 Hz) / 15 g |
Choosing the magnetic blow version
The 62.32 type exists in several forms: the standard 2 CO and 2 NO versions with AC or DC coils, a 3-pole 62.33, PCB 62.22 and 62.23 types, and the Faston 250 flange types 62.82 and 62.83. The 4800 code is the one with a magnet fitted, available as 1 pole double break (62.31-4800) or 2 pole (62.32-4800), always with a DC coil.
The datasheet gives separate maximum DC breaking capacity curves for the 62.31 and 62.32 magnetic blow versions, and the load voltage and current should be checked against those curves rather than only against the table figures. Where the load is AC only, the standard 62.32 without magnetic blow is the simpler choice.
Sockets and what to confirm before ordering
The 62.32 plugs into the 92.03 box clamp socket (16 A, 250 V, 35 mm rail or panel mount) with a metal retaining clip, identification tags and 99.02 coil indication or EMC modules as accessories. PCB sockets 92.13 and panel solder sockets 92.33 are also listed. Confirm the DC voltage and whether the load is resistive or inductive, then read the DC breaking curve in the datasheet for that voltage. For other relays and interface items browse the automation accessories category.
How the Finder 62.32.9.024.4800 works
A 24 V DC current flows through the coil and pulls the armature in. The armature closes two normally open contacts, which carry the load. When the load is DC and the contacts open, an arc forms and does not die away on its own. In this relay a permanent magnet sits in the contact chamber. Its field pushes the arc away from the contacts and into a space where it stretches and goes out. This is why the relay can break DC loads at 125 or 220 V.
Where the 62.32.9.024.4800 is used
- Battery-fed DC load switching
- DC bus control circuits
- Solenoid and contactor coil circuits
- Switchgear and substation panels
- Industrial control panels
Selection checklist for the 62.32.9.024.4800
- Load voltage and current in DC
- Resistive or inductive load
- Coil voltage of 24 V DC
- Terminal type: plug-in or Faston 187
- Contact arrangement: two normally open
- Socket or mounting type
- Magnet polarity of the load wiring
- Ambient temperature
Installation, commissioning and maintenance notes for the 62.32.9.024.4800
Plug the relay into a matching socket or fit it with Faston terminals. Wire the DC load as the datasheet shows, because the magnet needs the right current direction to push the arc the right way. Keep the coil voltage in the stated range. Check the contacts after long service on heavy loads.
Requesting a quotation for the Finder 62.32.9.024.4800
Please send the full order code, the socket needed and the quantity. Seven Star LLC serves industrial customers in Oman and the GCC and replies with a quotation based on the information provided.
62.32.9.024.4800 contact data
Both poles are normally open, rated 16 A at 250 V AC with a peak current of 30 A.
62.32.9.024.4800 DC breaking capacity
Resistive DC breaking is 16 A at 24 V, 12 A at 125 V and 6 A at 220 V.
62.32.9.024.4800 inductive loads
Inductive breaking is 10 A, 2 A and 1.2 A at the same three voltages with L/R of 40 ms.
62.32.9.024.4800 coil
The coil runs on 24 V DC with a range of 20.4 to 26.4 V and takes 1.3 W.
62.32.9.024.4800 timing
Operate time is 16 ms and release time is 5 ms.
62.32.9.024.4800 life
Mechanical life is 10 million operations. Electrical life at rated DC load is 100,000.
62.32.9.024.4800 contact material
The contacts are silver tin oxide and are cadmium free.
Relay records for the 62.32.9.024.4800
Record the order code, the load data and the date of installation.
Choosing the right 62.32.9.024.4800 relay
Choose the magnetic blow version whenever the load is DC at 110 V or more. The standard version is not rated for it.
Documents and quotation
The Finder 62 series datasheet (IX-2026 edition) is attached. It contains the ordering codes, coil tables for the magnetic blow version, DC breaking capacity curves, outline drawings and socket data. Please send the order code, quantity and delivery location through the quotation form for availability from Seven Star LLC.
Datasheets & Documents
- Datasheet Finder 62 series datasheet (EN, IX-2026) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Finder is an Italian manufacturer of relays, timers and other electromechanical and electronic devices for industry and buildings. It was founded in 1954 by Piero Giordanino, who had patented a step relay in 1949, and it is headquartered in Almese, Piedmont, where most of its manufacturing still takes place. Finder is owned and run by the Giordanino family.
Seven Star LLC is an independent supplier in Muscat. We list Finder relays, power supplies and protection devices for control panels, building services and machine automation in Oman and the GCC.
Finder company profile
| Founded | 1954, Italy, by Piero Giordanino |
|---|---|
| Headquarters | Almese, Piedmont, Italy; more than 70 % of manufacturing is done there |
| Ownership | Giordanino family |
| Range | More than 14,000 product types, according to the company |
| Product families | Industrial relays (series 40, 46, 55, 60), interface relay modules (34, 38, 39), timers (80, 85), monitoring relays (70, 71), surge protection (7P), switch-mode power supplies (78), thermostats and panel fans |
Milestones
- 1949: Piero Giordanino patents his first step relay.
- 1954: Finder is founded.
- 1965: The plant in Almese opens.
- 1966: The Series 60 industrial relay is launched.
Finder product series
Relays include the 46.61 miniature industrial relay, the 62.32 power relay with magnetic blow-out for DC loads, the 38.51 relay interface module and the 7S forcibly guided safety relay. Control relays include the 72.01 liquid level control relay and the 80.01 multi-function modular timer, and the 22.32 modular contactor switches loads up to 25 A.
Power supplies include the 78.12, 78.36, 78.W1, 78.Y1 and three-phase 78.Y3 DIN rail units from 12 W to 480 W, and surge protection includes the 7P.04 Type 1+2 and 7P.45 Type 2 three-phase devices.
Where Finder devices are used
Control panels for machines, pumps and HVAC, distribution boards in commercial and residential buildings, water tank and well level control, lighting control and the protection of electrical installations against surges.
Finder products we list
Ordering Finder products: what we need
Quote the complete ordering code, for example 62.32.9.024.4800, which includes coil voltage and contact variant, together with the quantity, the supply voltage and frequency and any approvals the project requires. With that information the matching Finder version can be confirmed against the datasheet before a quotation is issued.
Facts checked against Finder's own company pages (findernet.com), October 2026.
Browse Finder products by category: Automation Accessories, Power Modules, Contactors & Overload Relays.
FAQ
Questions about the Finder 62.32.9.024.4800 16 A Magnetic Blow DC Power
Answers from our engineering team on installation, compatibility and integration.
01What makes the 62.32.9.024.4800 different from a standard 62.32?
It has a magnetic blow contact system for breaking direct current loads, with 2 normally open contacts and a DC coil only.
02What DC loads can it switch?
Resistive loads up to 16 A at 24 V, 12 A at 125 V and 6 A at 220 V; inductive ratings are lower.
03What is the coil rating?
24 V DC nominal with an operating range of 20.4 to 26.4 V, 445 ohm, 54 mA and 1.3 W.
04Which socket does it use?
The 92.03 box clamp socket for 35 mm rail or panel mounting, among other 92 series sockets.
05How many poles and what contact gap?
Two normally open poles with a contact gap of at least 2.1 mm.