Brand:

Finder 62.32.9.024.4800 16 A Magnetic Blow DC Power Relay

Description

A 16 A power relay built for switching DC loads

The 62.32.9.024.4800 is a two-pole power relay from the Finder 62 series in the magnetic blow version. Both poles are normally open, rated 16 A at 250 V AC, and a permanent magnet in the contact chamber drives the arc away from the contacts so the relay can break direct current loads far above what an ordinary 16 A relay manages. The coil is 24 V DC and the terminals are plug-in or Faston 187 (4.8 x 0.5 mm).

Ordinary relay contacts that break DC at 125 or 220 V struggle because a DC arc does not extinguish at a current zero. The magnetic blow version of the 62.32 is rated 16 A / 12 A / 6 A resistive (DC1) at 24 / 125 / 220 V, and 10 A / 2 A / 1.2 A for inductive loads (L/R = 40 ms) at the same voltages. The standard 62.32 is rated only 0.6 A at 110 V DC, so the magnetic version is the one to specify for battery-fed and other DC-bus load switching.

Technical specifications

Parameter Specification
Order code 62.32.9.024.4800
Decoding 62 series; 3 = plug-in; 2 = 2 pole; 9 = DC coil; 024 = 24 V; contact material 4 = AgSnO2; contact circuit 8 = NO with magnetic blow; option 0 and special version 0 = standard
Contact configuration 2 NO (DPST-NO), contact gap at least 2.1 mm
Rated current / peak current 16 A / 30 A
Rated voltage / maximum switching voltage 250 V AC / 400 V AC
Rated load AC1 4000 VA
DC1 breaking capacity (24 / 125 / 220 V) 16 A / 12 A / 6 A
DC inductive breaking capacity (L/R 40 ms; 24 / 125 / 220 V) 10 A / 2 A / 1.2 A
Minimum switching load 1000 mW (10 V / 10 mA)
Contact material AgSnO2, cadmium free
Coil 24 V DC nominal; operating range 20.4 to 26.4 V; resistance 445 ohm; 54 mA; 1.3 W
Holding / drop-out voltage 0.6 UN / 0.1 UN
Operate / release time 16 ms / 5 ms
Mechanical life 10 million operations
Electrical life at rated load DC1 100,000 operations
Insulation, coil to contacts Reinforced, 6 kV (1.2/50 microseconds), 6 mm clearance and 8 mm creepage
Dielectric strength, open contacts 2000 V AC (2.5 kV impulse)
Ambient temperature -40 to +70 degC
Environmental protection RT I
Power lost to the environment 1.3 W without contact current; 3.3 W at rated current
Vibration / shock resistance 20 g (10 to 150 Hz) / 15 g

Choosing the magnetic blow version

The 62.32 type exists in several forms: the standard 2 CO and 2 NO versions with AC or DC coils, a 3-pole 62.33, PCB 62.22 and 62.23 types, and the Faston 250 flange types 62.82 and 62.83. The 4800 code is the one with a magnet fitted, available as 1 pole double break (62.31-4800) or 2 pole (62.32-4800), always with a DC coil.

The datasheet gives separate maximum DC breaking capacity curves for the 62.31 and 62.32 magnetic blow versions, and the load voltage and current should be checked against those curves rather than only against the table figures. Where the load is AC only, the standard 62.32 without magnetic blow is the simpler choice.

Sockets and what to confirm before ordering

The 62.32 plugs into the 92.03 box clamp socket (16 A, 250 V, 35 mm rail or panel mount) with a metal retaining clip, identification tags and 99.02 coil indication or EMC modules as accessories. PCB sockets 92.13 and panel solder sockets 92.33 are also listed. Confirm the DC voltage and whether the load is resistive or inductive, then read the DC breaking curve in the datasheet for that voltage. For other relays and interface items browse the automation accessories category.

How the Finder 62.32.9.024.4800 works

A 24 V DC current flows through the coil and pulls the armature in. The armature closes two normally open contacts, which carry the load. When the load is DC and the contacts open, an arc forms and does not die away on its own. In this relay a permanent magnet sits in the contact chamber. Its field pushes the arc away from the contacts and into a space where it stretches and goes out. This is why the relay can break DC loads at 125 or 220 V.

Where the 62.32.9.024.4800 is used

  • Battery-fed DC load switching
  • DC bus control circuits
  • Solenoid and contactor coil circuits
  • Switchgear and substation panels
  • Industrial control panels

Selection checklist for the 62.32.9.024.4800

  • Load voltage and current in DC
  • Resistive or inductive load
  • Coil voltage of 24 V DC
  • Terminal type: plug-in or Faston 187
  • Contact arrangement: two normally open
  • Socket or mounting type
  • Magnet polarity of the load wiring
  • Ambient temperature

Installation, commissioning and maintenance notes for the 62.32.9.024.4800

Plug the relay into a matching socket or fit it with Faston terminals. Wire the DC load as the datasheet shows, because the magnet needs the right current direction to push the arc the right way. Keep the coil voltage in the stated range. Check the contacts after long service on heavy loads.

Requesting a quotation for the Finder 62.32.9.024.4800

Please send the full order code, the socket needed and the quantity. Seven Star LLC serves industrial customers in Oman and the GCC and replies with a quotation based on the information provided.

62.32.9.024.4800 contact data

Both poles are normally open, rated 16 A at 250 V AC with a peak current of 30 A.

62.32.9.024.4800 DC breaking capacity

Resistive DC breaking is 16 A at 24 V, 12 A at 125 V and 6 A at 220 V.

62.32.9.024.4800 inductive loads

Inductive breaking is 10 A, 2 A and 1.2 A at the same three voltages with L/R of 40 ms.

62.32.9.024.4800 coil

The coil runs on 24 V DC with a range of 20.4 to 26.4 V and takes 1.3 W.

62.32.9.024.4800 timing

Operate time is 16 ms and release time is 5 ms.

62.32.9.024.4800 life

Mechanical life is 10 million operations. Electrical life at rated DC load is 100,000.

62.32.9.024.4800 contact material

The contacts are silver tin oxide and are cadmium free.

Relay records for the 62.32.9.024.4800

Record the order code, the load data and the date of installation.

Choosing the right 62.32.9.024.4800 relay

Choose the magnetic blow version whenever the load is DC at 110 V or more. The standard version is not rated for it.

Documents and quotation

The Finder 62 series datasheet (IX-2026 edition) is attached. It contains the ordering codes, coil tables for the magnetic blow version, DC breaking capacity curves, outline drawings and socket data. Please send the order code, quantity and delivery location through the quotation form for availability from Seven Star LLC.

Datasheets & Documents
  • PDF Datasheet Finder 62 series datasheet (EN, IX-2026) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Finder is an Italian manufacturer of relays, timers and other electromechanical and electronic devices for industry and buildings. It was founded in 1954 by Piero Giordanino, who had patented a step relay in 1949, and it is headquartered in Almese, Piedmont, where most of its manufacturing still takes place. Finder is owned and run by the Giordanino family.

Seven Star LLC is an independent supplier in Muscat. We list Finder relays, power supplies and protection devices for control panels, building services and machine automation in Oman and the GCC.

Finder company profile

Founded 1954, Italy, by Piero Giordanino
Headquarters Almese, Piedmont, Italy; more than 70 % of manufacturing is done there
Ownership Giordanino family
Range More than 14,000 product types, according to the company
Product families Industrial relays (series 40, 46, 55, 60), interface relay modules (34, 38, 39), timers (80, 85), monitoring relays (70, 71), surge protection (7P), switch-mode power supplies (78), thermostats and panel fans

Milestones

  • 1949: Piero Giordanino patents his first step relay.
  • 1954: Finder is founded.
  • 1965: The plant in Almese opens.
  • 1966: The Series 60 industrial relay is launched.

Finder product series

Relays include the 46.61 miniature industrial relay, the 62.32 power relay with magnetic blow-out for DC loads, the 38.51 relay interface module and the 7S forcibly guided safety relay. Control relays include the 72.01 liquid level control relay and the 80.01 multi-function modular timer, and the 22.32 modular contactor switches loads up to 25 A.

Power supplies include the 78.12, 78.36, 78.W1, 78.Y1 and three-phase 78.Y3 DIN rail units from 12 W to 480 W, and surge protection includes the 7P.04 Type 1+2 and 7P.45 Type 2 three-phase devices.

Where Finder devices are used

Control panels for machines, pumps and HVAC, distribution boards in commercial and residential buildings, water tank and well level control, lighting control and the protection of electrical installations against surges.

Finder products we list

Family Examples
Automation Accessories 38.51.7.024.0050 24 V DC 6 A Relay Inter…, 46.61.9.024.0040 16 A Miniature Industri…, 62.32.9.024.4800 16 A Magnetic Blow DC P…, 72.01.9.024.0000 Liquid Level Control Re…, 7P.04.8.260.1025 Type 1+2 Three-Phase Su…, 7P.45.8.275.1020 Type 2 Three-Phase Surg…, 7S.23.9.024.0210 Forcibly Guided Safety…, 80.01.0.240.0000 Multi-Function Modular…
Power Modules 78.12.1.230.2400 24 V 12 W DIN Rail Powe…, 78.36.1.230.2402 24 V 36 W Modular Power…, 78.W1.1.230.2402 24 V 120 W DIN Rail Pow…, 78.Y1.1.230.2412 24 V 480 W Single-Phase…, 78.Y3.1.440.2414 24 V 480 W Three-Phase…
Contactors & Overload Relays 22.32.0.230.1340 25 A 2 NO Modular Conta…

Ordering Finder products: what we need

Quote the complete ordering code, for example 62.32.9.024.4800, which includes coil voltage and contact variant, together with the quantity, the supply voltage and frequency and any approvals the project requires. With that information the matching Finder version can be confirmed against the datasheet before a quotation is issued.

Facts checked against Finder's own company pages (findernet.com), October 2026.

FAQ

Questions about the Finder 62.32.9.024.4800 16 A Magnetic Blow DC Power

Answers from our engineering team on installation, compatibility and integration.

01What makes the 62.32.9.024.4800 different from a standard 62.32?
It has a magnetic blow contact system for breaking direct current loads, with 2 normally open contacts and a DC coil only.
02What DC loads can it switch?
Resistive loads up to 16 A at 24 V, 12 A at 125 V and 6 A at 220 V; inductive ratings are lower.
03What is the coil rating?
24 V DC nominal with an operating range of 20.4 to 26.4 V, 445 ohm, 54 mA and 1.3 W.
04Which socket does it use?
The 92.03 box clamp socket for 35 mm rail or panel mounting, among other 92 series sockets.
05How many poles and what contact gap?
Two normally open poles with a contact gap of at least 2.1 mm.