Weflo Fig. F1318 UL Pressure Reducing Valve
Description
Pilot-operated pressure reducing valve for fire water systems
The Weflo Fig. F1318 is a UL 1739 listed pressure reducing valve with flanged ends. It takes a high inlet pressure from a fire pump or riser and delivers a lower, constant outlet pressure across a wide flow range, which protects hose connections, sprinklers and risers on the lower floors of tall buildings and in zoned fire water networks. The main valve is pilot-operated, so the set outlet pressure does not fall away as flow increases.
Regulation is stabilised even at near-zero flow, and opening and response speed can be adjusted. The outlet pressure is changed with a single adjusting screw on the pilot. Enamel paint or fusion bonded epoxy coating is applied inside and out.
Technical specifications
Values are from the Weflo Fig. F1318 FLxFL data sheet. The sheet states that 1.5 to 10 in. valves are UL listed.
| Parameter | Specification |
|---|---|
| Type | Pilot-operated pressure reducing valve, flanged by flanged |
| Sizes | DN40 to DN300 |
| End connections | Flanges to EN 1092-2 PN16, ANSI Class 125/150/250; other flanges on request |
| Upstream pressure | 300 psi maximum |
| Downstream pressure ranges | 15 to 60 psi, 35 to 85 psi or 65 to 165 psi, by pilot spring |
| Approvals | UL 1739 listed, 3C certified |
| Body and bonnet | Ductile iron ASTM A536 Grade 65-45-12 |
| Seat, stem and spring | Stainless steel ASTM A276 Type 304 |
| Diaphragm | Nylon-reinforced natural rubber, EPDM or NBR |
| Seat disc | NBR or EPDM |
| Pressure reducing pilot | Bronze ASTM B62 C62300 |
| Pilot circuit | Pressure reducing pilot, ejector, Y-strainer, stabilizer and tubing |
| Coating | Enamel paint or fusion bonded epoxy, interior and exterior |
Main dimensions
| Size | L, mm | H, mm | W, mm |
|---|---|---|---|
| DN40 | 200 | 180 | 410 |
| DN50 | 230 | 200 | 420 |
| DN65 | 290 | 215 | 440 |
| DN80 | 310 | 265 | 455 |
| DN100 | 350 | 290 | 470 |
| DN125 | 400 | 340 | 490 |
| DN150 | 480 | 390 | 540 |
| DN200 | 600 | 470 | 590 |
| DN250 | 730 | 570 | 640 |
| DN300 | 850 | 690 | 690 |
Selection notes
Pick the pilot spring range that includes the required downstream pressure, and check that the inlet pressure never exceeds 300 psi. A reducing valve needs a minimum flow range and correct sizing for the largest hose or sprinkler demand, so the system designer should confirm sizing against the flow curves.
Documents and quotation
The attached data sheet gives the material table, the pilot schematic and dimensions. Send the size, end connections, inlet and outlet pressures, flow rate and quantity when requesting a quotation. See other fire protection valves under Fire Fighting.
Datasheets & Documents
- Datasheet Weflo Fig. F1318 Pressure Reducing Valve FLxFL data sheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Fire protection contractors meet the Weflo name on gate valves, hydrants and check valves for sprinkler and hydrant mains. Weflo Valve is based in Qingdao, China, and makes industrial and fire protection valves. Seven Star LLC lists the Weflo Fig. 1209 flanged balancing valve and supplies Weflo valves for building services and fire water projects in Oman on inquiry.
Weflo valve families
The manufacturer program covers OS&Y and NRS gate valves, fire hydrants, check and alarm check valves, butterfly valves, deluge, pre-action, pressure relief and pressure reducing valves, Y and basket strainers, and air relief valves. Weflo states that its OS&Y and NRS gate valves are UL listed and FM approved through 24 inches. Products are identified by figure number, as with the Fig. 1209 balancing valve in our listing.
Ordering Weflo valves: what we need
Send the figure number, size, end connection and flange standard, pressure rating, the medium, and the listing or approval the project specification demands. Approvals apply per figure and size, so we check each line against the manufacturer datasheet. GCC civil defense requirements should be quoted in the request.
Related products
Frequently Asked Questions
Upstream pressure is a maximum of 300 psi.
Downstream ranges of 15 to 60 psi, 35 to 85 psi and 65 to 165 psi are listed.
UL 1739 listing and 3C certification; the data sheet notes that 1.5 to 10 in. valves are UL listed.
Yes. The outlet pressure is adjusted with a single screw on the pilot.
DN40 to DN300 with flanges to EN 1092-2 PN16 or ANSI Class 125/150/250.