Mitsubishi AX82 Input Module
Description
Mitsubishi AX82 64-point DC input module overview
The Mitsubishi AX82 is a 64-point DC input module for the MELSEC-A large-type PLC family. It reads 12 V DC or 24 V DC signals from field devices such as proximity switches, limit switches, pushbuttons, relay contacts and transistor outputs of other equipment, and passes their ON/OFF state to the CPU through the base unit. Seven Star LLC supplies the Mitsubishi AX82 on request for maintenance teams in Oman and the GCC that keep installed MELSEC-A systems running.
This module belongs to a generation that Mitsubishi Electric has discontinued. It is still found in older machine tools, packaging lines, water and utility panels and process skids that were built around A-series CPUs. Most Mitsubishi AX82 enquiries are therefore for like-for-like replacement of a failed module, for spares held against a critical line, or for planning a migration to a newer platform.
Key features
- 64 input points in a single slot, which makes it a high-density choice for panels with many discrete signals.
- 12/24 V DC rated input, so one module type can serve both voltage levels.
- Photocoupler insulation between the field side and the PLC internal circuit.
- Connector-type external wiring using D-sub style connectors rather than a screw terminal block.
- LED status indication in which one LED covers two points, and a switch selects which block of 32 points is shown.
- Source-loading input arrangement, as listed by distributor documentation; the actual polarity must be confirmed against the manufacturer manual and the existing wiring.
Technical specifications
| Parameter | Specification |
|---|---|
| Model | AX82 |
| PLC family | MELSEC-A large type |
| Number of input points | 64 |
| Rated input voltage | 12/24 V DC |
| Rated input current | Approx. 3 mA at 12 V DC; approx. 7 mA at 24 V DC |
| Operating voltage range | 10.2 – 26.4 V DC |
| Simultaneous ON points | 40 points maximum (26 points when mounted next to the power supply module) |
| Insulation method | Photocoupler |
| Status display | One LED per two points, block of 32 points selected by switch |
| Internal current consumption | 120 mA at 5 V DC |
| External wiring | Connector (D-sub type) |
| Weight | Approx. 0.57 kg |
| Lifecycle status | Discontinued; MELSEC-A/QnA large-type production ended in September 2006 |
Response time, input resistance and ON/OFF threshold values should be confirmed against the manufacturer datasheet for the exact hardware version before they are used in a design calculation.
Operating principle
Each Mitsubishi AX82 input channel passes the field current through a current-limiting resistor and the LED side of a photocoupler. When the field device closes, the photocoupler transistor switches and the module presents an ON state to the PLC bus. The CPU reads the 64 states during its I/O refresh and maps them to X device addresses according to the slot position on the base unit. Because the field circuit and the logic circuit are only coupled optically, noise and ground differences on the field wiring are kept away from the CPU.
The limit on simultaneous ON points comes from heat. Each energised channel dissipates power in its resistor and photocoupler, so the module is rated for 40 points ON at the same time, and fewer (26) when it sits beside the power supply module where the temperature inside the base is higher. Applications where most of the 64 inputs stay ON together should be split across two modules.
Typical applications
- Machine tools and transfer lines with many sensor and limit-switch signals on A-series controllers.
- Conveyor, palletising and packaging equipment that collects photo-eye and position signals.
- Utility panels in pumping stations and treatment plants where an A-series PLC monitors valve feedback and alarms.
- Test rigs and older OEM machines where high input density was needed in a limited number of slots.
Selection and compatibility notes for the Mitsubishi AX82
The Mitsubishi AX82 sits in a family of related references, and the suffix matters. For example, the AX81 is the 32-point terminal-block version, and suffixed versions differ in voltage or input characteristics. Always order against the full code printed on the module label, not against the point count alone.
- Check the base unit and CPU type so that the replacement module is recognised in the same slot and I/O assignment.
- Check the connector cables. The Mitsubishi AX82 is wired through connectors, so the existing cable sets or interface terminal blocks are normally reused.
- Confirm the field supply voltage. The rated range covers 12 V DC and 24 V DC systems.
- Count how many inputs are ON together in normal operation, and check the result against the simultaneous ON limit.
Installation and commissioning
Switch off the PLC power and the external 12/24 V DC supply before removing or fitting the module. Seat the module fully on the base connector and tighten the fixing screw. Reconnect the connector cables in the same orientation as before, and check that the common and supply wiring match the drawings. After power-up, use the LED display and the block-select switch to confirm that each field signal appears on the expected point, and check the X addresses in the programming software monitor before returning the machine to automatic operation.
Mitsubishi AX82 maintenance and troubleshooting
- No LED on a point: measure the field voltage at the connector, check the common connection and confirm that the correct 32-point block is selected for display.
- LED on but no signal in the program: check the slot assignment, the I/O allocation parameters and the base connector.
- Intermittent inputs: look for leakage current from two-wire sensors, damaged connector pins and voltage drop on long runs. The 10.2 V DC lower limit is easy to reach on a 12 V DC system with long cables.
- Module running hot: reduce the number of simultaneously ON points, or move the module away from the power supply slot.
Mitsubishi AX82 legacy and replacement notes
According to Mitsubishi Electric bulletin T99-0050, production of MELSEC-A/QnA large-type modules ended in September 2006. Repair was accepted until September 2013, and spare-part production was extended to September 2008. Units offered today are therefore surplus, refurbished or used units held in the market, and their condition must be agreed for each order.
For migration to the MELSEC-Q series, the same bulletin maps the Mitsubishi AX82 to the QX82, with the following points:
- The external wiring changes from a D-sub connector to an FCN connector.
- The slot count and the number of occupied I/O points stay the same.
- The QX82 does not accept 12 V DC input. The QX72 is named instead for 12 V DC systems.
- The rated input current and the ON/OFF characteristics change, so field devices with high leakage should be reviewed.
For the AnS compact series, the bulletin names the A1SX82-S1 with an A1ADP-XY adapter. Its 5 V DC consumption is 160 mA, against 120 mA for the Mitsubishi AX82, so the power supply budget should be rechecked.
Quotation enquiries for Oman and the GCC
Seven Star LLC supplies the Mitsubishi AX82 on request. Availability, condition (new surplus, used or refurbished) and lead time are confirmed at quotation. For an accurate offer, please send the following:
- The exact reference from the module label, including any suffix and hardware version.
- The quantity required, and whether the units are for an immediate repair or for spares.
- A clear photograph of the nameplate and of the connectors.
- The CPU and base-unit references, and a short description of the application.
- Whether you are also considering migration to the QX82 or QX72, so that technical support with selection and cross-checking of the reference can be given.
See also: Mitsubishi TH-T25 Thermal Overload Relay, 0.2 to 26 A; Mitsubishi A68RD4 Temperature Input Module.
Datasheets & Documents
- Manual A Series Hardware Manual — IB66542-J Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Mitsubishi Electric is the Japanese electrical and electronics manufacturer whose factory automation range includes MELSEC programmable controllers, GOT operator panels, MELSERVO servo systems, FR inverters and low-voltage switchgear. It was established on 15 January 1921, when the electrical machinery works of Mitsubishi Shipbuilding in Kobe became a separate company. Mitsubishi Electric Corporation is headquartered in Tokyo and listed on the Tokyo Stock Exchange.
Laboratories that run an NSX-2100 trace sulfur, nitrogen or chlorine analyzer usually know it as a Mitsubishi instrument. The nameplate reads Mitsubishi Chemical Analytech, a name later changed to Nittoseiko Analytech. Seven Star LLC lists the TN6RPC gas tube dryer set for this analyzer and sources NSX-2100 consumables for refinery and fuel-testing laboratories in Oman and the GCC.
The Mitsubishi listing also includes Mitsubishi Electric factory automation and drive products: MR-J3, MR-J5 and MR-JE servo amplifiers, GOT2000 and GOT SIMPLE HMI touch panels, FR-A800, FR-E800, FR-F800 and FR-CS80 FREQROL inverters, MELSEC iQ-F PLC modules, MELSEC A-series input and temperature modules with a memory cassette, and S-T magnetic contactors and TH-T thermal overload relays.
Mitsubishi company profile
| Established | 15 January 1921, from the electrical works of Mitsubishi Shipbuilding in Kobe, Japan |
|---|---|
| Headquarters | Tokyo, Japan |
| Ownership | Mitsubishi Electric Corporation, public company listed on the Tokyo Stock Exchange; a member of the Mitsubishi group of companies |
| Product families | MELSEC iQ-R, iQ-F and Q series PLCs, GOT2000 HMIs, MELSERVO MR-J5 and MR-JE servo amplifiers and motors, FR series inverters, S-T magnetic contactors and TH-T thermal overload relays, circuit breakers |
| Note | Laboratory analysers sold under the Mitsubishi Chemical Analytech name (now Nittoseiko Analytech) come from a different Mitsubishi company |
Mitsubishi NSX-2100 parts
The NSX-2100 was built with a horizontal or a vertical furnace, and one furnace can serve several detectors. The dryer set removes water from the combustion gas before it reaches the detector. Like the connection kits, it is a consumable, and its part code changes with the analyzer variant.
Mitsubishi products we list
Ordering NSX-2100 consumables: what we need
Send the part code, for example TN6RPC, together with the exact analyzer model shown on the nameplate (the letters after NSX-2100 indicate furnace type and detectors), the serial number and the detectors fitted. Some original part codes have been replaced by newer ones, so we check each code against the manufacturer's current parts list before quoting.
Facts checked against Mitsubishi Electric's published corporate profile, October 2026.
Browse Mitsubishi products by category: Gas Analyzer Accessories.
FAQ
Questions about the Mitsubishi AX82 Input Module
Answers from our engineering team on installation, compatibility and integration.
01How many inputs does the Mitsubishi AX82 have and what voltage does it accept?
It has 64 DC input points rated for 12/24 V DC, with an operating range of 10.2 to 26.4 V DC.
02How many AX82 inputs can be ON at the same time?
Up to 40 points can be ON simultaneously, or 26 points when the module is mounted next to the power supply module.
03Is the AX82 still in production?
No. Mitsubishi Electric bulletin T99-0050 states that MELSEC-A/QnA large-type production ended in September 2006, and that repair acceptance ended in September 2013.
04What is the MELSEC-Q replacement for the AX82?
The bulletin maps it to the QX82, which uses an FCN connector instead of a D-sub and does not accept 12 V DC. The QX72 is named for 12 V DC systems.
05How much 5 V DC current does the AX82 draw from the base?
The internal current consumption is 120 mA at 5 V DC.