Brand:

DUNGS MB-DLE 407 B01 S50 GasMultiBloc Rp 3/4, 230 V

Description

Overview

The DUNGS MB-DLE 407 B01 S50 is one specific size and version of the Karl Dungs GasMultiBloc: a compact fitting that combines a dirt trap, a pressure regulator and two safety shut-off solenoid valves in a single aluminium body. The 407 designation means a DN 20 body with a double-seat second valve, B01 means one regulator and two Class A valves for single-stage operation, and S50 means both valves are switched together with an outlet pressure range of 4 to 50 mbar. Fitted with Rp 3/4 flanges and a 230 V coil set, this is the gas train used on many commercial forced-draught burners in the 60 to 320 kW class, including the Bentone BG 400 single-stage burner.

Seven Star LLC supplies the DUNGS MB-DLE 407 B01 S50 to boiler service contractors, burner builders and plant maintenance teams in the Sultanate of Oman and across the GCC, with engineering support in Muscat. The wider family, covering the 405, 410 and 412 sizes, is described on our Dungs MB-DLE 405-412 B01 GasMultiBloc Combined Regulator and Safety Valves page; this page focuses on the exact 407 B01 S50 configuration that is most often requested as a direct replacement on installed burners.

Operating Principle

Gas enters the inlet flange and first passes a fine mesh-sieve that protects the valve seats and the regulator diaphragm from pipeline debris. Valve V1 is a fast-opening, fast-closing solenoid valve to DIN EN 161 Class A Group 2. Downstream of V1 the proportional regulator, built to DIN EN 88 Class A Group 2 and compensated for residual pressure, holds the burner-side pressure at the value set on the spring. In the S50 version the fixed setpoint spring covers 4 to 50 mbar, which suits burners fed from a normal low-pressure supply and needing a relatively high head pressure at full load. When the burner stops, V1 provides the leak-tight closure for the regulator, and because an internal pulse tap is fitted, no vent line above the roof is needed.

Valve V2 in the DUNGS MB-DLE 407 closes fast but opens slowly. A hydraulic brake delays the opening, and the datasheet gives an opening time of up to 20 seconds for MB-DLE versions, while the main volume restrictor on V2 limits the maximum flow. The Bentone BG 400 manual describes the same arrangement as slow-opening valves with adjustable start load and maximum flow. In practice the DUNGS MB-DLE 407 gives a soft, controlled light-off with less pressure surge in the combustion chamber, which reduces nuisance flame failures and mechanical stress on the burner head and boiler.

Engineering Design of the DUNGS MB-DLE 407

The housing of the DUNGS MB-DLE 407 is aluminium die casting; diaphragms and seals are NBR-based with Silopren silicone rubber, and the solenoid drive is made of steel, brass and aluminium. The 405 and 407 bodies share the same outer dimensions, so the 407 can take Rp 1/2 or Rp 3/4 flanges and combinations of the two; the version on this page uses Rp 3/4 threads to ISO 7/1. The dimension table for the MB-DLE 405/407 gives dimension a as 110 mm, b as 151 mm and h as 115 mm, plus a 185 mm space requirement for exchanging the solenoid, and a weight of 2.6 kg. The difference between a 405 and a 407 is the second valve: a single seat in the 405 and a double seat in the 407, which gives the 407 a higher flow for the same body size.

Electrical connection of the DUNGS MB-DLE 407 is by plug to DIN EN 175301-803 for the valves and any mounted pressure switch, supplied at 220 to 230 V AC, 50 to 60 Hz, with a tolerance of minus 15 to plus 10 percent. For the 405/407 S50 the rated power consumption is 36 VA at 230 V and 20 degrees Celsius, the switch-on duration is 100 percent and the enclosure is IP 54. Measuring and ignition gas connections are G 1/8 screw plugs, there is a test nipple on the inlet side, and a GW A5 or GW A2 pressure switch can be mounted directly on the block. The DUNGS MB-DLE 407 may be installed with the solenoid upright, horizontal or at any position in between.

Key Features

The DUNGS MB-DLE 407 B01 S50 brings the following practical advantages to a single-stage burner gas train:

  • The filter, regulator and two Class A safety valves are combined in one short, light assembly instead of four separate components.
  • The S50 regulator spring gives an outlet pressure range of 4 to 50 mbar with a maximum operating pressure of 360 mbar.
  • The double-seat V2 of the 407 size delivers more flow than the single-seat 405 in the same compact DN 20 housing.
  • A hydraulic opening delay and a main volume restrictor on V2 give a smooth, adjustable light-off.
  • Both valves are controlled together in the S50 version, so a single valve output from the burner control is sufficient.
  • An internal pulse tap removes the need for an external impulse line or a vent line to atmosphere.
  • A minimum gas pressure switch and a VPS 504 valve proving system can be added within the modular system.
  • EU type examination covers the Gas Appliances Regulation and the Pressure Equipment Directive.

Industrial Applications

The DUNGS MB-DLE 407 is fitted on forced-draught gas burners for hot water and steam boilers, air heaters, dryers, bakery ovens and similar process heat equipment. It is suitable for gases of families 1, 2 and 3 and other neutral gaseous media, which covers natural gas and gaseous LPG. The datasheet notes that in liquid gas systems the unit must not be operated below 0 degrees Celsius and is only suitable for the gaseous phase; the ambient range is minus 15 to plus 70 degrees Celsius, which suits enclosed boiler rooms in the Gulf climate.

In Oman these gas trains are found in hotel, hospital and laundry boiler houses in Muscat, in food processing plants in Rusayl and Sohar, and in process heaters in Salalah. Seven Star LLC supplies the DUNGS MB-DLE 407 B01 S50 together with related parts such as the Dungs GW A6 Compact Pressure Switch for Gas and Air, the DUNGS VPS 504 219881 and the DUNGS DMV-D 507/11 Double Solenoid Valve, so a burner gas train can be serviced with one order to a GCC supplier.

Technical Specifications

The values below for the DUNGS MB-DLE 407 B01 S50 are taken from the manufacturer datasheet for the MB-D(LE) 405-412 B01 series attached to this page.

Parameter Specification
Model DUNGS MB-DLE 407 B01 S50, GasMultiBloc, single-stage function
Nominal size DN 20, V2 double-seat valve
Flange threads Rp 3/4 to ISO 7/1 (405/407 body also accepts Rp 1/2)
Max. operating pressure 360 mbar (36 kPa)
Outlet pressure range (S50) 4 – 50 mbar (0.4 – 5 kPa)
Valve control V1 and V2 controlled together (S50)
Valves DIN EN 161 Class A Group 2; V1 fast opening; V2 slow opening with main volume restrictor
Opening time V2 Below 20 s (MB-DLE)
Regulator DIN EN 88 Class A Group 2, fixed setpoint spring, internal pulse tap
Filter Fine mesh-sieve
Voltage 220 – 230 V AC, 50 – 60 Hz, −15 % / +10 %
Power consumption 36 VA (MB 405/407 S50, 230 V, 20 °C)
Protection / duty IP 54, 100 % switch-on duration
Ambient temperature −15 °C to +70 °C
Gas connections G 1/8 measuring and ignition gas taps
Weight 2.6 kg

How to Order

To order the DUNGS MB-DLE 407 B01 S50, send Seven Star LLC an RFQ with the type code from the label, the flange size and coil voltage, or the burner model it serves. Our instrumentation team in Muscat checks the selection against the datasheet, shares the document for download and arranges delivery to sites in Oman and across the GCC.

Datasheets & Documents
  • PDF Datasheet DUNGS MB-D(LE) 405-412 B01 Datasheet (manufacturer, Ed. 03.19, No. 214 762) - covers MB-DLE 407 B01 S50 Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Open the gas train cabinet of a boiler or an industrial burner and there is a good chance the valves and pressure switches inside are marked DUNGS. Karl Dungs GmbH & Co. KG is a German maker of gas valves, regulators, pressure switches and combustion controls, based in Urbach near Stuttgart.

The company is family-owned and was established in 1945. Its North American business trades as DUNGS Combustion Controls through Karl Dungs Inc. Seven Star LLC is an independent supplier in Muscat. We source DUNGS gas valves, regulators, pressure switches and valve proving systems for burner operators and boiler contractors in Oman and the GCC, identified by type designation and article number.

DUNGS at a glance

Established 1945, Urbach, Germany, which is still the main manufacturing site
Company Karl Dungs GmbH & Co. KG, with subsidiaries including Karl Dungs Inc. in the USA
Product families Gas pressure regulators, safety shut-off solenoid valves, double solenoid valves, GasMultiBloc combined units, pressure switches, valve proving systems, burner controls and air/gas ratio controls
Applications Boilers and burners, process heat and furnaces, gas engines and CHP, heating appliances

DUNGS products we list

Series Type Role in the gas train
FRS Gas pressure regulator Holds a stable outlet pressure to the burner; sizes from Rp 3/8 to DN 150
MB-DLE GasMultiBloc Combined regulator and two safety valves Filter, regulator and two shut-off valves in one compact body, e.g. MB-DLE 407 B01 S50
DMV-D, DMV-D 5125/11 ECO Double solenoid valve Two automatic shut-off valves in series in one body, the standard safety shut-off arrangement for a burner
SV-D 505 Single safety solenoid valve Fast-closing shut-off valve, Rp 1/2 to Rp 2
GW A6, GW 150 A6 Pressure switch Low and high gas pressure and air pressure monitoring, e.g. 5 to 150 mbar
VPS 504 Valve proving system Checks that both shut-off valves seal tightly before every burner start

A typical gas train runs from the manual isolation valve through a filter, the regulator, a low gas pressure switch and two automatic shut-off valves to the burner. Larger burners add a high pressure switch and valve proving. Combined units such as the GasMultiBloc put several of these functions in one body, which saves space in compact burner housings.

Standards behind a DUNGS gas train

Each component in a gas train is tested to its own European product standard, and the standard printed on the DUNGS nameplate tells you which role the part is approved for. A replacement must carry the same approval for the same role.

EN 161 Automatic shut-off valves for gas burners and gas appliances: DMV double solenoid valves, SV single valves and the valve section of a GasMultiBloc
EN 88-1 Gas pressure regulators with inlet pressures up to 500 mbar, such as the FRS series
EN 1854 Pressure sensing devices for gas burners: GW gas and air pressure switches
EN 1643 Valve proving systems for automatic shut-off valves, such as the VPS 504
EN 298 Automatic burner control systems that supervise flame and start-up sequence
EN 676 Forced-draught gas burners as a whole, which sets when a high-pressure switch and valve proving are required

DMV, GasMultiBloc or separate components?

A DMV double solenoid valve puts two class A shut-off valves in one body and is used where the regulator and filter are separate parts of the train. A GasMultiBloc such as the MB-DLE adds the filter and regulator to the same body, so it is the usual choice on compact packaged burners. Larger and industrial burners keep separate components: a flanged FRS regulator, a DMV or two SV valves, GW pressure switches and a VPS valve proving system. When replacing a part, keep the same arrangement as the burner manufacturer, because the burner approval was issued for that train.

Where DUNGS products are used

In Oman and the GCC, DUNGS components sit on burners for steam and hot water boilers in hotels, hospitals, laundries and food plants, on industrial furnaces and dryers, and on gas engine fuel trains. Most requests are like-for-like replacements of valves, coils and pressure switches during burner servicing.

Ordering DUNGS parts: what we need

Send the full type designation and the 6-digit article number from the label (for example VPS 504 S04, 219881), the connection size, the maximum inlet pressure, the coil voltage, and the burner make and model if known.

Facts checked against DUNGS product information and company directory records, October 2026.

FAQ

Questions about the DUNGS MB-DLE 407 B01 S50 GasMultiBloc Rp 3/4, 230 V

Answers from our engineering team on installation, compatibility and integration.

01What does the code DUNGS MB-DLE 407 B01 S50 mean?
MB-DLE is the GasMultiBloc with main volume restrictor and adjustable slow opening, 407 is the DN 20 size with a double-seat second valve, B01 is the single-stage version with one regulator and two Class A valves, and S50 means the valves are switched together with a 4-50 mbar outlet range.
02What supply voltage does the DUNGS MB-DLE 407 B01 S50 need?
The datasheet specifies 220-230 V AC at 50-60 Hz, with a tolerance of minus 15 to plus 10 percent. Power consumption for the 405/407 S50 is 36 VA at 230 V.
03Is the DUNGS MB-DLE 407 B01 S50 used on Bentone BG 400 burners?
Bentone lists BG 400 single-stage models with an MB-DLE 407 gas valve, and its BG 400 manual covers the MultiBloc DLE 405-412 with an S50 governor range of 4-50 mbar. Always compare the label on the installed valve before ordering a replacement.
04What is the difference between the MB-DLE 405 and the MB-DLE 407?
Both use the same compact body and flange options. The 405 has a single-seat second valve, while the 407 has a double-seat second valve that allows a higher flow rate.
05Can Seven Star LLC supply the DUNGS MB-DLE 407 B01 S50 in Oman?
Yes. Seven Star LLC supplies this GasMultiBloc and related pressure switches and valve proving systems to customers in Oman and the GCC, with engineering support in Muscat.