Brand:

Fireye BurnerLogiX YB110 Burner Management Control

Description

A modular burner management control with plug-in programmers and optional OLED display

The Fireye BurnerLogiX YB110 (120 Vac) and YB230 (230 Vac) form a microprocessor-based burner management control for automatically ignited oil, gas and combination fuel burners. With the limit and operating controls, it sequences the burner or blower motor, ignition and fuel valves for proper and safe operation. SMART LEDs show operating status and lockout information, and an optional two-line by sixteen-character OLED (BLV512) or LCD (BLL510) display gives full-language status and diagnostic messages through a keypad.

A complete system comprises the YB chassis fitted with the flame amplifier needed for the application, a suitable flame detector, a plug-in YP programmer module, a wiring base and the optional display. The programmer sets functions such as pre-purge time, recycling or non-recycling interlocks, high fire proving and the trial for ignition timings of the pilot and main flame. The chassis is available for UV, self-check UV, IR auto-check, flame rod and direct-coupled integrated scanner (Phoenix or InSight) inputs.

Technical specifications

Parameter Specification
Chassis models YB110UV, YB110UVSC, YB110IR, YB110IR2, YB110FR, YB110DC (120 Vac); YB230UV, YB230UVSC, YB230IR, YB230IR2, YB230FR, YB230DC (230 Vac)
Amplifier codes UV = non-self-check UV; UVSC = self-check UV; IR = IR auto-check; IR2 = special application, consult factory; FR = flame rod; DC = direct coupled (Phoenix / InSight)
Supply YB110: 120 Vac +10 % / -15 %, 50/60 Hz; YB230: 230 Vac +10 % / -15 %, 50/60 Hz; 25 VA
Ambient temperature -40 to +60 C for the chassis, programmers and OLED display; LCD display -20 to +60 C
Humidity 90 % RH, non-condensing
Protection Control NEMA 1 (IP01); remote-mounted display NEMA 4X (IP66)
Wiring bases 60-2812-1 (conduit knockouts) and 60-2814-1 (open base), both with terminal block for 2 x 14 AWG; 4.0 in W x 7.0 in H (101 x 178 mm)
Shipping weight Approx. 3.2 lb (1.45 kg)
Programmer modules YP100 / YP102 / YP113 / YP115 (non-recycle, modulation; FFRT 4 / 2 / 1 / 1 s), YP118, YP138, YP148, YP183, YP184, YP200, YP202, YP300, YP302 (see bulletin tables)
Maximum connected load 2000 VA; ignition and valve terminal ratings per combination table in the bulletin
Displays; accessories BLV512 OLED, BLL510 LCD (ordered separately; blank module BLD500 included); remote mounting kits 129-178-4 and 129-178-8; IT1000 wireless alarm annunciation
Communications; outputs Modbus via RS485 multi-drop, programmable baud rate; flame signal via display or 4-20 mA output
Functions Non-volatile memory, lockout history, fuel hours and cycle counts, run/check switch, remote reset, valve proving for two-valve systems, low gas pressure check, revert to pilot
Approvals as printed UL MCCZ, MCCZ2, MCCZ7, MCCZ8 file MP1537; Factory Mutual approved; acceptable to I.R.I.

Selecting the chassis and programmer

Start from the flame detection method: a UV tube scanner calls for a UV chassis, a self-checking UV scanner such as the 45UV5 for UVSC, an infrared scanner for IR, a flame rod for FR, and an integrated Phoenix or InSight scanner for the DC chassis. Then choose the programmer that matches the firing sequence and flame failure response time, and decide whether a display is required. Fireye warns that programmers fit a common chassis mechanically but the correct model must be selected by a competent professional for the application.

See also burners and gas trains and flame detection; the LAMTEC BurnerTronic BT300 is a comparable burner control system.

Related Fireye products: Fireye 65UV5 Simplicity Integrated UV Flame Scanner, Fireye InSight 95DSS2 UV/IR Integrated Flame Scanner, Fireye InSight S4 95S4 UV/IR Integrated Flame Scanner and Fireye Phoenix 85UVF1A-1QD UV Integrated Flame Scanner.

Documents and quotation

The attached Fireye bulletin BL-1001 (May 2026) covers specifications, part numbers, wiring, programmer selection, operating sequences, lockout codes and Modbus communications. Send the chassis, programmer, display and base part numbers with the fuel and scanner type for a quotation, and confirm all part numbers before ordering.

Datasheets & Documents
  • PDF Datasheet Fireye BurnerLogiX YB110/YB230 integrated burner management control bulletin BL-1001 (May 2026) Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Fireye is an American maker of flame safeguard and burner management equipment, with roots in the 1930s, when it offered the first commercial and industrial electronic flame safeguard control. Its early history was in Waltham and Cambridge, Massachusetts, as part of Electronics Corporation of America. Fireye is now part of Carrier and has its headquarters and main plant in Derry, New Hampshire.

Seven Star LLC is an independent supplier in Muscat. We list Fireye scanners and controls for boiler and burner service in Oman and the GCC.

Fireye company profile

Origins 1930s, Massachusetts
Headquarters Derry, New Hampshire
Ownership Carrier
Key invention Electronic flame safeguard control
Product families InSight and Phoenix integrated flame scanners, 65UV5 UV scanners, BurnerLogix and Flame-Monitor burner management systems, combustion controls, spark igniters

Fireye product series

Integrated flame scanners include the 65UV5 Simplicity UV scanner, the Phoenix 85UVF1A-1QD UV scanner and the InSight 95DSS2 and InSight S4 95S4 UV/IR scanners.

The BurnerLogiX YB110 is a burner management control.

Flame scanners detect the ultraviolet or infrared radiation of the flame and tell the burner management control whether a flame is present. UV scanners suit gas flames, while UV/IR scanners help discriminate between burners in multi-burner boilers.

The burner management control runs the start-up sequence, purge, ignition and flame supervision and shuts the fuel off if the flame fails.

Where Fireye products are used

Boilers, furnaces, heaters and thermal oxidisers burning gas or oil in plants and buildings.

Fireye products we list

Family Examples
Burners & Gas Trains 65UV5 Simplicity Integrated UV Flame Sca…, InSight 95DSS2 UV/IR Integrated Flame Sc…, InSight S4 95S4 UV/IR Integrated Flame S…, Phoenix 85UVF1A-1QD UV Integrated Flame…

Ordering Fireye products: what we need

Send the model and suffix, fuel, burner type and the existing control or scanner being replaced.

Facts checked against Fireye's company overview brochure and trade profiles, October 2026.

FAQ

Questions about the Fireye BurnerLogiX YB110 Burner Management Control

Answers from our engineering team on installation, compatibility and integration.

01What is the Fireye BurnerLogiX YB110?
A 120 Vac burner management chassis with flame amplifier that takes a plug-in YP programmer and an optional OLED or LCD display.
02What is the difference between YB110 and YB230?
Supply voltage: the YB110 runs on 120 Vac and the YB230 on 230 Vac, both 50/60 Hz and 25 VA.
03Which flame detectors can it use?
UV, self-check UV, infrared auto-check, flame rod and direct-coupled integrated scanners, depending on the chassis amplifier chosen.
04Is the display included?
No. A blank display module is included; the BLV512 OLED or BLL510 LCD display is ordered separately.
05Does it support communications?
Yes. It offers Modbus over an RS485 multi-drop link with programmable baud rate, plus a 4-20 mA flame signal output.