Schneider Electric TM3TM3 Modicon TM3 Analog/Temperature Mixed

Description

TM3TM3 a mixed analog and temperature expansion module

The TM3TM3 is a Schneider Electric product listed in the datasheet as: analog IO module, Modicon TM3, 2 analog or temperature inputs, 1 analog output, screw, 24V DC. The TM3TM3 combines two inputs, each usable as an analogue signal or a temperature sensor, with one analogue output. It saves rack space on small machines that need a little of everything, such as an oven with a thermocouple, a pressure transmitter and a valve output. Seven Star LLC supplies the TM3TM3 in Oman and the GCC as an independent supplier based in Muscat.

Decoding the reference: TM3 is the family, the second TM stands for temperature and mixed, and 3 refers to the three channels (two inputs and one output). The datasheet describes thermocouple support and 16-bit analogue input resolution.

Technical specifications of the TM3TM3

Parameter Specification
Manufacturer / part number Schneider Electric / TM3TM3
Description analog IO module, Modicon TM3, 2 analog or temperature inputs, 1 analog output, screw, 24V DC
Range of Product Modicon TM3
Product or Component Type Input/output analog module
Range Compatibility Modicon M221; Modicon M241; Modicon M251; Modicon M262
Analogue input number 2
Analogue output number 1
Analogue input type Current 4 to 20 mA; Current 0 to 20 mA; Voltage 0 to 10 V; Voltage – 10 to 10 V; Thermocouple – 200 to 1000 °C thermocouple J
Analogue input resolution 16 bits; 15 bits + sign
Permissible continuous overload 13 V voltage; 40 mA current
Stabilisation time 1 ms
Input impedance <= 50 Ohm; >= 1 MOhm
Sampling duration 10 ms
Analogue output type Current 4 to 20 mA; Current 0 to 20 mA; Voltage 0 to 10 V; Voltage – 10 to 10 V
Conversion time 100 ms + 100 ms per channel + 1 controller cycle time thermocouple
Absolute accuracy error ± 6 °C at 25 °C for thermocouple R, S 0 to 200 °C; ± 0.4 % of full scale at 25 °C for thermocouple K – 200 to 0 °C
Repeat accuracy ±0.5 %FS input
Output ripple 20 mV
Cross talk <= 1 LSB
Type of cable Twisted shielded pairs cable <30 m input/output
Electrical connection 11 x 2.5 mm² removable screw terminal block with pitch 5.08 mm adjustment for inputs, outputs and supply
LSB value 0.15 mV, 0 to 10 V; 0.30 mV, – 10 to 10 V; 0.30 µA, 0 to 20 mA; 0.244 µA, 4 to 20 mA; 0.1 °C; 2.44 mV, 0 to 10 V; 4.88 mV, – 10 to 10 V
Insulation Between input and supply 1500 V AC; Between input and internal logic 500 V AC; Between output and supply 1500 V AC
Immunity to microbreaks 10 ms
Load impedance ohmic 1 kOhm voltage; 300 Ohm current
load type Resistive
Temperature drift ± 0.006 %FS/°C
Non-linearity ± 0.01 %FS analog output; ± 0.1 %FS analog input
Typical current consumption 55 mA 24 V DC no load; 55 mA 5 V DC no load; 60 mA 5 V DC full load; 80 mA 24 V DC full load
Local signalling 1 LED green PWR
Mounting support Top hat type TH35-15 rail IEC 60715; Top hat type TH35-7.5 rail IEC 60715 plate or panel with fixing kit
Height 90 mm
Width 23.6 mm
Depth 70 mm
Net Weight 0.115 kg
IP Degree of Protection IP20
Product certifications CE; UKCA; RCM; EAC; CULus; CULus HazLoc
Standards IEC 61131-2
Electromagnetic emission Radiated emissions 40 dBμV/m QP class A 10 m30 to 230 MHz IEC 55011; Radiated emissions 47 dBμV/m QP class A 10 m230 to 1000 MHz IEC 55011
Ambient air temperature (operation or storage, as listed) -25 to 70 °C
operation -10 to 35 °C vertical installation
Relative humidity 10 to 95 % without condensation

Inputs and output of the TM3TM3

Analogue inputs: 2. Analogue outputs: 1. Analogue input types: Current 4 to 20 mA; Current 0 to 20 mA; Voltage 0 to 10 V; Voltage – 10 to 10 V; Thermocouple – 200 to 1000 °C thermocouple J. Input resolution: 16 bits; 15 bits + sign.

The analogue inputs accept 0 to 10 V, plus or minus 10 V, 0 to 20 mA and 4 to 20 mA, with 16-bit resolution and 1 megohm input impedance for voltage. For temperature, the conversion time of 100 ms plus 100 ms per channel reflects the slower sensor measurement, and thermocouple accuracy is specified in degrees (for example 6 degrees Celsius at 25 degrees for R and S type over a low range).

The analogue output is a single channel with voltage or current ranges, ripple of 20 mV and load limits of 1 kilohm or 300 ohms. Isolation is 1500 V AC to the supply.

Applying the TM3TM3 on a small machine

For temperature control, the module reads the sensor and the controller runs the PID loop, while the analogue output drives a heater power controller or valve. This keeps the whole loop within one expansion string.

If more than two measurement channels are needed, the TM3TI4D provides four dedicated temperature inputs and the TM3AQ4 offers four outputs. Mixed modules are best for compact systems, while larger systems benefit from dedicated modules for easier diagnosis.

Selection checklist for the TM3TM3

  • Sensor type per input: voltage, current, thermocouple or RTD as listed.
  • Output type: voltage or current range for the actuator.
  • Conversion time: slower on temperature channels.
  • Cable: twisted shielded pairs, correct compensation cable for thermocouples.
  • Isolation: 1500 V AC to supply.
  • Mounting: 23.6 mm width on TH35 rail.

Wiring, scaling and diagnostics of the TM3TM3

Use the correct compensating cable for thermocouples and keep junctions clean and tight. Cold-junction effects at the terminal block show up as small constant errors when a draught or heat source acts on the module.

Test each channel with a simulator before connecting to the process. Check that the output response is within limits at the extremes of the actuator range, as a mis-scaled output at 100 percent can overdrive a valve.

Typical applications of the TM3TM3 in Oman and the GCC

In Oman and the GCC, mixed analogue and temperature modules suit ovens, dryers, small chillers and boiler skids where ambient temperatures are high. Keep the module away from heat sources inside the panel to avoid drift.

Dimensions, environment and approvals of the TM3TM3

For the TM3TM3, plan the mounting space from the datasheet: 23.6 mm (W) x 90 mm (H) x 70 mm (D). The TM3TM3 weighs 0.115 kg. Mounting, derating and enclosure choices follow the environmental data below, which should be compared with the actual panel temperature and the dust and humidity of the site in Oman and the GCC.

Ambient temperature limits in the datasheet: -25 to 70 °C. Relative humidity: 10 to 95 % without condensation. Ingress protection: IP20. Operating altitude: 0 to 2000 m. Vibration resistance: 3.5 mm 5 to 8.4 Hz on DIN rail; 3 gn 8.4 to 150 Hz on DIN rail. Shock resistance: 15 gn 11 ms. Standards listed: IEC 61131-2. Certifications listed for this reference: CE; UKCA; RCM; EAC; CULus; CULus HazLoc.

Information to send with an RFQ for the TM3TM3

  • Full reference and quantity required
  • Existing equipment, panel or rack it must fit
  • Supply voltage, load or signal details of the application
  • Required delivery location and timing
  • Whether a spare, a replacement or a new installation

Documents and quotation

A datasheet for this product is attached on this page. It lists the electrical, mechanical and environmental data summarised above.

Send us the part number, quantity and application and we will confirm availability and a quotation. Seven Star LLC is an independent supplier in Muscat and does not represent itself as an official channel of the manufacturer.

Datasheets & Documents
  • PDF Datasheet Schneider Electric TM3TM3 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric TM3TM3 Modicon TM3

Answers from our engineering team on installation, compatibility and integration.

01How many inputs and outputs does the TM3TM3 have?
The datasheet gives 2 inputs.
02What input types does the TM3TM3 support?
The datasheet lists Current 4 to 20 mA; Current 0 to 20 mA; Voltage 0 to 10 V; Voltage – 10 to 10 V; Thermocouple – 200 to 1000 °C thermocouple J; Thermocouple – 200 to 1300 °C thermocouple K.
03What output types does the TM3TM3 support?
The datasheet lists Current 4 to 20 mA; Current 0 to 20 mA; Voltage 0 to 10 V; Voltage – 10 to 10 V.
04What is the module width of the TM3TM3?
The datasheet gives 23.6 mm.
05What is the net weight of the TM3TM3?
The datasheet gives 0.115 kg.