- Automation & ControlView all 2,085 products
- AC Drives
- Automation Accessories
- PLC & I/O Cards
- Industrial Communications
- Vibration Monitoring
- Controllers & Data Acquisition
- Isolator & Barrier
- CCTV & Security
- Safety Switches & Guard Locking
- Encoders
- HMI Displays
- Motor Soft Starters
- Pneumatic Cylinders
- Industrial Computers
- Servo Drives
- Machine Vision
- Automation Software
- Robotics
Brand: Schneider Electric
Schneider Electric LV525608 CVS250B 250 A 3P Circuit Breaker
Description
LV525608: CVS250B 250 A EasyPact CVS breaker, TM-D thermal-magnetic trip
The LV525608 is a Schneider Electric EasyPact CVS moulded-case circuit breaker, listed in the datasheet as the CVS250B: three poles, all three protected (3P 3D), with a TM-D thermal-magnetic trip unit rated 250 A. It is a fixed, backplate-mounted distribution breaker with front connections and a toggle handle, intended to protect a feeder against overload and short circuit. Seven Star LLC supplies the LV525608 in Oman and the GCC as an independent supplier based in Muscat.
Reading the reference from the datasheet: the short name CVS250B combines the CVS family, the 250 A frame size (compatibility code CVS250) and the breaking-capacity letter B, which the datasheet repeats as its breaking capacity code. Within the same frame, the letter changes the Icu and Ics figures, not the physical size. The 250 A figure is the rated current of the trip unit, stated by the datasheet at 50 °C for In and 40 °C for the trip unit rating. Orders must therefore be checked on three items together: frame, breaking letter and ampere rating.
Technical specifications of the LV525608
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Schneider Electric / LV525608 |
| Range of product | EasyPact CVS |
| Device short name | CVS250B |
| Poles / protected poles | 3P / 3D |
| Earth leakage protection | Without |
| [In] rated current | 250 A at 50 °C |
| Trip unit | TM-D, thermal-magnetic |
| Trip unit rating | 250 A at 40 °C |
| Protection type | Short-circuit protection (magnetic) / Overload protection (thermal) |
| [Icu] breaking capacity | 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ics] service breaking capacity | 15 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 / 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 / 40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 |
| Rated impulse withstand [Uimp] | 8 kV conforming to EN/IEC 60947-2 |
| Breaking capacity code | B |
| Long time pick-up Ir | Adjustable / 0.7…1 x In |
| Instantaneous pick-up Ii | Fixed / 2500 A |
| Mechanical durability | 20000 cycles |
| Electrical durability | 10000 cycles 415 V In conforming to IEC 60947-2 |
| Connection pitch | 35 mm |
| Compatibility code | CVS250 |
| Width x depth x height | 105 x 86 x 161 mm |
| Net weight | 1.7 kg |
| Standards | IEC 60947-2 / EN 60947-2 |
| Product certifications | IEC / GOST |
| Operating ambient temperature | -25…70 °C |
| Storage ambient temperature | -50…85 °C |
LV525608 and the other CVS250 breakers
Parts of the same frame (CVS250) found in the same batch are listed below so that the LV525608 can be told apart from its neighbours. The table shows only data taken from each datasheet. Compared with the closest relative, LV525623 (CVS250F, 250 A, breaking code F), this part has a different breaking class, which changes the trip thresholds and fault duty rather than the physical size.
| Part number | Short name | In | Trip unit | Icu at 380/415 V |
|---|---|---|---|---|
| LV525608 | CVS250B | 250 A | TM-D | kA |
| LV525622 | CVS250F | 200 A | TM-D | 36 kA |
| LV525623 | CVS250F | 250 A | TM-D | 36 kA |
| LV525634 | CVS250N | 200 A | TM-D | 50 kA |
| LV525635 | CVS250N | 250 A | TM-D | 50 kA |
Trip unit and settings of the LV525608
The thermal element handles overload: the long-time pick-up Ir is adjustable from 0.7 to 1 times In, so on this 250 A unit the thermal setting can be placed between about 175 A and 250 A. The long-time delay is fixed, as is the short-time delay.
The magnetic pick-up of this breaker is fixed at 2500 A, which is 10 times In. Because the long-time and short-time delays are listed as fixed, selectivity with downstream breakers depends on the magnetic level and on the upstream and downstream ratings, so check the manufacturer coordination tables where selectivity is required.
Selection checklist for the LV525608
Use these checks before ordering; they are drawn from the datasheet fields and avoid the most frequent mismatches.
- Frame and short name: confirm CVS250B and compatibility code CVS250; the dimensions 105 x 86 x 161 mm must fit the enclosure and the connection pitch is 35 mm.
- Rating: 250 A, with 2500 A for the magnetic threshold.
- Fault level: compare the prospective short-circuit current with ? kA Icu at 380/415 V AC (or ? kA at 440 V).
- Poles: 3P with all poles protected (3D) and no earth-leakage block, as the datasheet lists.
- Mounting: the datasheet lists fixed mounting on a backplate with front connections.
- Ambient: operation -25…70 °C, with the rated current stated at 50 °C and the trip unit rating at 40 °C.
Installation and maintenance of the LV525608
Mount it on a flat backplate and connect from the front; the datasheet lists screw terminals where applicable and a connection pitch of 35 mm. Torque values and cable sizes are not in the datasheet, so follow the manufacturer installation instructions. After the cable is landed, close and open the toggle several times and check that the contact position indicator follows the handle.
Commissioning means setting Ir from the front; the dial should be set to the cable ampacity or the load current, not left at the maximum by habit. Maintenance is mostly visual: look for heat discolouration at terminals, dust build-up and loose lugs at each shutdown. Mechanical durability is listed at 20000 cycles and electrical durability at 10000 cycles 415 V In conforming to IEC 60947-2, so it is designed for occasional operation rather than as a frequent switching device.
Where the LV525608 fits in Oman and the GCC
In Oman and the GCC this class of breaker is typically specified for sub-distribution boards, pump and fan feeders, workshop and camp supplies, and utility rooms in commercial and light-industrial buildings, where a compact fixed breaker is enough. Summer heat in unventilated switchrooms and fine desert dust make enclosure cooling and cleaning part of the design: the datasheet states an operating range of -25…70 °C and an IP degree of see datasheet for the breaker itself, so the enclosure has to provide the real protection.
Breaking capacity of the CVS250B LV525608
For the LV525608 the datasheet gives an Icu of 40 kA at 220/240 V AC, and service breaking capacities Ics of 15 kA at 440 V AC, 25 kA at 380/415 V AC and 40 kA at 220/240 V AC, all to IEC 60947-2. No Icu values are printed for 380/415 V or 440 V on this reference, so any study at those voltages should rely on the Ics figures above and be confirmed with us before ordering.
Ics is the more practical number for an operator: it is the breaking capacity after which the breaker is rated to remain in service. Here Ics is 0 per cent of Icu at 415 V, which is worth noting when comparing with a breaker of another make. Prospective fault current at the busbar must not exceed the Icu at the system voltage.
Information to send with an RFQ for the LV525608
To quote the LV525608 quickly, please send the following with your request:
- Part number LV525608 and quantity.
- System voltage and prospective short-circuit current at the board.
- Required Ir setting range and the load or cable the breaker will protect.
- Whether accessories (auxiliary contacts, terminal shields, rotary handle) are also needed; these are separate references and must be confirmed against the product family.
- Delivery location and required documents.
Documents and quotation
The official Schneider Electric datasheet for the LV525608 is attached on this page, so the figures quoted above can be checked line by line against the manufacturer document. Please send the part number LV525608, the quantity and the delivery point in Oman or elsewhere in the GCC, and we will reply with availability and lead time.
Seven Star LLC is an independent supplier based in Muscat. We work independently of the manufacturer; we source, check the reference against the datasheet and quote. Ask for the LV525608 on your RFQ and mention any special packing, marking or documentation needed for the project file.
Datasheets & Documents
- Datasheet Schneider Electric LV525608 Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.
Schneider Electric company profile
| Origins | 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry |
|---|---|
| Headquarters | Rueil-Malmaison (Paris region), France |
| Ownership | Public company listed on Euronext Paris |
| Key acquisitions | Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software |
| Brand names still in use | Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform |
| Product families | Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software |
Milestones
- 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
- 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
- 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
- 1997: Modicon, the company behind the first programmable logic controller, joins the group.
- 1999: The group takes the name Schneider Electric.
- 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.
Choosing Schneider Electric breakers and motor control
Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.
Where Schneider Electric products are used
In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.
APC by Schneider Electric: UPS and critical power
Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.
Schneider Electric products we list
| Family | Examples |
|---|---|
| Circuit breakers | Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW |
| Motor control | TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480 |
| Drives | Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo |
| PLCs, HMIs and relays | Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655 |
| Protection, metering and power | Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS |
Ordering Schneider Electric products: what we need
Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.
Facts checked against Schneider Electric's published company history, October 2026.
Browse Schneider Electric products by category: Circuit Breaker, Electrical & Power Modules, AC Drives, PLC & I/O Cards, Metering Systems, UPS and Batteries.
FAQ
Questions about the Schneider Electric LV525608 CVS250B 250 A 3P
Answers from our engineering team on installation, compatibility and integration.
01What is the LV525608?
It is a Schneider Electric EasyPact CVS moulded-case circuit breaker, short name CVS250B, three poles protected, rated 250 A with a TM-D trip unit. It is a fixed backplate-mounted distribution breaker.
02What breaking capacity does the LV525608 have?
The datasheet lists 40 kA Icu at 220/240 V AC and Ics of 25 kA at 380/415 V AC, 15 kA at 440 V AC, to IEC 60947-2.
03Is the trip unit of the LV525608 adjustable?
Yes, the long-time pick-up Ir is adjustable from 0.7 to 1 x In, i.e. about 175 A to 250 A. The instantaneous pick-up is 2500 A.
04What are the dimensions of the LV525608?
The datasheet gives width 105 mm, depth 86 mm and height 161 mm and a net weight of 1.7 kg. The connection pitch is 35 mm.
05Does Seven Star LLC supply the LV525608 in Oman?
Seven Star LLC is an independent supplier in Muscat and quotes the LV525608 for Oman and the GCC on request. Send the part number and quantity with your RFQ and we will confirm availability and documents.


















Reviews
There are no reviews yet.