Brand: Schneider Electric
Schneider Electric LC1DT200ALSE 4P 200 A TeSys Deca Contactor
Description
LC1DT200ALSE: a 4-pole 200 A TeSys Deca Advanced contactor with EverLink connectors
The LC1DT200ALSE is a Schneider Electric contactor listed in the datasheet as: Contactor, Tesys Deca Advanced, 4P(4NO), AC-1, <=440V, 200A, 200-500V AC/DC coil,connector. It is a four-pole contactor with four normally open power contacts, built for resistive and mixed loads up to 200 A and for panels that need a wide-range coil. Seven Star LLC supplies the LC1DT200ALSE in Oman and the GCC as an independent supplier based in Muscat.
Reading the reference: LC1D is the TeSys Deca contactor family and the datasheet lists the compatibility code as LC1D. The datasheet title identifies the four-pole arrangement, the 200 A rating and the coil and connection style rather than a letter-by-letter code, so the title is the reliable reading. It states 200 to 500 V AC/DC coil and connector, which is the practical reading: a single coil that accepts either AC or DC over a very wide range, and power terminals designed as connectors rather than simple screw clamps.
Technical specifications of the LC1DT200ALSE
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Schneider Electric / LC1DT200ALSE |
| Description | Contactor, Tesys Deca Advanced, 4P(4NO), AC-1, <=440V, 200A, 200-500V AC/DC coil,connector |
| Range | TeSys Deca |
| Range of product | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Contactor application | Resistive load |
| Utilisation category | AC-3; AC-3e; AC-1; AC-4; DC-1; DC-3; DC-5 |
| Poles / contact composition | 4P / 4 NO |
| Rated operational voltage [Ue] | Power circuit: <= 1000 V AC 16.67 to 400 Hz; Power circuit: <= 300 V DC |
| Rated operational current [Ie] | 200 A (at <60 °C) at <= 440 V AC AC-1 for power circuit |
| Control circuit voltage [Uc] | 200 to 500 V AC 50/60 Hz; 200 to 500 V DC |
| Control circuit voltage limits | 0.8 Uc Min–1.1 Uc Max (-40 to 60 °C):operational AC/DC; 0.1 Uc Max (-40 to 60 °C):drop-out AC/DC |
| Coil technology | Built-in bidirectional peak limiting diode suppressor |
| Making capacity | 1260 A at 440 V for power circuit conforming to IEC 60947 |
| Rated breaking capacity | 1100 A at 440 V for power circuit conforming to IEC 60947 |
| Associated fuse (power circuit) | 315 A gG at <= 690 V for power circuit |
| Rated insulation voltage [Ui] | Power circuit: 1000 V conforming to IEC 60947-4-1 |
| Rated impulse withstand [Uimp] | 8 kV conforming to IEC 60947 |
| Inrush / hold-in power | 170 VA (at 20 °C) (120 W (at 20 °C)) | 16.5 VA (at 20 °C) (5.1 W at 20 °C) |
| Mechanical durability | 8 Mcycles |
| Electrical durability | 0.38 Mcycles 200 A AC-1 at Ue <= 440 V |
| Operating time | 10 to 80 ms opening; 20 to 90 ms closing |
| Maximum operating rate | 2400 cyc/h at 60 °C; 3600 cyc/h at Uc at 20 ºC |
| Auxiliary contacts | 1 NO + 1 NC (mechanically linked; mirror contact 1 NC) |
| Power circuit connection | connector 1: 10 to 120 mm2 / connector 2: 10 to 50 mm2 (flexible without cable end) |
| Tightening torque | Power circuit 12 N.m (hexagonal screw head 4 mm); control circuit 1.7 N.m |
| Dimensions (W x H x D) | 132 mm x 152 mm x 155 mm |
| Net weight | 3 kg |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Ambient air temperature | -40 to 60 °C operation; 60 to 70 °C with derating; -60 to 80 °C storage |
| Operating altitude | 0 to 3000 m without derating |
| Product certifications | CB Scheme; CCC cULus; CE; UKCA; EU-RO-MR by DNV-GL |
Why a four-pole 200 A contactor with a wide coil range
Four poles are not needed for a three-phase motor on its own. They are used when the neutral must be switched together with the phases, for example in heater banks, generator changeover, lighting feeders or building supply isolation, where all conductors must open at once. The datasheet lists the contactor application of the LC1DT200ALSE as resistive load and a rated operational current of 200 A in AC-1 at up to 440 V AC (below 60 °C) for the power circuit.
The coil is the second distinguishing feature of the LC1DT200ALSE. It accepts 200 to 500 V on either AC at 50/60 Hz or DC, so one reference covers a whole set of control voltages that would otherwise need several coil codes. For a spares shelf in a region with mixed 230 V, 400 V and DC control supplies, that is a real saving in stock variety. The datasheet notes a built-in bidirectional peak limiting diode suppressor in the coil, which limits the voltage surge generated when the coil is switched off.
Load categories and voltage ratings of the LC1DT200ALSE
For the LC1DT200ALSE the datasheet lists utilisation categories AC-3, AC-3e, AC-1, AC-4, DC-1, DC-3 and DC-5. The power circuit is rated up to 1000 V AC at 16.67 to 400 Hz and up to 300 V DC, with a rated insulation voltage of 1000 V under IEC 60947-4-1 and 600 V for CSA and UL. For motor duty the datasheet gives 55 kW at 400 V AC in AC-3, 59 kW at 415 and 440 V, 75 kW at 500 V, 80 kW at 690 V and 65 kW at 1000 V, so the 200 A frame also covers motors at higher voltages than the usual 400 V.
Short-circuit data: the making capacity is 1260 A at 440 V and the breaking capacity is 1100 A at 440 V. The associated fuse for the power circuit is 315 A gG at up to 690 V. Short-time withstand currents are listed from 1800 A for 1 second down to 350 A for 10 minutes, which helps in selecting the upstream protective device and in checking thermal limits during faults.
Coil, operation and durability of the LC1DT200ALSE
The operating window of the LC1DT200ALSE coil is 0.8 Uc minimum to 1.1 Uc maximum between -40 and 60 °C, with drop-out at 0.1 Uc maximum. On a 200 V coil supply, that corresponds to a pick-up from 160 V, and on a 500 V supply up to 550 V. Inrush is 170 VA and 120 W, hold-in is 16.5 VA and 5.1 W, and the heat dissipation of the coil circuit is 3 W at 20 °C. The datasheet gives opening times of 10 to 80 ms and closing times of 20 to 90 ms.
For the LC1DT200ALSE, mechanical durability is 8 million cycles; the electrical durability stated is 0.38 million cycles at 200 A in AC-1. The maximum operating rate is 2400 cycles per hour at 60 °C and 3600 cycles per hour at Uc at 20 °C. For functional safety calculations the datasheet adds B10d values of 684932 cycles at nominal load and 10000000 cycles under mechanical load, according to EN/ISO 13849-1.
Connections, auxiliary contacts and mounting of the LC1DT200ALSE
The power circuit of the LC1DT200ALSE uses connectors: connector 1 accepts 10 to 120 mm² flexible cable without cable end and connector 2 accepts 10 to 50 mm². The tightening torque is 12 N.m on a hexagonal screw head of 4 mm, which is a high torque that should be applied with a calibrated tool. The control circuit uses screw clamp terminals with 1.7 N.m. A protective cover is listed as supplied.
The built-in auxiliary contacts are 1 NO + 1 NC mechanically linked, and the NC contact is also described as a mirror contact. A mirror contact is the one safety systems use to confirm that the main contacts are open, so it can be wired into a safety relay feedback loop. The minimum switching level for the signalling circuit is 17 V and 5 mA, so the contacts suit low-level PLC inputs. The LC1DT200ALSE is mounted on a plate; its dimensions are 132 mm wide, 152 mm high and 155 mm deep, and the net weight is 3 kg.
Selection checklist for the LC1DT200ALSE
- Pole count: confirm that four poles are really required, for example to switch the neutral together with three phases.
- Load: 200 A AC-1 is the headline rating; for motors use the AC-3 powers in the table and check AC-4 duty separately.
- Control voltage: the coil covers 200 to 500 V AC or DC; check that the lowest and highest supply you expect both stay inside 0.8 to 1.1 Uc.
- Short-circuit protection: the datasheet associates a 315 A gG fuse for the power circuit.
- Cable: connector 1 takes 10 to 120 mm² flexible conductors; plan lugs or cable preparation accordingly.
- Space: 132 mm wide, 152 mm high, 155 mm deep and 3 kg; the body is plate mounted only.
- Status: say whether you need a spare for an existing panel or a new installation.
Environment, approvals and applications of the LC1DT200ALSE in Oman and the GCC
The datasheet gives operation from -40 to 60 °C, with derating between 60 and 70 °C, and storage from -60 to 80 °C. Altitude up to 3000 m needs no derating. The climatic withstand is listed according to IACS E10 exposure to damp heat and IEC 60947-1 Annex Q category D, which is relevant to humid coastal sites in the Gulf. Protection is IP20 on the front face, so the contactor needs an enclosure; protective treatment is listed as none. Vibration on a closed contactor is rated at 4 Gn from 5 to 300 Hz and shock at 15 Gn for 11 ms.
Certifications listed for this reference are CB Scheme, CCC, cULus, CE, UKCA and EU-RO-MR by DNV-GL. In Oman and the GCC the main practical issue is heat inside the panel: a contactor carrying 200 A dissipates 28.1 W per pole in AC-1 according to the datasheet, so the four poles of the LC1DT200ALSE add noticeable heat to the enclosure and the cabinet temperature should be checked against the 60 °C limit.
Four-pole 200 A contactors are typical in electric heating banks for process lines, generator and mains changeover panels, lighting and small-power feeders in plants and buildings, and large single loads such as dewatering heaters or battery-charging rectifier inputs. The DC categories (DC-1, DC-3 and DC-5 up to 300 V DC) also open the door to some DC auxiliary circuits, but the DC rating figures must be taken from the datasheet for the exact duty.
For plants that standardise on a single wide-range coil, the LC1DT200ALSE reduces the variety of spares to hold. If a contactor of this family is already installed and you need an identical spare, send us the full reference from the nameplate and the control voltage that the old coil has been running on.
Information to send with an RFQ for the LC1DT200ALSE
- Full reference LC1DT200ALSE and the quantity required
- Load type, current and number of poles to be switched
- Control circuit voltage and whether it is AC or DC
- Cable size and the way it is terminated
- Required delivery location and timing
- Whether it is a spare, a replacement or a new installation
Documents and quotation
A datasheet for this product is attached on this page. It lists the electrical, mechanical and environmental data summarised above, and it is the document to check against your own drawings.
Send us the part number, quantity and application and we will confirm availability and a quotation. Seven Star LLC is an independent supplier in Muscat and is not affiliated with the manufacturer.
Datasheets & Documents
- Datasheet Schneider Electric LC1DT200ALSE Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.
Schneider Electric company profile
| Origins | 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry |
|---|---|
| Headquarters | Rueil-Malmaison (Paris region), France |
| Ownership | Public company listed on Euronext Paris |
| Key acquisitions | Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software |
| Brand names still in use | Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform |
| Product families | Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software |
Milestones
- 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
- 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
- 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
- 1997: Modicon, the company behind the first programmable logic controller, joins the group.
- 1999: The group takes the name Schneider Electric.
- 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.
Choosing Schneider Electric breakers and motor control
Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.
Where Schneider Electric products are used
In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.
APC by Schneider Electric: UPS and critical power
Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.
Schneider Electric products we list
| Family | Examples |
|---|---|
| Circuit breakers | Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW |
| Motor control | TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480 |
| Drives | Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo |
| PLCs, HMIs and relays | Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655 |
| Protection, metering and power | Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS |
Ordering Schneider Electric products: what we need
Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.
Facts checked against Schneider Electric's published company history, October 2026.
Browse Schneider Electric products by category: Circuit Breaker, Electrical & Power Modules, AC Drives, PLC & I/O Cards, Metering Systems, UPS and Batteries.
FAQ
Questions about the Schneider Electric LC1DT200ALSE 4P 200 A TeSys Deca
Answers from our engineering team on installation, compatibility and integration.
01What is the current rating of the LC1DT200ALSE?
The datasheet lists 200 A in AC-1 at up to 440 V AC (below 60 °C) for the power circuit, with a 4-pole, 4 NO arrangement.
02What coil voltage does the LC1DT200ALSE accept?
The datasheet gives a control circuit voltage of 200 to 500 V AC 50/60 Hz and 200 to 500 V DC, with an operating window of 0.8 to 1.1 Uc.
03What auxiliary contacts does the LC1DT200ALSE have?
The datasheet lists 1 NO + 1 NC mechanically linked, and the NC contact is described as a mirror contact according to IEC 60947-4-1.
04How are cables connected to the LC1DT200ALSE?
Power connections use connectors that accept 10 to 120 mm² (connector 1) and 10 to 50 mm² (connector 2) flexible cable, tightened to 12 N.m.
05What ambient temperature does the LC1DT200ALSE support?
The datasheet gives -40 to 60 °C operation, 60 to 70 °C with derating, and -60 to 80 °C storage.