Schneider Electric EZC100F3020 Easypact EZC100F 20 A 3P Breaker

Description

EZC100F3020: Easypact EZC100F 20 A thermal-magnetic breaker

The EZC100F3020 is an Easypact EZC100F molded case circuit breaker, three poles, with a TM-D thermal-magnetic trip unit rated 20 A at 50 °C. The datasheet gives 20 A at 40 °C as the rated current and lists both AC and DC networks. Seven Star LLC supplies the EZC100F3020 in Oman and the GCC as an independent supplier based in Muscat.

In this group of datasheets the EZC100F frame is offered at 20, 30, 40 and 50 A; the EZC100F3020 is the 20 A step. The reference is made of the family name EZC100F, the pole count 3 and the current in amperes, as the neighbouring titles show: EZC100F3020, EZC100F3030, EZC100F3040, EZC100F3050.

Size, mounting and connection of the EZC100F3020

The breaker is 130 mm high, 75 mm wide and 60 mm deep, mounted fixed on a backplate with front connections at top and bottom on a 25 mm pitch. The control is a toggle with positive contact indication, so the position of the contacts can be read from the handle.

The datasheet lists a mechanical durability of 13000 cycles and a protection degree of IP20 with IK07. IP20 is a finger-safe degree, so the breaker belongs inside an enclosure and not exposed in a hall.

EZC100F3020 technical specifications

Parameter Specification
Manufacturer / part number Schneider Electric / EZC100F3020
Range EasyPact EZC
Device Easypact EZC100F
Application Distribution
Poles / protected poles 3P / 3t
Network type / frequency DC, AC / 50/60 Hz
Rated current [In] 20 A at 40 °C
Rated insulation voltage [Ui] 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand [Uimp] 6 kV conforming to IEC 60947-2
Rated operational voltage [Ue] 550 V AC 50/60 Hz conforming to IEC 60947-2; 250 V DC conforming to IEC 60947-2
Breaking capacity code F
Ultimate breaking capacity [Icu] 25 kA at 110 to 130 V AC; 25 kA at 220 to 240 V AC; 5 kA at 125 V DC 1P; 5 kA at 250 V DC 2P; 5 kA at 550 V AC; 10 kA at 380 V AC; 10 kA at 400 to 415 V AC; 7.5 kA at 440 V AC
Service breaking capacity [Ics] 12.5 kA at 110/130 V AC; 12.5 kA at 220/230/240 V AC; 2.5 kA at 125 V DC; 2.5 kA at 250 V DC; 2.5 kA at 550 V AC; 5 kA at 380 V AC; 5 kA at 400/415 V AC; 3.75 kA at 440 V AC
Isolation suitability Yes conforming to IEC 60947-2
Utilisation category Category A
Trip unit TM-D, thermal-magnetic, 20 A at 50 °C
Protection Overload protection; Short-circuit protection
Control / mounting Toggle / Fixed, Backplate
Connections / pitch Front top, Front bottom / 25 mm
Mechanical durability 13000 cycles
Local signalling Positive contact indication
Dimensions H x W x D 130 mm x 75 mm x 60 mm
Standards EN/IEC 60947-1; EN/IEC 60947-2; GB/T 14048.2; JIS C8201-2-2
Protection degree IP20 conforming to IEC 60529; IK07 conforming to IEC 62262
Operating / storage temperature -25 to 70 °C / -35 to 85 °C
Pollution degree 3 conforming to IEC 60664-1

Selection and RFQ checklist for the EZC100F3020

  • Current: 20 A, checked against the load and the cable size.
  • Network: AC or DC, and for DC the number of poles in series against the datasheet values.
  • Fault level: 10 kA Icu at 400/415 V AC against the prospective current.
  • Space: 130 mm high, 75 mm wide, 60 mm deep, in an enclosure suited to IP20.
  • Accessories such as handles, locks and releases are separate references.

For the quotation send the part number EZC100F3020, quantity, system voltage and delivery date.

Breaking capacity and voltage limits of the EZC100F3020

The breaking capacity code is F. Ultimate Icu is 25 kA at 220 to 240 V AC and 10 kA at 400 to 415 V AC, with 7.5 kA at 440 V AC and 5 kA at 550 V AC. On DC the datasheet gives 5 kA at 125 V DC for one pole and 5 kA at 250 V DC for two poles.

Service capacity Ics is lower: 5 kA at 400/415 V AC and 12.5 kA at 220/230/240 V AC. Insulation voltage is 690 V AC 50/60 Hz and the impulse withstand is 6 kV, with the maximum operational voltage 550 V AC or 250 V DC.

Thermal-magnetic protection in the EZC100F3020

The TM-D trip unit gives overload protection through its thermal element and short-circuit protection through its magnetic element; the datasheet lists both under protection type. Adjustment values are not given on this datasheet, so any statement about threshold settings must come from the ordering documents.

The trip unit rating is 20 A at 50 °C, while the rated current is 20 A at 40 °C. As a worked example, a 20 A three-phase circuit at 400 V carries about 13.9 kVA, and a single-phase 20 A circuit at 230 V about 4.6 kVA. These are illustrative arithmetic, not datasheet values, but they help to judge if the breaker is sized close to the load.

EZC100F ratings around the EZC100F3020

The four references below share the frame, the trip unit type, the breaking capacity code and the dimensions; they differ in the rated current. Neighbours of the EZC100F3020 are EZC100F3030.

Part number Rated current Poles Trip unit Icu at 400/415 V
EZC100F3020 20 A 3P TM-D 10 kA at 400/415 V AC
EZC100F3030 30 A 3P TM-D 10 kA at 400/415 V AC
EZC100F3040 40 A 3P TM-D 10 kA at 400/415 V AC
EZC100F3050 50 A 3P TM-D 10 kA at 400/415 V AC

Where the EZC100F3020 fits in Oman and the GCC

A 20 A thermal-magnetic breaker of this type is typically found in small distribution boards, auxiliary supplies, pump and fan feeders, lighting and small-power circuits in commercial and industrial buildings, workshops and utility rooms. The datasheet operating range is -25 to 70 °C with storage at -35 to 85 °C.

In Oman, boards in plant rooms and in unshaded outdoor kiosks reach temperatures well above the reference temperature, so check the load against the temperature inside the enclosure. The datasheet lists pollution degree 3, a relevant point for dusty rooms and coastal humidity.

Choosing the 20 A step: the EZC100F3020 in practice

At 20 A this is the smallest step offered in the group. It suits short feeder circuits for lighting groups, small fans, socket circuits and control-panel supplies, where the cable is thin and tripping should happen early on overload. A lower rating also keeps the use-phase footprint in the datasheet the lowest of the four.

Pick it only if the continuous load, after allowing for the board temperature, is clearly under 20 A; for loads near the limit, the 30 A step is the next in the group.

The datasheet lists the single pack as 805 g, measuring 9.5 cm high, 8.5 cm wide and 14 cm long. Pack weights differ slightly between the four ratings in this group, which gives a quick way to check that a delivered box matches the reference.

The total lifecycle carbon footprint is given as 121 kg CO2 eq., of which 113 kg CO2 eq. is the use phase; the manufacturing phase is 7 kg CO2 eq. for all four references. The footprint grows with the current rating, and the use phase accounts for most of it.

Documents and quotation

The manufacturer datasheet for the EZC100F3020 is attached on this page. It lists the ratings and dimensions summarised above, so compare it with your single-line diagram and short-circuit study before you order.

Send us the part number, quantity and a few lines about the installation and we will reply with availability and a quotation. Seven Star LLC is an independent supplier in Muscat and is not part of the manufacturer’s own sales network.

Datasheets & Documents
  • PDF Datasheet Schneider Electric EZC100F3020 Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.

Schneider Electric company profile

Origins 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry
Headquarters Rueil-Malmaison (Paris region), France
Ownership Public company listed on Euronext Paris
Key acquisitions Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software
Brand names still in use Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform
Product families Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software

Milestones

  • 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
  • 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
  • 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
  • 1997: Modicon, the company behind the first programmable logic controller, joins the group.
  • 1999: The group takes the name Schneider Electric.
  • 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.

Choosing Schneider Electric breakers and motor control

Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.

Where Schneider Electric products are used

In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.

APC by Schneider Electric: UPS and critical power

Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.

Schneider Electric products we list

Family Examples
Circuit breakers Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW
Motor control TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480
Drives Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo
PLCs, HMIs and relays Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655
Protection, metering and power Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS

Ordering Schneider Electric products: what we need

Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.

Facts checked against Schneider Electric's published company history, October 2026.

FAQ

Questions about the Schneider Electric EZC100F3020 Easypact EZC100F 20

Answers from our engineering team on installation, compatibility and integration.

01What is the rated current of the EZC100F3020?
The datasheet gives 20 A at 40 °C for the breaker, with a TM-D trip unit rated 20 A at 50 °C.
02What breaking capacity does the EZC100F3020 have?
Icu is 25 kA at 220 to 240 V AC and 10 kA at 400 to 415 V AC, with the breaking capacity code F.
03Can the EZC100F3020 be used on DC?
The datasheet lists DC among the network types with an operational voltage of 250 V DC and 5 kA Icu at 250 V DC for two poles.
04What are the dimensions of the EZC100F3020?
The datasheet gives 130 mm high, 75 mm wide and 60 mm deep.
05What type of trip unit does the EZC100F3020 use?
A TM-D thermal-magnetic trip unit with overload and short-circuit protection.