Brand: Schneider Electric
Schneider Electric DBV318MF DBSeT VTPN 18-Way 125A Board
Description
DBV318MF: VTPN DBSeT 18-way flush-mount three-phase board
The DBV318MF is a Schneider Electric VTPN distribution board in the DBSeT range, a three-phase 125 A board with a modular incomer and 18 outgoer ways. The datasheet describes a distribution enclosure for low-voltage electrical distribution, supplied with a pan assembly, earthing bar and neutral bar behind a plain flat door, in the flush-mounting version. Seven Star LLC supplies the DBV318MF in Oman and the GCC as an independent supplier based in Muscat.
Reading the reference from its title and datasheet, DBV3 is the three-phase VTPN group, the digits that follow give the outgoer way count, and the closing letters MF or MS carry the modular 125 A incomer with flush or surface mounting. This is our reading of the naming and not a published ordering key, so rely on the datasheet for anything binding.
Technical specifications of the DBV318MF
| Parameter | Specification |
|---|---|
| Manufacturer / part number | Schneider Electric / DBV318MF |
| Range | DBSeT (VTPN) |
| Product type | Distribution board, distribution enclosure |
| Application | Low voltage electrical distribution |
| Number of ways | 18 ways (outgoer) |
| Rated current [In] | 125 A |
| Rated voltage | 240–415 V AC 50/60 Hz |
| Network | 3 phases |
| Rated short-time withstand [Icw] | 17 kA for 0.25 s |
| Rated peak withstand [Ipk] | 34 kA |
| Rated impulse withstand [Uimp] | 6 kV |
| Rated insulation voltage [Ui] | 500 V AC |
| Incomer device | Isolator, RCCB or isolator + RCCB (incomer) |
| Outgoer devices | MCB; RCBO |
| Provided equipment | Pan assembly, earthing bar, neutral bar, enclosure |
| Mounting | Flush |
| Door | Plain flat door |
| Cable entry | Removable gland plate at top and bottom |
| Material / colour | Painted sheet steel 1.2 mm thick / White (RAL 9003) |
| Width / height / depth | 425 / 555 / 124.9 mm |
| IP / IK | IP41 conforming to IEC 60529; IK08 |
| Operating ambient temperature | 50 °C |
| Standards | IEC 61439-3, IEC 61439-1 |
| Product certification | DEKRA |
| Packed weight | 12.1 kg |
| Package size (L / W / H) | 57.5 cm / 44.5 cm / 13.6 cm |
| Warranty | 18 months |
Comparing the DBV318MF with its siblings
The table lists each flush-mount 125 A modular-incomer board of the DBV group with the figures from its datasheet.
| Reference | Outgoer ways | W × H × D (mm) | Packed weight |
|---|---|---|---|
| DBV312MF | 12 | 425 × 465 × 124.9 | 10 kg |
| DBV318MF | 18 | 425 × 555 × 124.9 | 12.1 kg |
| DBV324MF | 24 | 425 × 555 × 124.9 | 12.7 kg |
| DBV330MF | 30 | 425 × 685 × 124.9 | 16 kg |
| DBV336MF | 36 | 425 × 685 × 124.9 | 16 kg |
| DBV342MF | 42 | 425 × 715 × 124.9 | 17 kg |
Rating, voltage and short-circuit values stay constant in this group while way count, height and weight rise.
Selection checklist and RFQ information for DBV318MF
- Confirm a three-phase 240–415 V AC, 50/60 Hz supply and a maximum of 125 A.
- Compare the prospective fault level with 17 kA for 0.25 s and 34 kA peak.
- Count outgoers against 18 ways and allow for multi-pole devices and spares.
- Verify wall space or recess for 425 × 555 × 124.9 mm and the flush mounting.
- Decide on the incomer: an isolator, RCCB or both, and whether devices are quoted with the board.
For the RFQ please send the reference, quantity, delivery location, project name and a draft circuit schedule if available.
Where the DBV318MF fits in Oman and the GCC
A 125 A modular incomer suits a floor or a smaller building: apartments, retail units, offices, site accommodation and utility rooms across Oman and the GCC. Typical loads are lighting, air-conditioning units, pumps and small machines on 18 outgoer ways.
Summer heat is the main stress. Compare the 50 °C ambient limit and the IP41 rating with the real room, because an air-conditioned electrical room is generally suitable while a roof cabinet or unventilated cabin in direct sun may not be. Mention dust and humidity when you enquire.
Installing and maintaining the DBV318MF
The enclosure is painted sheet steel, 1.2 mm thick, finished in White (RAL 9003), rated IP41 under IEC 60529 and IK08, for an ambient operating temperature of 50 °C. IP41 means indoor, dry rooms; it does not cover splash, outdoor or heavy dust exposure.
The DBV318MF ships as an enclosure with pan assembly and bars, so the electrician fits the incomer and outgoer devices on site, connects neutral and earth to their bars, labels each way and tightens terminals to the device torque values. Test RCDs, record readings in the commissioning file and use thermal imaging under load during service to find loose connections. The datasheet lists an 18-month warranty.
Flush mounting of the DBV318MF
The flush version is built into a wall recess so that only the frame and door project from the finished surface. Its enclosure measures 425 × 555 × 124.9 mm (W × H × D), so the recess must be formed at first fix with room for conduit or feeder entry. The packed weight is 12.1 kg and the carton measures 57.5 cm by 44.5 cm by 13.6 cm; handle it with two people and keep it upright and dry until it is fitted.
Cables enter through the removable gland plate at the top and bottom of the enclosure. The surface-mounted twin is the DBV318MS, listed at 555 mm height and 12.3 kg packed weight, so the two are not identical in every figure; measure from the datasheet of the exact reference.
What 18 outgoer ways mean for the DBV318MF
The datasheet lists 18 ways (outgoer). That is a count of single-pole positions on one bank, and a three-pole breaker or an RCBO uses more than one of them, so plan the layout from a device list with spare positions at the end. At a height of 555 mm and a packed weight of 12.1 kg, the DBV318MF is a mid-size board in its group.
The next size down is the DBV312MF with 12 ways, and the next size up is the DBV324MF with 24 ways. Width stays at 425 mm throughout the group; only height, weight and way count change.
Modular incomer and short-circuit ratings of the DBV318MF
The DBV318MF is rated 125 A at 240–415 V AC, 50/60 Hz, three phases. The datasheet lists a rated short-time withstand current (Icw) of 17 kA for 0.25 s, a rated peak withstand current (Ipk) of 34 kA, an impulse withstand voltage (Uimp) of 6 kV and an insulation voltage (Ui) of 500 V AC. The assembly standards are IEC 61439-3 and IEC 61439-1 and the datasheet shows DEKRA certification.
The incoming side is intended for modular apparatus: an isolator, an RCCB or an isolator with an RCCB, while MCBs and RCBOs serve the outgoing circuits. Because the incomer is a modular device and not a moulded-case breaker, the DBV318MF suits a main supply up to 125 A. Where the feeder is larger, the 250 A NSX-type boards of the same family are the ones to look at. Compare the Icw and Ipk values with the prospective fault current at the installation point and with the data of the actual devices.
Documents and quotation
An official datasheet for the DBV318MF is attached on this page. It carries the electrical ratings, enclosure details, packing data and environmental profile summarised above.
To request a quotation, send the part number, quantity and delivery location. Seven Star LLC will confirm lead time and commercial terms and can quote related devices with the board.
Other Models in the Se Dbset Dbv M Range
Seven Star LLC supplies models from the Se Dbset Dbv M range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| Schneider Electric DBV312MF DBSeT VTPN 12-Way 125A Board | Switchgear, Enclosures & Distribution | View details |
| Schneider Electric DBV312MS DBSeT VTPN 12-Way 125A Board | Switchgear, Enclosures & Distribution | View details |
| Schneider Electric DBV318MF DBSeT VTPN 18-Way 125A Board | Switchgear, Enclosures & Distribution | You are viewing this model |
| Schneider Electric DBV318MS DBSeT VTPN 18-Way 125A Board | Switchgear, Enclosures & Distribution | View details |
| Schneider Electric DBV324MF DBSeT VTPN 24-Way 125A Board | Switchgear, Enclosures & Distribution | View details |
| Schneider Electric DBV324MS DBSeT VTPN 24-Way 125A Board | Switchgear, Enclosures & Distribution | View details |
Datasheets & Documents
- Datasheet Schneider Electric DBV318MF Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Schneider Electric is the French group for energy management and industrial automation: low and medium voltage switchgear and circuit breakers, motor control, drives, PLCs, power monitoring, UPS systems and building management. Its history goes back to 1836, when the brothers Adolphe and Eugène Schneider took over the iron and steel works at Le Creusot in Burgundy. Over the 20th century the company left steel and heavy engineering and became an electrical group through acquisitions such as Merlin Gerin, Télémécanique, Square D and Modicon. Its head office is in Rueil-Malmaison near Paris, and its shares are listed on Euronext Paris.
Schneider Electric company profile
| Origins | 1836, Le Creusot, France: Adolphe and Eugène Schneider take over the Le Creusot foundry |
|---|---|
| Headquarters | Rueil-Malmaison (Paris region), France |
| Ownership | Public company listed on Euronext Paris |
| Key acquisitions | Télémécanique (1988), Square D (1991), Merlin Gerin (1992), Modicon (1997), APC (2007), Invensys (2014); majority owner of AVEVA software |
| Brand names still in use | Acti9, ComPacT and MasterPacT breakers, TeSys motor control, Altivar drives, Altistart soft starters, Modicon PLCs, Harmony control components, PowerLogic and Easergy protection and metering, APC UPS, EcoStruxure software platform |
| Product families | Low voltage distribution, medium voltage switchgear and protection relays, motor control and drives, PLCs and HMIs, power meters, UPS and cooling, enclosures, building automation and energy software |
Milestones
- 1836: The Schneider brothers acquire the Le Creusot works; the business grows in steel, locomotives and heavy engineering.
- 1975: First investment in Merlin Gerin, a French maker of electrical distribution equipment.
- 1988–1992: Télémécanique, Square D (USA) and Merlin Gerin join the group, making it an electrical specialist.
- 1997: Modicon, the company behind the first programmable logic controller, joins the group.
- 1999: The group takes the name Schneider Electric.
- 2007 and 2014: APC (UPS and data centre power) and Invensys (process automation) are acquired.
Choosing Schneider Electric breakers and motor control
Circuit breakers are chosen by current and breaking capacity. Acti9 miniature circuit breakers (iC60, C120) protect final circuits up to 125 A. ComPacT NSX molded case breakers cover about 16 to 630 A, and the letter after the frame size sets the breaking capacity: B, F, N, H, S, L from lowest to highest. MasterPacT air circuit breakers are used as main incomers on large switchboards. For motors, a TeSys contactor with an LRD overload relay or a GV2 motor circuit breaker suits direct starting, an Altistart soft starter reduces starting current, and an Altivar drive controls speed. The breaking capacity must always be at least the prospective short-circuit current at the point of installation.
Where Schneider Electric products are used
In Oman and the GCC, Schneider Electric equipment is found in main and sub-main switchboards of commercial and residential buildings, motor control centres in water, oil and gas and industrial plants, substations protected by Sepam and Easergy relays, data centres powered by Galaxy and APC UPS systems, and buildings controlled by EcoStruxure Building Operation.
APC by Schneider Electric: UPS and critical power
Since 2007, APC has been part of Schneider Electric and is now its product brand for uninterruptible power supplies, replacement batteries, battery packs, network management cards and rack power distribution. Our APC catalogue covers Smart-UPS line-interactive and on-line models, Easy UPS On-Line, the modular Symmetra LX, RM and PX ranges, Silcon three-phase systems and their spare part kits, and the RBC cartridges that keep them running. Schneider Electric breakers, drives and PLCs can be quoted together with APC UPS systems in one request.
Schneider Electric products we list
| Family | Examples |
|---|---|
| Circuit breakers | Acti9 iC60N, C120N, NSX100F, NSX250N, NSX630, EasyPact EZC, MasterPacT MTZ1, MasterPacT NW |
| Motor control | TeSys Deca LC1D, TeSys F, LRD overload relay, GV2ME08, Altistart 22, Altistart 480 |
| Drives | Altivar 12, Altivar 320, ATV340, Altivar Process 630, ATV930, Lexium 32 servo |
| PLCs, HMIs and relays | Modicon M221, M241, M580 BMEP582040, Zelio Logic, Magelis HMISTU655 |
| Protection, metering and power | Sepam series 20, Easergy P3U30, MiCOM P139, PM5560, iEM3255, Galaxy VS UPS |
Ordering Schneider Electric products: what we need
Send the commercial reference from the label (for example LC1D18M7 or ATV320U22N4C). For breakers, confirm the rated current, number of poles, breaking capacity and trip unit. For contactors, give the coil voltage. For drives, give the motor power and supply voltage. APC products are listed on their own brand page.
Facts checked against Schneider Electric's published company history, October 2026.
Browse Schneider Electric products by category: Circuit Breaker, Electrical & Power Modules, AC Drives, PLC & I/O Cards, Metering Systems, UPS and Batteries.
FAQ
Questions about the Schneider Electric DBV318MF DBSeT VTPN 18-Way 125A
Answers from our engineering team on installation, compatibility and integration.
01What incomer does the DBV318MF take?
The datasheet lists an isolator, an RCCB or an isolator with RCCB as incomer, up to the 125 A rating of the board.
02What short-circuit ratings are listed for the DBV318MF?
The datasheet gives 17 kA for 0.25 s (Icw) and 34 kA peak (Ipk), with 6 kV impulse withstand and 500 V AC insulation voltage. Compare them with the prospective fault level at site.
03How many outgoer ways does the DBV318MF have?
The datasheet lists 18 ways (outgoer), 18 single-pole positions in total. Multi-pole breakers and RCBOs take more than one position.
04Does the DBV318MF include breakers?
No. The listed equipment is a pan assembly, earthing bar, neutral bar and enclosure, so the incomer, MCBs and RCBOs are fitted separately.
05How is the DBV318MF installed and where?
It is recessed into a wall, rated IP41 and IK08 with a 50 degC ambient limit, so it is for indoor dry rooms. The enclosure is 425 by 555 by 124.9 mm.