Moxa MGate 5118 J1939 to Modbus/PROFINET Gateway
Description
How the MGate 5118 bridges protocols
A gateway that reads SAE J1939 engine and generator data from a CAN bus and presents it to Modbus, PROFINET or EtherNet/IP controllers. Moxa’s own one-line description of the MGate 5118 reads: 1-port J1939 to Modbus/PROFINET/EtherNet/IP gateway, 0 to 60°C operating temperature.
Key figures from the Moxa page: the power input is 12 to 48 VDC; operating temperature is 0 to 60°C (32 to 140°F); dimensions are 45.8 x 105 x 134 mm (1.8 x 4.13 x 5.28 in); weight is 589 g (1.30 lb); the enclosure is rated IP30.
Standards and approvals printed for this model include hazardous-location listings of ATEX, Class I Division 2, IECEx; safety standard EN 62368-1, UL 61010-2-201. Approvals can differ between variants of a series, so check the one on the exact order code.
Technical specifications
| Parameter | Specification |
|---|---|
| Magnetic Isolation Protection | 1.5 kV (built-in) |
| Time Management | NTP Client |
| Authentication | Local database |
| Serial Interface: No. of Ports | 1 |
| Serial Interface: Connector | DB9 male |
| Serial Standards | RS-232/422/485 |
| Serial Interface: Baudrate | 50 bps to 921.6 kbps |
| Data Bits | 7, 8 |
| Stop Bits | 1, 2 |
| Terminator for RS-485 | 120 ohms |
| Serial Interface: Isolation | 2 kV |
| RS-485-2w | Data+, Data-, GND |
| Modbus RTU/ASCII: Mode | Master, Slave |
| Modbus RTU/ASCII: Max. No. of Commands | 128 |
| Max. No. of Client Connections | 16 |
| Max. No. of Server Connections | 32 |
| Modbus TCP: Max. No. of Commands | 128 |
| PROFINET: Mode | IO Device |
| Max. No. of IO Controller Connections | 1 (for read/write) |
| PROFINET: Input Data Size | 512 bytes |
| PROFINET: Output Data Size | 512 bytes |
| EtherNet/IP: Mode | Scanner, Adapter |
| Max. No. of Adapter Connections | 4 |
| EtherNet/IP: Input Data Size | 496 bytes |
| EtherNet/IP: Output Data Size | 496 bytes |
| CAN Interface: Industrial Protocols | J1939 |
| CAN Interface: No. of Ports | 1 |
| Terminator | 120 ohms |
| CAN Interface: Isolation | 2 kV (built-in) |
| J1939: Max. No. of Commands | 256 |
| J1939: Input Data Size | 2048 bytes |
| J1939: Output Data Size | 2048 bytes |
| Input Voltage | 12 to 48 VDC |
| Input Current | 416 mA @ 12 VDC |
| Housing | Metal |
| IP Rating | IP30 |
| Weight | 589 g (1.30 lb) |
| EMC | EN 61000-6-2/-6-4 |
| EMS | IEC 61000-4-2 ESD: Contact: 8 kV; Air: 15 kV; IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m; IEC 61000-4-4 EFT: Power: 4 kV; Signal: 4 kV; IEC 61000-4-5 Surge: Power: 2 … |
| Hazardous Locations | ATEX, Class I Division 2, IECEx |
| Freefall | IEC 60068-2-32 |
| Shock | IEC 60068-2-27 |
| Vibration | IEC 60068-2-6, IEC 60068-2-64 |
| Warranty Period | 5 years |
Selecting the right variant
It is a practical answer for monitoring diesel engines, gensets and compressors in power and oil and gas sites from standard SCADA systems.
On the practical side, the housing is metal; the stated MTBF is 727,873 hrs; the warranty period is 5 years. Treat the MTBF as a manufacturer prediction under its stated method, not a guarantee for your site.
Please check the J1939 parameter groups you need and the temperature grade before you place an order. Seven Star LLC supplies as an independent company and prices against the precise code requested.
For wiring and sizing, the J1939 side is one CAN port on a spring-type Euroblock terminal, selectable at 250 kbps, 500 kbps or 1 Mbps, with a 120 ohm terminator and 2 kV isolation. The datasheet lists up to 256 J1939 commands and 2048 bytes of input and output data. On the Ethernet side, EtherNet/IP works as scanner or adapter (four adapter connections) and PROFINET as an IO device with 512 bytes each way. Check the engine controller baud rate and the parameter groups you need before commissioning, and terminate the CAN bus only at its two physical ends.
Documents and quotation
Download the official Moxa datasheet (moxa-mgate-5118-series-datasheet-v1.4) from this page and send us your order code, quantity and destination for a quotation.
More products in this range: Industrial Communications.
Datasheets & Documents
- Datasheet Moxa MGate 5118 series datasheet v1.4 Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Moxa is the Taiwanese maker of industrial networking equipment: Ethernet switches, serial device servers, protocol gateways, media converters, secure routers and remote I/O. It was founded in Taiwan in 1987 and started with serial communication products before moving into industrial Ethernet. It is headquartered in Taipei.
Seven Star LLC is an independent supplier in Muscat. We list Moxa switches, serial servers, gateways and converters, and supply them to control system integrators, utilities, oil and gas and building automation projects in Oman and the GCC by exact model.
Moxa at a glance
| Established | 1987, Taiwan |
|---|---|
| Headquarters | Taipei, Taiwan |
| First products | Serial communication boards and serial connectivity |
| Product families | Unmanaged, managed and rackmount industrial Ethernet switches, serial device servers, Modbus and fieldbus gateways, media converters, serial converters, secure routers, remote I/O and industrial computers |
Moxa products we list
| Family | Models | Typical use |
|---|---|---|
| Unmanaged switches | EDS-205A, EDS-208A, EDS-2008-EL, EDS-2010-ML, EDS-308, EDS-316, EDS-G2005-EL, EDS-G205, EDS-G308, EDS-P206A PoE | Simple plug-and-play networks inside control panels |
| Managed switches | EDS-405A, EDS-408A, EDS-508A, EDS-510A, EDS-510E, EDS-518A, EDS-528E, EDS-G508E, EDS-G509, EDS-G512E, ICS-G7528A rackmount | Redundant ring networks, VLANs and diagnostics for SCADA and DCS |
| Serial device servers | NPort 5110A, 5150A, 5210A, 5250A, 5410, 5450, 5610-8, 5650-8, 6150, IA5150A | Putting RS-232/422/485 devices on an Ethernet network |
| Protocol gateways | MGate MB3180, MB3170, MB3280, MB3270, 5101-PBM-MN, 5105-MB-EIP, 5109 DNP3, 5114 IEC 104 | Linking Modbus RTU/TCP, PROFIBUS, EtherNet/IP, DNP3 and IEC 60870-5-104 systems |
| Converters, routers and I/O | IMC-21A, IMC-101, IMC-21GA, TCF-142, TCC-100, TCC-80, TCC-120, EDR-G9010 router, ioLogik E2210 | Fibre links over long distances, serial conversion, network security and remote I/O |
The choice between switch types follows the network. An unmanaged switch simply forwards traffic and suits a small, isolated panel. A managed switch adds redundancy protocols (Moxa's Turbo Ring recovers a broken ring in milliseconds), VLANs to separate traffic, port mirroring and alarms, which a SCADA or DCS network needs. The suffix on a Moxa model also matters: "-T" means a wide operating temperature range (typically -40 to 75 °C), which is the safe choice for outdoor cabinets in the Gulf summer. "-MM-SC" or "-S-SC" means multi-mode or single-mode fibre with SC connectors.
Where Moxa products are used
In Oman and the GCC, Moxa equipment connects RTUs, PLCs, meters and protection relays in oil and gas fields, electrical substations, water and wastewater SCADA, transport, and building and energy management systems.
Ordering Moxa products: what we need
Send the complete model including all suffixes (for example EDS-508A-MM-SC-T), the quantity, and for fibre models the fibre type and distance. For gateways, tell us which two protocols need to be linked.
Facts checked against Moxa company information, October 2026.
Browse MOXA products by category: Industrial Communications.
Related products
Frequently Asked Questions
Moxa lists it as: 1-port J1939 to Modbus/PROFINET/EtherNet/IP gateway, 0 to 60°C operating temperature. A gateway that reads SAE J1939 engine and generator data from a CAN bus and presents it to Modbus, PROFINET or EtherNet/IP controllers.
The Moxa specification gives an input voltage of 12 to 48 VDC. Check the terminal arrangement and, where relevant, the redundant-input wiring against your panel supply before ordering.
The listed operating temperature is 0 to 60°C (32 to 140°F). Wide-temperature versions carry a -T suffix in Moxa's order codes where the series offers them, and they are separate order codes.
Per Moxa's description, it is a 1-port J1939 to Modbus/PROFINET/EtherNet/IP gateway. Industrial protocols listed on the Ethernet side: Modbus TCP Client (Master), Modbus TCP Server (Slave), PROFINET IO Device, EtherNet/IP Scanner, EtherNet/IP Adapter.