ifm SI5000 Flow Monitor, Calorimetric, Liquids and Gases, 30 bar
Description
ifm SI5000 Flow Monitor, Calorimetric, Liquids and Gases, 30 bar
The ifm SI5000 is a flow monitor for liquids and gases in pipes. It has a stainless steel (316L) probe 45 mm long and 8.2 mm in diameter, a threaded connection with an M18 x 1.5 internal thread and an adapter system for other process connections, and it withstands 30 bar. The medium temperature is -25 to 80 degrees Celsius.
A PNP switching output, normally open or normally closed, carries up to 250 mA, with a response time of 1 to 10 seconds. The supply is 19 to 36 V DC at less than 60 mA, protection is IP67, and an LED bar graph shows the switch point and flow. Seven Star LLC supplies the ifm SI5000 in Oman and the GCC as an independent supplier in Muscat.
SI5000 technical specifications
The table lists the values published by the manufacturer for the SI5000. Where a parameter has several operating modes, the headline value is shown; the full parameter list is in the manufacturer documentation.
| Parameter | Specification |
|---|---|
| Manufacturer / part number | ifm electronic / SI5000 |
| Process connection | threaded connection M18 x 1.5 internal thread |
| Dimensions [mm] | Ø 50 / L = 113 |
| Probe length L [mm] | 45 |
| Installation length EL [mm] | 45 |
| Probe diameter [mm] | 8.2 |
| Media | Liquids; Gases |
| Medium temperature [°C] | -25 to 80 |
| Pressure rating | 30 bar / 3 MPa |
| Operating voltage [V] | 19 to 36 DC |
| Current consumption [mA] | < 60 |
| Output signal | switching signal |
| Electrical design | PNP |
| Output function | normally open / normally closed (parameterisable) |
| Permanent current rating of switching output DC [mA] | 250 |
| Response time [s] | 1 to 10 |
| Ambient temperature [°C] | -25 to 80 |
| Protection | IP 67 |
| Weight [g] | 246 |
| Materials | stainless steel (316L/1.4404); stainless steel (301/1.4310); PC; PBT-GF20; EPDM/X |
| Materials (wetted parts) | stainless steel (316L/1.4404); O-ring: FKM 80 Shore A |
| Connector | 1 x M12; coding: A; Contacts: 4 |
| MTTF [years] | 298 |
How the SI5000 works
The SI5000 uses the calorimetric principle: one element in the probe tip is heated and a second element reads the medium temperature. The faster the medium flows past the probe, the more heat it carries away, and the electronics translate that difference into flow velocity. Because the sensor measures flow and temperature at the same time, one device can supply both a flow switch signal and a temperature value. The medium selection in the menu adapts the evaluation to water, glycol, oil or air, and the relative mode lets you tune the response to the actual installation.
Where the SI5000 fits and related parts
The SI5000 is a flow monitor with no moving parts, used to watch for presence or absence of flow in cooling water, lubrication and air lines. The SA5000 in our range is a flow sensor with further output options, and the magnetic-inductive SM6004 measures conductive liquids with higher accuracy.
Selection and ordering checklist for the SI5000
Work through the points below before you confirm the order, so that the SI5000 you receive is the one your machine or plant needs.
- Define the medium and its temperature
- Check the pipe size and adapter for the M18 x 1.5 connection
- Confirm the pressure below 30 bar
- Choose normally open or normally closed
- Decide whether the 1 to 10 second response suits the alarm
The manufacturer lists this article under the type designation Flow monitor, SID10ABBFPKG/US-100. The article number SI5000 is the reference to quote when ordering, and the type designation is useful for technicians who compare the label on an installed unit.
Installation, commissioning and maintenance
Insert the probe into the pipe or fitting so that the tip sits in the middle of the flow with the stated installation length, orient it as the documentation describes, and tighten the process thread within the allowed torque. Allow a straight run before the sensor so the flow profile is stable. For commissioning, choose the medium, run the system at normal flow and teach the switch point, then confirm the response by throttling the flow. Deposits on the probe tip reduce sensitivity, so include it in cleaning rounds on dirty circuits, and re-check the setting after any change in medium temperature.
Typical applications in Oman and the GCC
Cooling water protection for compressors, gearboxes and heat exchangers, lubrication line checks and dry-run protection for pumps. In Oman and the GCC it is used on chilled and cooling water circuits where loss of flow can damage equipment within minutes.
Flow meters in the region often sit in cooling and utility circuits that run year-round at high ambient temperature. Scale, bubbles and dirt are the main sources of error, so strainers upstream and a full pipe at the measuring point matter more than any setting in the menu.
SI5000 compared with related ifm types
The table places the SI5000 next to neighbouring types in the same application group, so you can see whether a sibling would suit the job better.
| Part number | Key characteristics | Note |
|---|---|---|
| SI5000 | Calorimetric, M18 x 1.5, 30 bar, liquids and gases | This page |
| SV4200 | Vortex, G 1/2, 1-20 l/min, to 90 C, IO-Link | Related type |
| SM6000 | Mag-inductive, G 1/2 ext., 0.1-25 l/min, 16 bar | Related type |
| SM6004 | Magnetic-inductive flow meter | Related type |
| SM8000 | Magnetic-inductive flow meter | Related type |
| SA5000 | Flow sensor | Related type |
Information to send with an RFQ for the SI5000
To prepare an accurate offer for the SI5000, please include the following with your enquiry:
- Medium (water, glycol, oil or air) and viscosity
- Pipe size and the fitting or adapter used
- Flow velocity range and switching point
- Required outputs and IO-Link availability
- Quantity and delivery location
Documents and quotation
The official ifm data sheet for the SI5000 (document SI5000-01, English, issued 13 April 2023) is attached on this page as a PDF. It sets out the electrical data, the output function, the operating conditions, the approvals and the dimension drawing for this article. Check these values and the wiring diagram against your application before ordering, then send us the quantity and the delivery location for a quotation.
Seven Star LLC is an independent supplier in Muscat serving Oman and the GCC and is not affiliated with the manufacturer; the name ifm is used only to identify the product. Prices are not shown on the page, so send the part number, the quantity and the delivery location to receive a quotation.
Other Models in the Ifm61 Flow Range
Seven Star LLC supplies models from the Ifm61 Flow range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.
| Model | Category | |
|---|---|---|
| ifm SI5000 Flow Monitor, Calorimetric, Liquids and Gases, 30 bar | Automation Accessories | You are viewing this model |
| ifm SV4200 Vortex Flow Meter with Display, G 1/2, 1-20 l/min | Automation Accessories | View details |
| ifm SM6000 Magnetic-Inductive Flow Meter, G 1/2, 0.1-25 l/min | Automation Accessories | View details |
Datasheets & Documents
- Datasheet ifm SI5000 Data Sheet (PDF) Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
ifm is a German family-owned maker of sensors and automation products, founded in Essen in October 1969 by Robert Buck and Gerd Marhofer. Its first products were inductive proximity sensors sold under the efector name. ifm is still headquartered in Essen, and the founders' sons, Martin Buck and Michael Marhofer, have led it since 2001.
Seven Star LLC lists ifm position, distance and pressure sensors and supplies them by exact article number to plants and machine builders in Oman and the wider Gulf region.
ifm company profile
| Founded | 1969, Essen, Germany |
|---|---|
| Founders | Robert Buck and Gerd Marhofer |
| Headquarters | Essen, Germany |
| Ownership | Family-owned |
| Product families | Inductive and capacitive proximity sensors, PN pressure sensors, O1D laser distance sensors, flow and level sensors, IO-Link masters |
Milestones
- 1969: ifm is founded in Essen.
- 2001: The founders' sons take over management.
ifm sensors listed on this page
ifm identifies every device with a short article number, and that number is what we order against. Three are listed here:
- O1D100: laser distance sensor for position and distance measurement
- PN7093: pressure sensor with local display
- NG5021: inductive proximity sensor with NAMUR output
Other ifm inductive sensors, pressure sensors and connection cables can be quoted on request when you send the article number.
ifm products we list
Ordering ifm sensors: what we need
Send the six-character article number printed on the housing (two letters and four digits, or similar). If the label is worn, a photo plus the thread size, sensing range, output type and connector style is enough for us to check the part against ifm documentation. For NAMUR sensors, tell us which isolating amplifier is in the loop. Buyers in the GCC who need a successor for a discontinued article can send the old number and we will check the replacement the manufacturer names.
Facts checked against ifm's own 50-year chronicle (ifm.com), October 2026.
Browse ifm products by category: Sensors & Transmitters, Pressure Instrumentation.
FAQ
Questions about the ifm SI5000 Flow Monitor, Calorimetric, Liquids and
Answers from our engineering team on installation, compatibility and integration.
01What media can the ifm SI5000 monitor?
Liquids and gases. This is the value published by the manufacturer for the SI5000; confirm details before ordering.
02What is the pressure rating of the SI5000?
30 bar (3 MPa). This is the value published by the manufacturer for the SI5000; confirm details before ordering.
03What process connection does the SI5000 have?
An M18 x 1.5 internal thread, with adapters for other connections.
04How fast does the SI5000 respond?
The response time is 1 to 10 seconds. This is the value published by the manufacturer for the SI5000; confirm details before ordering.
05What temperature range applies to the SI5000 medium?
-25 to 80 degrees Celsius. This is the value published by the manufacturer for the SI5000; confirm details before ordering.