Brand:

Autonics TK4M-14RN 72×72 PID Temperature Controller Relay

Description

Overview

The Autonics TK4M-14RN is the large-display model of the TK series of PID temperature controllers: a 72 x 72 mm DIN panel unit with a big four-digit red process value and green setpoint display, powered from 100 to 240 V AC and driving a relay for heating or cooling. When operators must read temperature across a workshop or from a walkway, this is the size that is chosen. Seven Star LLC is an independent supplier serving Oman and the GCC.

Decoding Autonics TK4M-14RN

TK4 means the four-digit TK series. The letter M selects the 72 x 72 mm DIN size. The digit 1 is the option input and output group, which for this size is a single alarm output. The following 4 means a supply of 100 to 240 V AC at 50/60 Hz, whereas 2 would give 24 V AC or 24 to 48 V DC. R states that output 1 is a relay, as opposed to S for SSR drive or C for selectable current or SSR drive. The last letter N means normal type with no second control output, so the controller does heating or cooling control and not both at once.

Specifications for Autonics TK4M-14RN

Item Data
Front size 72 x 72 mm, panel cut-out 68 mm square
Display 4-digit 7-segment LED, PV red, SV green
Supply 100 to 240 V AC 50/60 Hz, permissible 90 to 110 percent
OUT1 Relay 250 V AC 3 A, 30 V DC 3 A, 1a
Alarm Alarm 1, relay 250 V AC 3 A, 1a
Thermocouple inputs K, J, E, T, B, R, S, N, C, G, L, U and Platinel II
RTD inputs Cu50, Cu100, JPt100, DPt50, DPt100, Nickel120
Analog inputs 0-10 V, 0-5 V, 1-5 V, 0-100 mV, 0-20 mA, 4-20 mA
Sampling period 50 ms
Control modes ON/OFF, P, PI, PD, PID; heating, cooling or heating and cooling
Display accuracy PV plus or minus 0.3 percent or plus or minus 1 degree C, whichever is greater, plus 1 digit, at 23 degrees C plus or minus 5
Relay life 5 million mechanical operations, 100,000 electrical (output)
Memory About 10 years, non-volatile
Dielectric strength 3,000 V AC for 1 minute (AC type)
Ambient minus 10 to plus 50 degrees C, 35 to 85 percent RH
Protection IP65 front panel
Weight about 140 g, about 210 g packaged

How the Autonics TK4M-14RN differs from other TK4 variants

All TK models share the same control engine and input table, so the differences are physical and in the outputs. The TK4S is 48 x 48 mm and weighs about 105 g, the TK4SP uses an 11-pin plug and is rated only IP50 at the front, and the TK4H is 48 x 96 mm at about 141 g. The Autonics TK4M-14RN is the roomiest of the square models: its cut-out of 68 mm compares with 45 mm for the TK4S, and the weight of about 140 g is the highest of the square family. Within the 72 mm size, the code 14RN keeps one alarm and one relay output; the 2, R, T, A, B and D options replace the single alarm with a second alarm, transmission output, RS485 or digital inputs.

Inputs and range selection

One controller accepts thermocouples, RTDs and analog signals, and the type is selected in a parameter. With thermocouple K the range is minus 200 to 1,350 degrees C at 1 degree resolution, or minus 199.9 to 999.9 degrees C with a decimal point. Thermocouple J covers minus 200 to 800 degrees C, R and S go from 0 to 1,750 degrees C, and B from 0 to 1,800 degrees C. Pt100 sensors, in the JPt and DPt types, read minus 200 to 650 degrees C. Analog inputs include 4 to 20 mA and 0 to 10 V. Permissible lead resistance per line is 5 ohm or less.

Control functions

The controller offers ON/OFF, P, PI, PD and PID algorithms. The proportional band is adjustable from 0.1 to 999.9, integral time from 0 to 9,999 seconds and derivative time also 0 to 9,999 seconds. The control cycle of the relay output is 0.1 to 120 seconds, and a manual reset of 0.0 to 100.0 percent is available. An auto tuning routine finds the PID values, indicated by a flashing AT lamp. Because a relay is a mechanical contact, choose a cycle long enough to protect it, such as 10 to 20 seconds on a heater with a thermal mass, and consider an SSR drive model for fast loops.

Typical uses in Oman and the GCC

Large-display PID units fit ovens, kilns, plastic extruders, hot-melt tanks, heat treatment furnaces, water baths, environmental chambers and boiler skids. In hot-climate plants they also monitor cabinet temperature and process fluid temperature. The IP65 front resists dust and splashes from cleaning, while the maximum ambient of 50 degrees C is the number to check when the panel sits in direct sun or near the furnace wall.

Installation and wiring

Cut the panel opening to 68 mm square, push the controller through and fasten it with the bracket by pressing it with a flathead screwdriver. Use AWG 20 or heavier cable for the supply and relay, and AWG 28 to 16 for the sensor, and tighten terminal screws to 0.74 to 0.90 N m. Check polarity of the sensor terminals, and for a three-wire RTD use three wires of the same gauge and length. Do not wire unused terminals.

Alarms, faults and care

If the sensor wire breaks, the PV display flashes OPEN at 0.5 second intervals, and the output goes to the value set in the sensor error MV parameter, which gives a defined fail-safe state. Check the sensor first, then terminal tightness. Relay contacts wear out according to switching count, so log how often the output switches and plan replacement. Wipe the front with a dry cloth and keep the key lock set to prevent accidental changes.

Related items you may also need: Autonics E40S6-2500-6-L-5 Rotary Encoder Incremental | SICK KTX-WP91142252ZZZZ KTX Contrast Sensor, Short-Side Emission | SICK WTB2S-2P1151 Proximity Sensor | All Autonics products.

Documents and quotation

The TK series product manual covering the Autonics TK4M-14RN is attached to this page, with the ordering code table, input ranges, wiring diagrams and cut-out dimensions. Send an RFQ with the part number Autonics TK4M-14RN, quantity and delivery location in Oman or the GCC.

Other Models in the TK Range

Seven Star LLC supplies models from the TK range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Autonics TK4S-14RN PID Temperature Controller 48×48 mmControllers & Data AcquisitionView details
Autonics TK4M-14RN 72×72 PID Temperature Controller RelayPhotoelectric SensorsYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Autonics TK4M-14RN 72x72 PID Temperature Controller Relay Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Autonics is a South Korean maker of sensors and controllers, founded in 1977 as a small engineering business making controllers for looms. It took the Autonics name in 1988 and opened a new corporate headquarters in Busan in 2014. Autonics makes proximity and photoelectric sensors, rotary encoders, temperature controllers, counters, timers and stepper motor systems, with factories in Busan and Yangsan.

Seven Star LLC lists the Autonics E40S6-2500-6-L-5 incremental rotary encoder and supplies Autonics sensors and control devices in Oman and the GCC.

Autonics company profile

Founded 1977, South Korea
Current name Autonics, since 1988
Headquarters Busan, South Korea
Factories Busan and Yangsan
Product families E40 and E50 rotary encoders, PR proximity sensors, BJ photoelectric sensors, TK temperature controllers

Milestones

  • 1977: The company is founded.
  • 1988: Renamed Autonics Corporation.
  • 2014: Opens its Busan headquarters.

Reading the Autonics E40S encoder code

E40S is the 40 mm diameter shaft-type incremental encoder, and the 6 that follows is the 6 mm shaft. 2500 is the resolution in pulses per revolution. The next 6 means six output signals: A, B and Z with their inverted signals. L is a line driver output and the final 5 is a 5 V DC supply. The same 40 mm body is made in hollow shaft form as the E40H and E40HB series.

Where Autonics encoders are used

Servo and spindle feedback, conveyor length measurement, packaging and printing machines.

Ordering Autonics encoders: what we need

Send the complete model string from the label. If it is worn off, give the body and shaft diameter, pulses per revolution, output type, supply voltage and cable or connector style.

Facts checked against Autonics corporate profiles, October 2026.

FAQ

Questions about the Autonics TK4M-14RN 72×72 PID Temperature Controller

Answers from our engineering team on installation, compatibility and integration.

01What size is the Autonics TK4M-14RN?
It is a 72 x 72 mm DIN panel controller with a 68 mm square panel cut-out and about 140 g weight, the large display model of the TK series.
02What supply and output does the Autonics TK4M-14RN have?
It takes 100 to 240 V AC at 50/60 Hz and has a relay control output rated 250 V AC 3 A, plus one alarm relay output.
03Which sensors can the Autonics TK4M-14RN read?
It accepts thermocouples K, J, E, T, B, R, S, N, C, G, L, U and Platinel II, RTDs such as JPt100 and DPt100, and analog signals like 4-20 mA.
04Can the Autonics TK4M-14RN do heating and cooling together?
No, the final N means normal type with one control output; the R and C versions in the last position add a second control output.
05What is the protection rating of the Autonics TK4M-14RN?
The front panel is IP65, and the permitted ambient range is minus 10 to plus 50 degrees C at 35 to 85 percent relative humidity.