When a speed reading must be seen from across a room and also sent to a recorder or a PLC, an indicator alone is not enough. The Autonics MP5W-44 is the largest, most capable format of the MP5 pulse meter family in this manual: a 96 by 48 mm unit with 14 mm high red digits, five NPN comparison outputs (HH, H, GO, L and LL), and a 4 to 20 mA or 0 to 20 mA current output that follows the displayed value. It runs from 100 to 240 VAC and takes pulses up to 50 kHz.

Seven Star LLC is an independent supplier serving Oman and the GCC. This exact code is a frequent request for speed and flow monitoring panels where limit alarms and a transmitted signal are both needed from one pulse source.

Autonics MP5W-44 electrical data

Parameter Value
Series MP5W multi pulse meter, DIN 96 x 48 mm
Output code 4, NPN open collector quintuple plus PV transmission
Comparison outputs HH, H, GO, L, LL as NPN open collector, 30 VDC, 30 mA
PV transmission 4 to 20 mA or 0 to 20 mA, load up to 500 ohm
PV resolution 1/8,000 for 4 to 20 mA, 1/10,000 for 0 to 20 mA
PV response and accuracy 300 ms or less, plus or minus 0.3 percent of full scale at 23 C
Supply 100 to 240 VAC, 50 and 60 Hz
Power consumption 15 VA or less
Sub power supply 24 VDC, up to 30 mA, for the output stage
Display 5-digit LED, characters 7 x 14 mm, range -19999 to 99999
Inputs Solid state 50 kHz, 5 kHz; contact 45 Hz
Measurement accuracy Plus or minus 0.05 percent of reading plus 1 digit
Sensor supply 12 VDC, up to 80 mA
Temperature -10 to 50 C
Protection IP54 front
Weight About 210 g, about 334 g packaged
Panel cut-out 92 x 45 mm

How the outputs of the Autonics MP5W-44 work

The five comparison outputs divide the measured range into zones. HH and LL are the outer alarm limits, H and L are the inner limits, and GO is on while the value lies between them. A conveyor speed monitor could use LL to trip the line when speed collapses, L to give a warning, GO as a healthy signal for the PLC, H for a warning of overspeed and HH for an overspeed trip. All five are open collector transistors that sink up to 30 mA at 30 VDC, so interposing relays are needed for heavy loads.

The analogue output converts the displayed value to a current signal, scaled between two settable display values, which a PLC analogue input, chart recorder or remote indicator can use. The output stage needs the 24 VDC sub supply described in the manual and a load of 500 ohm or less.

How MP5W-44 differs from other MP5 variants

The MP5W line has more output codes than the other sizes. A is a relay quintuple, 1 a relay triple, 2 NPN open collector with BCD output, 4 NPN open collector with current output, 5 the PNP counterpart of 4, 8 NPN with RS485 and 9 PNP with RS485. The MP5W-44 is the NPN member with current output; the MP5W-45 is the PNP equivalent.

Against the smaller MP5Y, the W case has digits that are 7 by 14 mm instead of 4 by 8 mm, a panel cut-out of 92 by 45 mm instead of 68 by 31.5 mm, and a weight of about 210 g compared with 140 g. Both operate on the same 100 to 240 VAC supply for code 4.

Operation modes

The sixteen modes cover frequency, revolutions and speed (F1), passing speed (F2), cycle (F3), passing time (F4), time interval (F5), time differential (F6), ratio and error ratio (F7, F8), density (F9), error (F10), two length measurement modes (F11, F16), interval (F12), accumulation (F13) and addition or subtraction with separate inputs (F14) or phase-difference input (F15). The measuring range in frequency modes is 0.0005 Hz to 50 kHz.

Wiring and connectors

The MP5W uses a connector for outputs: the manual lists a Hirose HIF3BA-20PA-2.54DS plug on the unit with the matching HIF3BA-20D-2.54R socket, and an Autonics I/O cable series CO20-HP sold separately. Power and pulse input wires use the screw terminals, with crimp lugs of 3.5 mm or more and up to 7 mm width. Contact the manufacturer through your supplier for the correct socket or cable if you wish to pre-wire.

Where it is installed

Typical installations include line speed displays with overspeed trips on cranes, conveyors and winders; flow-rate indicators with high and low alarms in water treatment; and fan or pump speed supervision with a 4 to 20 mA feedback signal for a control room. In Oman, utilities and process plants that need a standalone alarm without PLC programming use meters of this kind.

Setup tips

Set the operation mode, the prescale and the five limit values with the front keys. Set the analogue scaling points for the current output. Check hysteresis so that outputs do not chatter around a limit. Keep sensor cables shielded and away from power wiring. The settings are held in non-volatile memory. During commissioning, simulate the limits by feeding a signal generator or by running the machine slowly, and watch the output indicators on the front: each comparison output has its own lamp, so the alarm logic can be proved without connecting the PLC. Check the analogue output with a milliammeter at the low and high scaling points before the signal is connected to a control system, and make sure the receiving input is configured for the same 4 to 20 mA or 0 to 20 mA range. If a limit output seems to chatter, increase the hysteresis setting.

Ordering

Send Autonics MP5W-44 on your RFQ with the quantity. The PNP version is MP5W-45 and the RS485 versions are MP5W-48 and MP5W-49. A terminal cover for the W size can be quoted as an accessory.

Related items you may also need: Autonics BEN5M-MFR Retroreflective Photoelectric Sensor 5 m | Autonics PR18-8DN M18 Inductive Proximity Sensor 8 mm | Autonics E40S6-2500-6-L-5 Rotary Encoder Incremental | All Autonics products.

Documents and quotation

The manufacturer publishes a product manual that covers Autonics MP5W-44, and the PDF is attached to this page for download so your engineers can check wiring, ratings and dimensions before ordering. Please send your RFQ with the part number and the quantity you need, plus the delivery site, and our team will reply with availability and lead time.

Other Models in the MP5 Range

Seven Star LLC supplies models from the MP5 range in Oman and the GCC. Compare the related models below and request a quote for the one that matches your application.

ModelCategory
Autonics MP5S-4N Multi Pulse Meter 48 x 48 mm IndicatorControllers & Data AcquisitionView details
Autonics MP5Y-4N Multi Pulse Meter 72 x 36 mm IndicatorControllers & Data AcquisitionView details
Autonics MP5W-44 Multi Pulse Meter 96 x 48 mm NPN 4-20 mAControllers & Data AcquisitionYou are viewing this model
Datasheets & Documents
  • PDF Datasheet Autonics MP5W-44 Multi Pulse Meter 96 x 48 mm NPN 4-20 mA Datasheet Download
Reviews (0)

Reviews

There are no reviews yet.

How would you rate this product?

It takes about 10 seconds — just tap a star. Your email is never published.

About brand

Autonics is a South Korean maker of sensors and controllers, founded in 1977 as a small engineering business making controllers for looms. It took the Autonics name in 1988 and opened a new corporate headquarters in Busan in 2014. Autonics makes proximity and photoelectric sensors, rotary encoders, temperature controllers, counters, timers and stepper motor systems, with factories in Busan and Yangsan.

Seven Star LLC lists the Autonics E40S6-2500-6-L-5 incremental rotary encoder and supplies Autonics sensors and control devices in Oman and the GCC.

Autonics company profile

Founded 1977, South Korea
Current name Autonics, since 1988
Headquarters Busan, South Korea
Factories Busan and Yangsan
Product families E40 and E50 rotary encoders, PR proximity sensors, BJ photoelectric sensors, TK temperature controllers

Milestones

  • 1977: The company is founded.
  • 1988: Renamed Autonics Corporation.
  • 2014: Opens its Busan headquarters.

Reading the Autonics E40S encoder code

E40S is the 40 mm diameter shaft-type incremental encoder, and the 6 that follows is the 6 mm shaft. 2500 is the resolution in pulses per revolution. The next 6 means six output signals: A, B and Z with their inverted signals. L is a line driver output and the final 5 is a 5 V DC supply. The same 40 mm body is made in hollow shaft form as the E40H and E40HB series.

Where Autonics encoders are used

Servo and spindle feedback, conveyor length measurement, packaging and printing machines.

Ordering Autonics encoders: what we need

Send the complete model string from the label. If it is worn off, give the body and shaft diameter, pulses per revolution, output type, supply voltage and cable or connector style.

Facts checked against Autonics corporate profiles, October 2026.

FAQ

Questions about the Autonics MP5W-44 Multi Pulse Meter 96 x 48 mm NPN

Answers from our engineering team on installation, compatibility and integration.

01What outputs does the Autonics MP5W-44 have?
Five NPN open collector comparison outputs (HH, H, GO, L, LL) rated 30 VDC 30 mA, plus a 4 to 20 mA or 0 to 20 mA current output.
02How big is the display of MP5W-44?
It has five red digits measuring 7 x 14 mm in a 96 x 48 mm case, with a display range of -19999 to 99999.
03What accuracy does the current output have?
The manual gives plus or minus 0.3 percent of full scale at 23 C with a response time of 300 ms or less and a load of 500 ohm maximum.
04What panel cut-out does it need?
A cut-out of 92 mm by 45 mm, with the unit about 89.5 mm deep.
05Is there a PNP version?
Yes. The PNP open collector version with current output is MP5W-45.