Brand: Pepperl+Fuchs
Pepperl+Fuchs NCB5-18GM40-N0 M18 NAMUR Inductive Sensor 5 mm
Description
Pepperl+Fuchs NCB5-18GM40-N0: a 5 mm flush NAMUR proximity switch in an M18 steel body
The Pepperl+Fuchs NCB5-18GM40-N0 is a two-wire inductive proximity sensor for intrinsically safe loops. It is built into a threaded M18 x 1 barrel of stainless steel 1.4305 (AISI 303), measures 40 mm in length and 18 mm in diameter, and detects metal targets up to a rated operating distance of 5 mm when it is mounted flush with the surrounding metal.
Because the NCB5-18GM40-N0 uses a NAMUR output rather than a transistor stage, it does not switch a load. It changes its current draw: a minimum of 3 mA when no measuring plate is present and 1 mA or less when the plate is detected. A downstream switch amplifier or isolating barrier turns that current step into a relay or transistor signal. This is the classic arrangement for valve position feedback, counting and presence detection on plants where the sensor sits close to or inside a hazardous area.
The datasheet lists the part as normally closed in the NAMUR sense, with a 2 m PVC cable in blue and wire end ferrules. It can be used up to SIL 2 according to IEC 61508 and carries an MTTFd of 2040 years at a 20-year mission time with 0 percent diagnostic coverage.
Key features of the NCB5-18GM40-N0
- Rated operating distance sn of 5 mm, assured operating distance sa from 0 to 4.05 mm, actual operating distance 4.5 to 5.5 mm.
- Housing of stainless steel 1.4305 with a PBT sensing face, degree of protection IP66 / IP67.
- All-direction yellow LED showing the switching state, visible from any side of the barrel.
- Short-circuit protection and polarity reversal protection built in.
- Ambient range of -25 to 100 degrees C in operation, -40 to 100 degrees C in storage.
- Two self-locking nuts are supplied with every sensor.
NCB5-18GM40-N0 technical data
| Parameter | Value |
|---|---|
| Part number | NCB5-18GM40-N0 |
| Switching function | Normally closed (NC) |
| Output type | NAMUR, 2-wire |
| Rated operating distance sn | 5 mm |
| Assured operating distance sa | 0 to 4.05 mm |
| Actual operating distance sr | 4.5 to 5.5 mm, typically 5 mm |
| Installation | Flush |
| Reduction factors | rAl 0.35, rCu 0.3, r304 0.74 |
| Nominal voltage Uo | 8.2 V, Ri approx. 1 kOhm |
| Switching frequency | 0 to 400 Hz |
| Hysteresis | 1 to 15 percent, typically 5 percent |
| Current, plate not detected | minimum 3 mA |
| Current, plate detected | 1 mA or less |
| Functional safety | SIL 2, MTTFd 2040 a, TM 20 a, DC 0 percent |
| Ambient temperature | -25 to 100 degrees C |
| Housing / face | Stainless steel 1.4305 / AISI 303, PBT |
| Protection | IP66 / IP67 |
| Cable | 2 m PVC, 6 mm diameter, 2 cores, 0.75 mm2, blue |
| Dimensions | 40 mm long, 18 mm diameter, M18 x 1 |
Where the NCB5-18GM40-N0 is used in Oman and Gulf plants
In oil and gas facilities the NCB5-18GM40-N0 is a common choice for detecting the open and closed end positions of ball and gate valve actuators, usually with a steel cam or a mild steel flag as the target. Its NAMUR current signature is read by a zone-0 or zone-1 isolating barrier in the marshalling cabinet, so the sensor wiring remains an intrinsically safe circuit.
Water and wastewater works use the same device on penstock and sluice-gate stems, on pump coupling guards and on dosing skid levers. In manufacturing and utilities, expect it on conveyors, rotating shafts and hydraulic cylinders where a 5 mm sensing gap is practical. The stainless body tolerates washdown and the heat of a compressor shed better than a plain brass barrel.
How NCB5-18GM40-N0 differs from other NCB / NJ NAMUR variants
Within Pepperl+Fuchs NAMUR cylinders, the number after NCB or NJ is the rated distance and the digits after it are the thread and housing length. The NCB5-18GM40-N0 is the M18 flush body at 5 mm. By comparison, the NCB2-12GM35-N0 is an M12 body with a 2 mm rated distance and a switching frequency of 1000 Hz, while the NJ10-30GM-N is an M30 body with 10 mm distance and only 300 Hz.
Against the plug version NCB5-18GM40-N0-V1, the NCB5-18GM40-N0 has a fixed 2 m cable instead of an M12 connector and a 2040 year MTTFd instead of 1880 years. Choose the cable version when the sensor will be wired directly into a junction box, and the V1 plug when quick replacement matters.
Selection and compatibility notes
Confirm that the isolating barrier or switch amplifier is rated for NAMUR sensors per EN 60947-5-6: the nominal voltage of 8.2 V with 1 kOhm internal resistance is what the barrier input expects. Steel is the reference target; the reduction factors on the datasheet mean aluminium is sensed at about 35 percent of 5 mm, copper at 30 percent and stainless steel 304 at 74 percent of the rated distance.
For hazardous-area use, the NCB5-18GM40-N0 datasheet cites IECEx PTB 11.0037X and ATEX PTB 00 ATEX 2048 X for gas and dust, plus TUV 20 ATEX 8524 X for dust category Dc. Always read the instruction manual for the permitted associated apparatus before installation. Marine approval DNVGL TAA00001A5 and cULus listing are also stated.
Installing and commissioning the NCB5-18GM40-N0
Thread the NCB5-18GM40-N0 into the bracket and lock it with the two self-locking nuts. Because it is a flush type, the surrounding metal may reach the sensing face. Set the gap so the target passes within the assured operating distance of 4.05 mm, which leaves margin for temperature and mechanical play.
Terminate the blue cable on the barrier terminals observing the polarity noted in the connection diagram, and use the supplied ferrule crimps. At commissioning, move the target in and out and confirm the yellow LED follows, then check the barrier output changes state at the expected current threshold.
Maintenance and troubleshooting
A NAMUR sensor has no moving parts. Inspection means checking the sensing face for damage or build-up, confirming the nuts have not loosened under vibration, and inspecting the cable jacket for abrasion. If a loop shows line fault, measure the loop current: a short drives it above the plate-detected band, an open circuit drops it below 1 mA.
Related products and ordering notes
Ask for the plug variant when you want a replaceable M12 connection, or the 2 mm and 10 mm siblings listed above when the sensing gap differs. When you send an RFQ for the NCB5-18GM40-N0, include the quantity, the barrier type and whether you need the cable length shown here. Seven Star LLC is an independent supplier serving Oman and the GCC and is not affiliated with the manufacturer.
Frequently asked questions in brief
The NCB5-18GM40-N0 is a 5 mm flush NAMUR sensor, SIL 2 capable, IP66 / IP67, with 2 m cable. It does not switch a load directly and needs a barrier or amplifier.
Documents and quotation
The datasheet for the NCB5-18GM40-N0 is attached to this page with the full dimension drawing and approval list. To request a quotation, send an RFQ to Seven Star LLC with the part number NCB5-18GM40-N0, quantity and delivery location in Oman or the GCC.
Datasheets & Documents
- Datasheet Pepperl+Fuchs NCB5-18GM40-N0 M18 NAMUR Inductive Sensor 5 mm Datasheet Download
Reviews (0)
How would you rate this product? Cancel reply
About brand
Pepperl+Fuchs is a German manufacturer of industrial sensors and explosion protection equipment, founded in 1945 in Mannheim by Walter Pepperl and Ludwig Fuchs as a radio repair shop. Defective transformers led them into manufacturing, and the company developed its first proximity switch in the late 1950s. Pepperl+Fuchs is headquartered in Mannheim and is a pioneer of intrinsically safe electrical equipment for hazardous areas.
Seven Star LLC lists Pepperl+Fuchs sensors, isolated barriers, power supplies and hazardous-area mobile devices, and supplies them to instrument and automation teams in Oman by exact model designation.
Pepperl+Fuchs company profile
| Founded | 1945, Mannheim-Sandhofen, Germany, by Walter Pepperl and Ludwig Fuchs |
|---|---|
| Headquarters | Mannheim, Germany |
| Ownership | Privately owned (Pepperl+Fuchs SE) |
| Origins | Radio repair workshop that began making replacement transformers |
| Product families | Inductive, capacitive, ultrasonic and photoelectric sensors, rotary encoders, R2000 LiDAR scanners, KFD and HiC isolated barriers, Zener barriers, remote I/O, purge and pressurization systems, Ex-rated enclosures |
Milestones
- 1945: Walter Pepperl and Ludwig Fuchs open their radio repair shop in Mannheim.
- 1958: The first proximity switch is developed (some company sources say 1959).
Pepperl+Fuchs product families on this page
On the interface side there are two systems. The K-System mounts on DIN rail and is represented here by the KFD2-UT2-Ex2 universal temperature converter. The H-System plugs into termination boards and is represented by the HiD2030 SMART transmitter power supply with HART. The PS1000-A6-24.20 is a 24 VDC, 20 A power supply for cabinets. Sensors listed include the NJ2-12GK-SN NAMUR inductive sensor, the R101 retro-reflective photoelectric sensor and the R2000 2-D LiDAR scanner. For field staff there are the Tab-Ex 05 DZ1 tablet for Zone 1/21 areas and the Smart-Ex 03 DZ2 smartphone for Zone 2/22 and Division 2 areas.
Where Pepperl+Fuchs equipment is used
Isolated barriers sit between field instruments in Zone 0 or Zone 1 and the DCS or safety system in refineries, gas plants and chemical works. NAMUR sensors report valve position and machine states in classified areas. Photoelectric sensors and LiDAR scanners work in conveying, packaging, warehousing and vehicle guidance. Ex-rated tablets and phones are carried on operator rounds and maintenance jobs.
Pepperl+Fuchs products we list
Ordering Pepperl+Fuchs parts: what we need
Send the complete model designation as printed on the device, including every suffix; a single letter can change the supply voltage or the output type. Add the part number if the label shows one. For barriers, tell us the field device and signal type, the number of channels and whether the safety loop needs a SIL-assessed module. For mobile devices, state the zone or division and the regional radio version.
Facts checked against Pepperl+Fuchs's own chronicle pages, October 2026.
Browse Pepperl+Fuchs products by category: Sensors & Transmitters, Industrial Computer, Isolator & Barrier, Power Modules.
FAQ
Questions about the Pepperl+Fuchs NCB5-18GM40-N0 M18 NAMUR Inductive
Answers from our engineering team on installation, compatibility and integration.
01What type of output does the Pepperl+Fuchs NCB5-18GM40-N0 have?
It has a 2-wire NAMUR output: current is at least 3 mA with no target and 1 mA or less when the measuring plate is detected, read by a barrier or amplifier.
02What is the sensing distance and how is it mounted?
Rated operating distance is 5 mm, assured 0 to 4.05 mm, and it is a flush type, so surrounding metal may reach the sensing face.
03Can it be used in a SIL loop?
The datasheet states the NCB5-18GM40-N0 is usable up to SIL 2 per IEC 61508 with an MTTFd of 2040 years and a mission time of 20 years.
04What housing and cable does it have?
Stainless steel 1.4305 housing, PBT face, IP66 / IP67, with a 2 m blue PVC cable of 6 mm diameter and wire end ferrules.
05What do I send to quote the NCB5-18GM40-N0 in Oman?
Send an RFQ to Seven Star LLC with the part number, quantity and destination; the datasheet is available on request.